EM 50-2 English
OFFSET T2 0.0C
Zone 2 temperature can be calibrated here. With
EF 50-25 H sensor, the temperature shown on the
EM 50-2 display is always the core temperature
of the sensor. For calibration, please see page 13.
OFFSET OUT. 0.0C
Outdoor temperature can be calibrated here. The
temperature, recorded by the ATF outdoor sensor,
can be adjusted so that the exact temperature is
displayed on EM 50-2. Measure the temperature
beside the sensor using a thermometer. Adjust
the necessary oset using the encoder button.
Press OK.
SENSORHEAT AUTO
In auto mode, sensor heating is switched o
during periods when snow melting is active. In
special options or extreme cold weather the sen-
sor heat can be selected on continuously. Select
ON and press OK.
MOIST CTRL ON
The moist control on sensor can be switched o
here. The termostat will only control snow and ice
melting after the set temperature, see SET TEMP.
Select OFF for switching o the moist control and
press OK.
Note that energy consumption/costs will
rise with lacking moisture control.
SENSITIVITY NORM
Sensor sensitivity can be adjusted in 5 steps:
MIN - LOW - NORM - HIGH - MAX. To change
sensitivity, press OK, turn the encoder button to
the desired setting and confirm with OK.
LANGUAGE ENGLISH
Menu language is selectable here. Select your
preferred language and press OK
FACTORY RESET
All EM 50-2 factory settings can be restored here.
Selecting this option deletes all customised set-
tings.
FACTORY RESET
REINSTALL
PASSWORD XXXX
Whether setup failure in startup menu, or new
hardware connection has been done, The primare
setup must be changed in STARTUP menu. Se-
lect PASSWORD and turn the encoder button to
the factory code (1202) The controller will then re-
turn to the startup menu, see STARTUP.
EXIT
Select this option and press OK to return to the
main menu.
Restart
When changing the settings or require a new process start, the EM
50-2 can be restarted in this menu.
RESTART
Restart operation. Keeping your current settings.
The EM 50-2 will go to the initial status display.
Oset calibration
If it is necessary to calibrate the temperature measured by the
GROUND SENSOR sensor, please follow the steps below:
1. Disconnect the sensor from terminals 11 and 12 (sensor heating)
of the EM 50-2.
2. Wait a few hours until the sensor has acquired the same tempera-
ture as the ground.
3. Measure the real ground/sensor temperature and compare it with
the temperature shown on the EM 50-2 display.
4. Program the oset for the sensor concerned to match the dier-
ence between the two temperatures (displayed/real). Adjust the
necessary oset using the encoder button. Press OK.
5. Reconnect the sensor to terminals 11 and 12 of the EM 50-2.
NOTE: With EF 50-25 H sensor, the temperature shown on the EM
50-2 display is always the core temperature of the sensor.
Setup Factory settings Own settings
Application Electric
Zone 1 GROUND SENSOR
Zone 2 OFF
Select scale Celsius
Afterrun time Zone 1 2.00 hours
Afterrun time Zone 2 2.00 hours
Temp. oset Zone 1 0.0°C/0.0°F
Temp. oset Zone 2 0.0°C/0.0°F
Temp. oset ATF 0.0°C/0.0°F
Temperature setpoint Zones 1+2 3.0°C/37.4°F
OFF temperature Zones 1+2 OFF
Sensor heating Zones 1+2 AUTO
Moisture control Zones 1+2 ON
Sensitivity Zones 1+2 NORM
Factory settings
Troubleshooting
By errors in the snow melting system, it is recommendable to
check the setup of the EM 50-2. Activate the menu by pressing the
adjustment knob, press SHOW INFO and readout the programmed
application. By errors in the setup, activate REINSTALL with factory
code 1202.
Check that all connections are placed correctly, and that cables are
fastened in the clamps.
Ice/snow does not melt
Does the display show heat ON in zone 1 / 2?
YES:
o Wait 1-2 hours.
o Check under the snow, if the snow is beginning to melt the
system is OK.
o Check heating cables for defects, bad connections, incorrect
connections.
o It is too cold for snow melting (power/m2) or undersized heating
cables/ water heating system.
NO:
o The temperature is higher than SET TEMP. Adjust SET TEMP to
higher temperature.
o The snow around the ground sensor is melting/drifting snow has
exposed the sensor.
AFTERRUN time must be increased. Alternatively, FORCED
HEAT can be activated.
o Igloo eect around the sensor. The ground sensor has melted
an insulated hollow under the snow. Activate FORCED HEAT or,
alternatively, set MOIST SENSOR to OFF.
o The temperature is lower than the OFF TEMP setting.
Depending on dimensioning, the system has a lower temperature
limit, at which the system can melt the snow. Try melting the
8

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für AEG EM 50-2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von AEG EM 50-2

AEG EM 50-2 Installationsanweisung - Deutsch, Englisch - 8 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info