Operating Instructions - P AC15
Click www .andrews-sykes.com or Call Us Free 0800 2 1 1 61 1
only be determined by the user . However , you should never allow more than two
months to elapse between cleaning. The probable life of the filter will be about one
year and spares ar e available from the supplier of the unit itself. Failure to have filter
fitted during operation will cause serious damage.
The refrigeration cir cuit inside the room unit is fitted with a HIGH and a LOW
pr essur e sensi ng sw itch . The y ar e both m anua lly re- sett able. Nec essar y ac cess is
provided either via the lower fr ont panel or through the control console. A pencil or
screwdriver with gentle pr essure on the knob behind is all that is requir ed to re-set.
HOWEVER, DO NOT A TTEMPT TO RE-SET WITHOUT FIRST DISCOVERING
WHY THE TRIP OCCURRED IN THE FIRST PLACE
Installation
USE THE CHAINS PROVIDED TO SUPPORT THE HEA T EXCHANGER - IT
WOULD BE HIGHL Y DANGEROUS TO SUPPORT THE HEA T EXCHANGER BY
MEANS OF THE FLEXIBLE LINES ALONE.
In operation the room unit is constantly condensing water vapour out of the
atmosphere (r educing relative humidity). This water has to be drained away , An
automatic condensate pump is fitted inside the room unit. The flexible hose outlet
from the condensate pump runs to the outside, inside the flexible sheath and the
condensate is deposited in the base of the heat exchanger , but please remember
that there will also be a degr ee of dripping through the base of the heat exchanger .
HA VE GREA T REGARD FOR THIS CHARACTERISTIC WHEN POSITIONING THE
EXTERNAL HEA T EXCHANGER
The flexible water pipes should be routed so as to avoid any possibility of kinking
or unnecessary restrictions to the flow of water inside. Also, r emember that plastic
and rubber becomes much more flexible when warm and. as a r esult, much more
susceptible to distortion.
Machine Link-Up
Ensure the mains supply lead to the r oom unit is disconnected, A 5m (extendable
to 30m) line set to connect all services between the room unit and the external
heat exchanger will have been suppled. The water pipe connections are by means
of ‘quick connect couplers’ . These are simple ‘push-on’ connectors which,
when disconnected (after pulling back sprung loaded locking ring), re-seal the
water system on either side. The complete system will have been filled with the
necessary amount of water/ antifreeze prior to its arrival on site. A water pr oof 3
pin quick connect electrical coupler (push fit with screw lock ring, hand tight only),
and condensate drain pipe coupler 6mm clear polythene (push fit), should also be
connected. Having made the couplings, the system is operational immediately .
Room W ater Levels
The water system in the room unit will be to the corr ect level when delivered.
However if for some reason the level has fallen, antifreeze (33%) and water will have
to be added. The header tank filler and level indication is located to the rear of the
room unit and can be accessed by r emoving the two screws holding the security
plate over the filter tank cap. Ensure the machine is running in cooling mode
before r emoving the header tank cap, and as with all the pressure caps, r emove
slowly . It is recommended that a mixture, by volume, of one part antifr eeze to two
parts water is utilised, this will prevent fr eezing down to an external temperature
of -20C/-5F . The appr oximate total volume of both the available systems, large or
small room unit with external heat exchanger and lines is as follows.
This unit MUST be transported and operated in the upright position at all times.
Electrical Supply
WARNING! As standar d this unit requires a 13 amp fused electrical supply rated at
230 volts. -1N, 50Hz.
The unit will operate from a standar d 13A wall socket. The size of any extension
cable that may be 2-5mm2 minimum up to a maximum length of 10 metres. For
longer lengths 4mm² cable must be used. If the cable is on a ‘cable drum’ then
ensure that it is completely unwound; serious complications will occur otherwise.
System Description
The system comprises a room unit cooling section, an external heat exchanger
and the two are inter connected by means of a flow and return water pipe and
an electrical supply to the heat exchanger fan. The room unit is fitted with an
automatic condensate disposal pump which discharges the condensate via a small
plastic pipe into the base of the external heat exchanger and all interconnecting
pipes and electrics are enclosed in a flexible plastic sheath. In addition, both ends
of each pipe are fitted with ‘quick connect’ couplings that open on coupling but
reseal to become water tight on disconnect.
Airflow
The angled air outlets at the top of the room unit ar e fitted with air grilles that allow
the angle of air outlet to be adjusted vertically and horizontally and, in conjunction
with the fan speed control switch, the air velocity and dir ection can be carefully set
up to obtain maximum coverage of the area being cooled without causing drafts.
Care should be taken to avoid outlet air being obstructed as this will cause the air
to ‘eddy’ around the unit r esulting in recirculation and short/inaccurate cycling of
the machine. Ideally , cold air should be directed to create a ‘blanket’ all acr oss the
ceiling area allowing natural convection to dr op the air over the whole area at very
low velocity .
Siting
Ideally , the room unit should be positioned equidistant along he shortest wall in the
room blowing down the length of the r oom. Of there is more than one unit in the
same area, then they would normally be positioned side by side, and equidistant
along the long wall, all pointing in the same direction. Sometimes it may be
filler cap
necessary to position units around the perimeter of an ar ea but, in this case, great
care should be taken to avoid one unit blowing cold air straight into another which
will adversely affect the machine operation. Good and corr ect air flow is, perhaps,
the single most important aspect of satisfactory applying portable air conditioners.
If in doubt seek the advice of your supplier .
The heat exchanger must stand external to the area being cooled and, preferably ,
in the outside atmosphere. It can stand fr eely on a flat surface or may be hung in
the upright position, from a window-sill, balcony etc (see fig. 1).
1. Revolve thermostat knob fully
CLOCKWISE to the number ‘8’ position
2. Plug in the room unit mains cable, and
switch on the electricity , red mains light
will illuminate.
3. Select ‘Fan Only’ with the mode switch.
The fan will start.
4. Select ‘Fan Speed’ with the fan speed
switch, high or low depending on air
velocity required.
5. Select ‘Cooling’ with the mode switch,
and revolve the thermostat knob fully
ANTI-CLOCKWISE to he number ‘1’
position. If fitted the external heat
exchanger fan and the water pump in
the room unit will start. After a delay of
10 mins the green ‘Cooling’ light will
illuminate and the machine will proceed
to cool the air .
Monitor the room temperature and when it has r educed to the desired level, very slowly
revolve the thermostat knob back, clockwise until the green ‘Cooling’ light goes out. The
room unit will now control the r oom temperature cooling automatically at this setting.
Fig. 1
Fig. 2