With the illumination switched off, rst press on one of the buttons to switch the illumination on and then continue with the setting. Having pressed the last button,
the illumination will switch off after 2 min.
Menu structure at Basic level
Good
Operational status Basic setting Timeprog. options Param Mode Info
Tech. Read-out
CH prog Set date and time Boiler param Cascade
DHW prog Timeprog. CH Other
Pump prg. Timeprog. DHW
Timeprg. CH
Timep. DHW
CH temp
DHW temp
Units
Language
Restore Defaults
In the table below you nd all sub settings of each parameter.
Water pressure
When the screen shows ‘FILL’ the water pressure is too low. Press, if necessary
the + or - button to read out the water pressure. Please contact your installer/
supervisor to check the installation and top up.
Turning the programs on or off
Proceed as follows:
(Switch on the main power supply switch).
From the standard blue illuminated screen:
1. Press the right arrow button:
Screen displays: Basic settings;
2. Press OK;
3. Press the right arrow button:
Screen displays: CH prog off/on;
4. Press the + (on) or - (off) key:
Screen displays: CH prog on or off;
5. Press OK;
6. Repeat procedure from point 3 onward.
This switches off the functions DHW prog. and
Pump prg. respectively.
7. Press the return button to return to the standard display.
Depending which program is selected the corresponding
symbol will be shown in the display.
In some cases it might be necessary to put the complete boiler out of operation.
The boiler is put out of operation by switching off the three functions (
,
and/or ). The frost protection will remain active. Leave gas supply open.
A.O. Smith recommends leaving the power switch switched on to ensure that the
boiler pump(s) and three-way valve (if available) are automatically activated to
prevent them from getting stuck.
If your heating system is not being used during periods of frost we
advise you isolate the power and drain the boiler and the system. In
this case: close the gas valve.
Error, maintenance and warranty
If a fault is detected the boiler will be blocked. This will be reected, with an E
for Error, a B for Blocking or M for Message and a number code on the display.
You can try to reset the boiler by pressing the Reset key once. If the problem
remains please contact your installer and inform them about the fault and give
them the number code.
If, on the screen the message “Service” appears, the installer must perform maintenance according to the installation and service manual. Please contact your installer.
We advise you to obtain a service contract with your installer for regular maintance and adjustment to keep your boiler safe and in good condition.
If you discover any leaks from the boiler contact your installer.
The casing of the boiler consists of metal and plastic parts which can be cleaned with a normal non abrasive cleaning agent.
Important!
It is in your own interest to register your warranty, visit the website www.aosmithinternational.com/content/product-registration and ll in the Pro-
duct Registration Form. Registering the boiler gives the owner of the boiler supplied by A.O. Smith Water Heaters the right to the warranty which
denes the commitments of A.O. Smith Water Heaters to the owner. You can nd the warranty conditions in the Installation and Service Manual
which is supplied with the boiler.
With the arrow buttons
you can go through the
different chapters.
Press OK to select or to
conrm a change.
With the + and - button
you can increase or
decrease a selected
value.
Back to previous screen
or standard read out:
Press this ‘return-button’.
Basic settingsBasic settings
PARA
factory
setting
DescriptionRange
CH progoffCH-programon/off
DHW progoffDHW-programon/off
Pump prgoffPump program (frost protection)on/off
Timerpr CHoffClock program CHon/off
Timerp DHWoffClock program DHWon/off
CH temp90
Adjusted maximum flow temperature in °C
(only active with connected outdoor sensor & P101=0)
10-90
DHW temp65Adjusted maximum DHW temperature in °C (only visible when DHW is activated)10-80
UnitsSISelection possibility units SI=Europe, Imp(erial)= USASI/Imp
LanguageGBLanguage selection
GB, NL, I, D, F,
PL, TR, DK, E
Restore defaultsReset of the factory settings (dependant of selected level)
Timeprog optionsClock program options
PARA
factory
setting
DescriptionRange
Set date and time
Set Time00:00Actual time setting in hours and minutes
Set DateDD-MM-YYActual date setting day-month-year
Daylight savingEuropeZone for daylight savingOff-Eur-USA
12/24hrs0-24h12-hour (AM/PM) or 24-hour displayAM/PM-24h.
Date formatDD-MM-YYReproduction of date display (DD-MM-YY, MM-DD-YY, YY-MM-DD)
Time prog CH (only visible when NOT OpenTherm or 0-10V)
Day tempT-day 20
Day temperature according heating line in °C
(if outdoor sensor is NOT connected: max flow temp.)
10-30
(10-90)
Night tempT-night 15Night temperature according heating line (Eco) in °C10-30
Select PresetPreset 1Choice for the preselected time programm CH1 or 2
Adjust Timeprog
mo1 off
03:00
See table time programs CH
It is possible to select 4 switch moments (steps of 30 min.) per day.
Choice: day temperature, night temperature, off, - - -
Copy function to next day: after switch moment 4.
Store PresetStore of the adjusted time program for CH
Timepr DHW (only visible when NOT OpenTherm)
Select PresetPreset 1Choice for the preselected time programm DHW1 or 2
Adjust Timeprog
mo1 off
03:00
See table time programs DHW
It is possible to select 4 switch moments (steps of 30 min.) per day.
Choice: on, off, - - -
Copy function to next day: after switch moment 4.
Store PresetStore of the adjusted time program for DW
Param ModeParameter chapter
PARA
factory
setting
DescriptionRange
Boiler param
Boiler parameters
P1321Pump continuously1-2
1:Unit
p
um
p
P1
2 Unit
p
um
p
P1 and installation
p
um
p
P
3
InfoInformation
Cascade
Information of cascade system
T3xx.x°CDHW temperature T3 in external cylinder in °C (if connected and P100 is selected for DHW)
T4xx.x°COutdoor temperature T4 in °C (if connected)
T10xx.x°CTemperature T10 sensor in low velocity header in °C
Boiler
Information of the boiler
T3xx.x°CDHW temperature T3 in external cylinder in °C (if connected and P100 is selected for DHW)
Others
Stand-byxx h Number of hours stand by
Burn. Onxx h Number of running hours with burner on
Servicexx h Number of running hours to go for maintenance interval
Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.
Art des Missbrauchs:
Forenregeln
Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:
Lesen Sie zuerst die Anleitung;
Schauen Sie nach, ob die Frage bereits gestellt wurde;
Stellen Sie die Frage so deutlich wie nur einigermaßen möglich;
Erwähnen Sie was Sie bereits versucht haben um das Problem zu lösen;
Ist Ihr Problem von einem Besucher gelöst dann lassen Sie ihn / sie wissen in diesem Forum;
Falls Sie reagieren möchten, so verwenden Sie bitte das Antworten- Formular;
Da ihre Frage für alle Besucher sichtbar ist, sollten Sie lieber keine persönliche Daten erwähnen.
Neu registrieren
Registrieren auf E - Mails für A.O. Smith Upsilon UB-140 wenn:
neue Frage gestellt werden
neue Handbücher vorhanden sind
Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.
Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.
Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.
Ihre Frage wurde zu diesem Forum hinzugefügt
Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.