If the DC voltage continues to increase due to the sun's rays
getting stronger and the mains voltage and mains frequency are
within acceptable limits, a start-up attempt is made. During a start-
up attempt, the inverter stack is switched on, thereby drawing
power from the DC voltage that is present. The inverter output
contactor K7 is open during a start-up attempt. If the load on the
DC voltage causes it to collapse too dramatically during this start-
up attempt, the inverter stack is switched off again and there is a
delay until the next start-up attempt is made.
If the DC voltage does not dip too significantly, the inverter output
contactor K7 closes and power is fed into the mains. The inverter
is now in the "Operation" status.
Day:
During the course of the day, the inverter will remain in the
"Operation" status if the sun's rays are strong enough and no
faults occur. Power is fed into the mains and the inverter output
contactor K7 is closed.
Evening:
As the sun goes down, the power fed into the mains decreases.If
this power falls below a certain value for a certain time, the
operating conditions are no longer met. The inverter stack is
switched off, the inverter output contactor K7 opens and the unit
switches to the "Waiting" status.
Once the "Waiting" status delay has elapsed, the unit switches
back to "Waiting for feed conditions". Although the sun's rays are
not as strong, the DC voltage might still be high enough for a
successful start-up attempt with the inverter stack and the inverter
output contactor K7 being switched on again. However, because
the sun's rays are not as strong, it is unlikely that the operating
conditions will still be met in the "Operation" status. As a result, the
equipment will switch back to the "Waiting" status once a delay
has elapsed. When the equipment switches back to this status, the
delay is extended until the unit switches back to the "Waiting for
feed conditions" status.
The cyclic changes of status "Operation" -> "Waiting" -> "Waiting
for feed conditions" -> "Operation" can take place several times
depending on insolation, the time of year, location and other
conditions (e.g. snow on the PV cells). So that the inverter output
contactor K7 is not overloaded by this cycle of changes, the
"Waiting" status delay is extended every time the unit switches to
this status. This has very little effect on the energy fed in, because
the low levels of insolation mean that hardly any energy is being
generated.
Later in the evening:
Levels of insolation continue to fall. As a result, the DC voltage
also carries on dropping. If the DC voltage drops below a certain
value for a certain time, no more start-up attempts are made. If the
DC voltage continues to drop, the unit switches to the "Night"
status.
Night:
The equipment shuts down all possible loads so that as little
energy as possible is being consumed. The equipment remains in
the "Night" status until the following morning.
33

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für AEG Protect PV 500 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von AEG Protect PV 500

AEG Protect PV 500 Bedienungsanleitung - Deutsch - 136 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info