IMDCFJ. 12.05 6343841_03
Alarms summary table
The units envision two types of malfunction-
ing signals:
• Pre-alarm
• Alarm
The first type is indicated by the flashing
of the red LED on the display, successive
pressing of the bell key allows to display
except for the switch-on of the fixed red
LED. Before rearming the unit, it is recom-
mended to contact the after-sales service.
To rearm the unit, switch it off and back on
again using the stand-by key.
the list of alarms (with index and cause
indicated in the table below). A pre-alarm
remains such for 60 seconds: if after this
time the condition that caused the pre-
alarm has not disappeared, the same
becomes an alarm. The alarms are dis-
played in the same way as the pre-alarms,
ATTENTION:
The pre-alarms can become alarms when:
• A time has passed longer than or equal to 60 seconds, in the pre-alarm condition.
The maximum number of pre-alarms in one hour (five) has been exceeded. In this case, every successive pre-alarm will be dis-
played directly as an alarm, and as such, will stop the machine until the reason for the same is solved.
Code
Alarm
Code
Pre-alarm
Causes Notes
1 101
Compressor magnet circuit breaker
This signal intervenes if the contact relative to the magnet circuit
breaker switch protecting the MTC compressor opens (Table 2,
contact ID1, clamps M7.1 - M7.2, normally closed)
Fan magnet circuit breaker
Pump magnet circuit breaker
2 102 Fan magnet circuit breaker
This signal intervenes if the contact relative to the magnet circuit
breaker switch protecting the MTV fans opens (Table 2, contact
ID6, clamps M7S.3 - M7S.4, normally closed) This code is dis-
played only if the board is used as a board spare part with SW up
to version 3.6.
3 103 High pressure switch
This signal DOES NOT give the state of the high pressure switch
itself but of the compressor switch. The high pressure switch oper-
ates directly on the compressor switches. If the board commands
compressor switch-on and the switch does not become active
after 3 seconds, this signal occurs. This alarm can also be caused
by an operating defect of the return relay from the compressor
switch to the board (indicated as RAP in the wiring diagrams).
This signal occurs if the compressor switch deactivates during
operation. AP (Table 2, contact ID4, clamps M7.7 – M7.8, normally
closed)
4 104
Flow switch
This signal occurs with the opening of the contact relative to the
differential flow switch or pressure switch; this alarm is not relative
for the first 40" from pump start-up. The machine blocks in alarm
mode when the maximum number of flow switch interventions
allowed (expressed by the set_factory parameter (y): default 5)
is exceeded. If the frost protection in standby mode is activated
(and therefore also the pump), the state of the flow switch is also
controlled. FL/PD (Table 2, contact ID2, clamps M7.3 – M7.4, nor-
mally closed)
Water differential pressure switch
5 105 Low pressure switch
This signal intervenes when the contact relative to the low pres-
sure switch opens (compressor intake). BP (Table 2, contact ID5,
clamps M7S.1 – M7S.2)
6 106 No water inlet probe This signal occurs when the water inlet probe is disconnected
7 107 No water outlet probe This signal occurs when the water outlet probe is disconnected
8 108 Water freezing
This signal occurs when the anti-freeze threshold is reached
(set_installer (6) default: 3°C) from the output water temperature.
The pre-alarm state is exited with outlet water temperature tem-
perature exceeding the set_installer (6) + set_factory (J) (default
3+1=4°C).
The anti-freeze alarm is suspended (in heating mode) for a period
of time equal to 3' (set_factory parameter (H)) from compressor
switch on.
9 109 No pressing line probe
This signal occurs when the pressing line gas probe is absent
10 110 High pressing line gas temperature
This signal occurs when the temperature of the pressing line gas
(SGP probe) exceeds the threshold envisioned by the parameter
(set_factory (6), default 135°C). The pre-alarm state is exited with
set_factory (7) temperature (default 135 – 10 = 125 °C)
11 111
Flow pressure transducer
no compressor
This signal occurs when the compressor flow transducer is absent
and the machine is set as heat pump or the presence of the DCP
is set
70

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

aermec-moducontrol

Suche zurücksetzen

  • Ich will den Kontakt M1S-8 für eine externe Störungsmeldung nutzen , welche Möglichkeiten gibt es , vielen Dank im vorraus Eingereicht am 22-6-2021 08:06

    Antworten Frage melden
  • wie kann ich bei aermec modu control den Kontakt M1S-8 nutzen Eingereicht am 22-6-2021 08:02

    Antworten Frage melden
  • Wie stellt man die Anlage Moducontrol von kühlen auf Heizen um? Eingereicht am 21-10-2017 12:53

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Aermec MODUCONTROL wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info