TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
No additional charge of compressor oil is necessary.
L Tot. = Total tubing length (L1 + L2 + L3...)
Ln = Maximum tubing length of a single indoor unit (n=1,2,3...)
L = Keep Emix tubing as short as possible (MAX. 10/12m)
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 “ - 3/8” = 15g/m
For tubing 1/4 “ - 1/2” = 20g/m
For tubing Emix (1/2”) = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4, H5, H6)
LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)