702741
3
Zoom out
Zoom in
Vorherige Seite
1/10
Nächste Seite
3
2. If Inputs 2,3 or 4 or even 5, 6, 7 and 8 are used, they
must be within the ATS1290 I/O range. If they are out
of range, they are not available.
3. If some AD044 inputs are not used, the linked zone
input in the ATS control panel must be programmed
as disabled (default).
4. If some AD044 outputs are not used, the linked output
in the ATS control panel must not be programmed
(default).
Refer also to the ATS1290 manual for the direct link to the
zone number (control panel).
MEMORY LOCATION MAP
Every PID device has its own characteristics concerning
related I/O lines or certain functionality of the device.
A total of 16 memory locations are reserved to configure
the PID devices. Only the first nine are normally user
configurable. This depends on the functionality of the
particular device.
For the AD044 external PID interface only memory locations
3 and 5 matter.
On Memory Location 3, the zone type can be configured for
each input to Single EOL, Double EOL (default) or the zone
can be switched off (the status will always be “Normal”).
On Memory Location 5, the output supervision can be
enabled (default) or disabled for each output.
MEMORY LOCATION MAP FOR AD044
Location Function Decimal values Binary values
3 Zone types
For example:
0 = All zones are Off
85 = All zones are Single EOL
170 = All zones are Double EOL (default)
Zone 4 Zone 3 Zone 2 Zone 1
Bit 7-6 Bit 5-4 Bit 3-2 Bit 1-0
00 = Zone is Off
01 = Single EOL
10 = Double EOL (default)
11 = Undefined
5
Supervision
outputs
For Example:
0 = All Output Supervisions disabled
15 = All Output Supervisions enabled (default)
Output 4 Output 3 Output 2 Output 1
Bit 3 Bit 2 Bit 1 Bit 0
0 = Disabled
1 = Enabled (default)
ZONE TYPE
Input loop
resistance
Status ATS control panel
Double EOL
Status ATS control panel
Single EOL
<20 ohm Short Short
47K Normal Normal
94K Alarm Open
> 1Meg ohm Open Open
TECHNICAL SPECIFICATIONS
Bus protocol.........................................GE Interlogix Point ID
Bus voltage........................................................ 12 V or 24 V
External power supply ...................12/24 V (see Note below)
Current consumption from bus ...................................290 µA
Unit load for DGP ................................................................ 1
Address range .......................................................... 0 to 255
Max Current Outputs ......................................500 mA (each)
Single EOL resistor Inputs ................................ 47 k +/- 5%
Double EOL resistors Inputs........................2 x 47 k +/- 5%
EOL resistors Outputs ................................................. 47 K
Category........................................................................... I/O
Device type........................................................................ T1
Note: The auxiliary power output of closest panel or DGP can
also be used.
3

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Aritech AD044 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info