SETTINGS
To be done in the installation phase, only by expert personnel.
Some functions are not compatible with each other and, for
this reason, limits to Dip-Switch configurations have been set.
By turning on or off Dip-Switches inside the thermostat, we
get the following functions:
Sw1 Dip 1 (Default OFF)
Water valve fitted:
- Present, set (ON).
- Absent, set (OFF).
Sw1 Dip 2 (Default OFF)
Position of the water temperature probe:
- Water temperature probe positioned up line from the valve,
set (ON).
- Water temperature probe positioned down line from the
valve, set (OFF).
Sw1 Dip 3 (Default OFF )
Water valve management:
- Optimised, set (ON).
heating mode: valve closure delayed compared to the
turning off of the ventilation;
cooling: valve closure earlier than the turning off of the
ventilation.
- Normal, set (OFF).
Sw1 Dip 4 (Default OFF )
Probe adjustment:
- Fixed adjustment, set (ON).
- Dynamic correction, set (OFF),
calculated on the basis of the water temperature.
NOTES:
*
= In the fan coils with two valves installed in four-pipe systems the installation of a PLASMACLUSTER
®
air purifier is not allowed.
- For the proper functioning of the SA room probe make sure that the Sw2Dip3 is in ON position and the jumper at INT. position.
Sw1 Dip 5 (Default OFF)
Heating mode enabling temperature:
- Reduced, set (ON).
Minimum water temperature 35 °C
- Normal, set (OFF).
Minimum water temperature 39 °C.
Sw1 Dip 6 (Default OFF)
Cooling mode enabling temperature:
- Reduced, set (ON).
Maximum water temperature 22°C
- Normal, set (OFF).
Maximum water temperature 17°C
Sw2 * Dip 1 (Default OFF)
Selection of the type of plant in which the fan coil is included:
- Four-pipe system, set (ON).
- Two-pipe system, set (OFF).
Sw2 * Dip 2 (Default OFF)
Presence of PLASMACLUSTER
®
air purifier:
- Present, set (ON).
- Absent, set (OFF).
Sw2 Dip 3 (Default ON)
Air temperature probe enabling:
- Internal control panel probe,set (ON).
- Probe in fan coil, set (OFF).
Sw2 Dip 4 (Default OFF)
Option not available
ON
OFF
123
4
5
Sw1
6
1
2
3
4
*
*
*
*
Sw2
DIP-SWITCH CONFIGURATION
Water valve present
Water probe upline from the valve
Factory setting
Option not available
Internal command panel sensor
PLASMACLUSTER
®
present
Four-pipe system
Maximum water temperature 22°C in cooling mode
Minimum water temperature 35°C in heating mode
Fixed sensor correction
Optimised water valve management:
Dynamic Probe Correction
Minimum water temperature 39 °C in heating mode
Maximum water temperature 17 °C in cooling mode
Two-pipe system
PLASMACLUSTER
®
not fitted
Probe in the fan coil
Normal water valve management:
Water probe downline from the valve
Water valve not fitted
Sw1
JP1
EXT
INT
Sw2
8

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Aermec PXA E wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info