Operation
Manual
Operation Manual - GB
GB
www.atmos.cz
GB - 3
Contents
1. Application 5
2. Technical description 5
Layout of the instrument panel 6
3. Technical specifications 7
Captions for the diagrams of the boilers 8
Technical specifications 8
Diagrams of the boilers 9
Sections of the D14P, D21P and D25P boiler 9
4. Accessories delivered with the boiler 10
Automatic removal of ash from the boiler body 10
5. Fuel 11
6. Boiler foundations 11
7. Type of environment and location of the boiler with the burner in the boiler room 12
8. Chimney 12
9. Flue gas duckt of the boiler 13
10. Fire protection within the installation and use of heat appliances 13
11. Connection of boilers to the electric mains 14
12. Electric wiring diagram of the electro-mechanical control for the D14P, D21P and D25P
boilers without an exhaust valve with a 5-pin connector
15
13. Obligatory ČSN EN standards for the design and installation of boilers 16
14. Selection and method of connection of control and heating-system elements 16
15. Protection of the boiler from corrosion 17
16. Basic connection diagram of the boiler with an equalizing tank and burner
control by the TS and TV sensor 17
17. Diagram of prescribed connection of the boiler with an equalizing tank
and the ACD01 control unit 18
18. Connection diagram of the boiler with Laddomat 21 18
19. Laddomat 21 19
20. Thermoregulatory valve 19
21. Operation instructions 20
Preparation of boilers for the operation 20
22. Burner connection for the D14P, D21P and D25P boilers 21
23. Boiler system with an external storage container and conveyor 21
24. Boiler room with a large built-in pellet storage 22
25. Cleaning of the boilers and ash removal 23
26. Maintenance of the heating system, including boilers 24
27. Operation and supervision 24
28. Možné závady a způsob jejich odstranění 24
29. Spare parts 25
Replacing the door sealing cord 25
Adjusting the door hinges and closures 26
30. Environment protection 26
Disposal of the boiler after the end of its service life 26
GUARANTEE CONDITIONS 27
RECORD OF INSTALLATION OF THE BOILER AND BURNER 28
ANNUAL INSPECTIONS RECORDS 29
RECORDS OF GUARANTEE PERIOD AND POST-GUARANTEE PERIOD REPAIRS
30
GB
www.atmos.cz
4 - GB
Operation Manual - GB
HOPING YOU WILL BE SATISFIED WITH OUR PRO-
DUCT WE RECOMMEND YOU TO OBSERVE THESE
MAIN PRINCIPLES, IMPORTANT FOR THE SERVICE
LIFE AND PROPER FUNCTIONING OF THE BOILER
1. The installation, lighting of the test fire and training of the operators shall be performed by an
installation company trained by the manufacturer, which shall also fill in the boiler installati-
on record (page 28).
2. When using pellets for heating only use high-quality fuel with the diameter of 6 - 8 mm, made
of soft wood without bark and contaminants (white pellets).
3. During fuel combustion substances are produced that may damage the boiler body. Therefore,
the boiler must be equipped with Laddomat 21 or a thermo-regulation valve to maintain the mi-
nimum temperature of return water to the boiler of 65°C.
The operation temperature of the water in the boiler must be in the range of 80-90°C.
4. Each circulation pump in the system must be controlled by a separate thermostat so that the mi-
nimum temperature of return water can be guaranteed.
5. We recommend you to use the boiler in a system with one equalizing tank the volume of which should
be 500 - 100 l to achieve a higher service life of the pellet burner and lower fuel consumption.
CAUTION - If the boiler is equipped with Laddomat 21 or a hot-water thermo-regu-
lation valve - 60°C and an equalizing tank (see the attached diagrams), the boiler body
is subject to an extended guarantee of 36 months instead of 24 months. The guarantee
period of the other parts remains unchanged. If these principles are not observed, the
service life of the boiler body may be considerably reduced due to low-temperature
corrosion.
Operation Manual - GB
GB
www.atmos.cz
GB - 5
1. Application
ATMOS D14P, D21P and D25P hot-water boilers are designed for convenient heating of family
houses, holiday homes and other buildings with pellets. For the heating you can use high-quality
wooden pellets with the diameter of 6 to 8 mm. The boiler is not intended for burning of wood,
sawdust and minor wood waste.
2. Technical description
The boilers are designed in such a way that in their left or right side an ATMOS A25 pellet burner
with a conveyor is installed that is attached to a boiler frame with an 18 x 32 mm sealing cord with the
use of screws. The boiler body is made as a weldment of steel sheets with the thickness of 3-6 mm.
It consists of a combustion chamber that is equipped in its top part with a three-tube exchanger with
inserted decelerators that increase efficiency. In the bottom part of the boiler there is a large ash pan.
The front part of the boiler is equipped in its top part with a cleaning door behind which a stainless-
steel screen ensuring high quality of fuel combustion with high efficiency is inserted. The boiler
body is insulated from the outside with mineral felt located under the sheet-metal covers of the outer
boiler jacket. In the top part of the boiler there is a panel with the main switch, the automatic deashing
switch (if installed), the switch of the pellet burner, an operation (control) thermostat, a pump thermo-
stat, a safety thermostat, a thermometer and a 6.3A fuse. In the bottom right part of the boiler there is
a blind flange for additional installation of automatic ash discharge. The boiler is not equipped with a
cooling loop against overheating as thanks to the small quantity of fuel in the burner there is no risk
of boiler overheating in case of a power supply failure.
Boiler with an ATMOS A25 burner, a 500 l fuel container and a 1.5 m conveyor.
GB
www.atmos.cz
6 - GB
Operation Manual - GB
Layout of the instrument panel
1. Thermometer
2. Main switch 7. 6.3A fuse - T6, 3A/1500 - type H
3. Control thermostat (of the boiler) 8. Place for an electronic control unit (92x138 mm)
4. Pump thermostat 9. Automatic deashing switch
5. Safety thermostat 10. Burner switch
Description:
1. Thermometer - monitors the output temperature of the boiler water
2. Main switch - allows you to switch off the whole boiler if necessary (restart the pellet burner)
3. Control thermostat - control the operation of the pellet burner by the output temperature of the
boiler water
4. Pump thermostat - it is designed to switch the pump in the boiler circuit (set to a temperature of 70-80°C)
5. Irreversible safety thermostat - it serves as protection of the boiler from overheating in case of a
failure of the control thermostat or as an indicator of exceeding of the emergency temperature - after
exceeding of the emergency temperature it must be reset
7. Fuse (6.3 A) - protection of the electronic unit of the pellet burner
8. The place for an electronic control unit of the heating system can be tted with any control unit that match-
es the opening (92x138 cm), e.g. ACD01. The electric harness is already prepared for its power supply.
9. Automatic deashing switch - it is used to switch off deashing for the purpose of emptying of the
auxiliary ash pan and restart of automatic deashing. By turning the switch off and on you will ac-
tivate the deashing module in such a way that it will stop emitting the warning sound and start the
automatic deashing operation.
10. Burner switch - it is used to start the burner and to stop it (initiate the burn-down process) before
cleaning of the boiler.
ČERPADLO / PUMP
KOTLOVÝ / OPERATING
3
8
4
5
7
9
10
Operation Manual - GB
GB
www.atmos.cz
GB - 7
3. Technical specifications
ATMOS boiler type D14P D21P D25P
Boiler output kW 4-14 4-19,5 7 -24
Heat-delivery area m
2
1,7 1,7 2
Fuel shaft volume dm
3
88 88 105
Filling opening dimensions mm 270x450 270x450 270x450
Prescribed chimney draught Pa 16 18 22
Max. working overpressure of water kPa 250 250 250
Boiler weight kg 231 231 254
Exhaust orifice diameter mm 152 152 152
Boiler height mm 1207 1207 1207
Boiler width mm 620 620 620
Boiler depth mm 768 768 868
Ingress protection of the electric part IP 20
El. power input - on startup
- in operation
W
522
42
522
42
522
42
Boiler efficiency % 90,3 90,2 90,2
Boiler class 3
Flue gas temperature at the nominal
output (pellets)
°C 127 147 151
Weight flow of flue gas at the nominal
output (pellets)
kg/s 0,011 0,015 0,018
Prescribed fuel
high-quality pellets with the diameter of 6 - 8 mm and the
calorific value of 15 - 18 MJ/kg
Average consumption of fuel - pellets
- at the nominal output
kg.h
-1
3,5 4,5 5,4
Water volume in the boiler l 56 56 62
Hydraulic loss of the boiler mbar 0,18 0,18 0,19
Minimum volume of the equalizing tank l 500 500 500
Mains voltage V/Hz 230/50
The prescribed minimum temperature of return water in operation is 65°C.
The prescribed operation temperature of the boiler is 80-90°C.
GB
www.atmos.cz
8 - GB
Operation Manual - GB
Captions for the diagrams of the boilers
Technical specifications
1. Boiler body
2. Cleaning door
3. Ash pan
for D14P, D21P (code: P0097)
for D25P - (code: P0080)
4. Control panel
5. Frame screen
6. Door filling - Sibral - large (code: S0263)
7. Door gasket, 18 x 18 mm (code: S0240)
8. Closure (code: S0212)
9. Decorative nut (code: S0413)
10. Lid of the burner opening - plate + insulation
(code: S0275)
11. Cleaning lid of the smoke channel
12. Tube plate decelerator
13. Stainless-steel screen of the combustion
chamber
for D14P (P14) - (code: S0936)
for D21P, D25P (P21, P25) - (code: S0937)
14. Blind flange for installation of automatic
deashing
15. Thermometer (code: S0041)
16. Main switch (code: S0091)
17. Control (boiler) thermostat (code: S0021)
18. Pump thermostat (code: S0023)
19. Safety thermostat (code: S0068)
20. Fuse T6,3A/1500 - typ H
21. Double switch of automatic deashing and the
pellet burner (code: S0098)
K - flue gas orifice
L - water outlet from the boiler
M - water inlet to the boiler
N - socket for the filling tap
Dimensions
D14P D21P D25P
A
1207 1207 1207
B
570 570 670
C
620 620 620
D
801 801 801
E
152 152 152
G
215 215 215
H
934 934 934
CH
221 221 221
I
221 221 221
J
6/4” 6/4” 6/4”
Operation Manual - GB
GB
www.atmos.cz
GB - 9
Diagrams of the boilers
Sections of the D14P, D21P and D25P boiler
GB
www.atmos.cz
10 - GB
Operation Manual - GB
4. Accessories delivered with the boiler
Steel brushes with accessories 1 piece
Poker for cleaning of the boiler body 1 piece
Poker for easy cleaning of the combustion chamber of the pellet burner 1 piece
Filling tap 1 piece
Operation and maintenance manual 1 piece
Automatic removal of ash from the boiler body
As an accessory for every pellet boiler produced after April 1, 2010
(from the serial no. 209500 on) you can equip the boiler with au-
tomatic ash removal from the boiler body to an additional ash pan
that only needs emptying once every 3 to 45 days depending on the
quality of pellets and heating intensity. This automatic device uses
a worm conveyor with a gearbox to remove ash from the chamber
under the burner in regular intervals two times a day for one minute
or on the basis of another setting in the deashing module, which is
installed under the boiler hood. You can repeat the cycle any time by
turning off and on the switch /20(15)/ on the boiler. When the ad-
ditional ash pan is completely full, the ash removal device (worm) will be automatically switched off and
the deashing module will start to emit a sound signal. You can restart the device after cleaning (emptying)
of the additional ash pan by merely turning off and on the switch /20(15)/ on the boiler for 5 seconds.
The automatic deashing system does not require any special operation; you only need to
empty the additional ash pan in regular intervals that is attached with two securing clips
with a safety pin to the boiler, which must be properly snapped during operation of the
boiler to prevent the deashing system from releasing and the ash from getting to the boiler
room. You must also properly tighten and snap the body of the automatic ash removal sys-
tem and the lid of the entire additional ash pan top prevent ash from being pushed to the
boiler plant. When installing this system follow the installation instructions supplied with it.
CAUTION - The deashing system for the D14P, D21P and D25P boilers is not the same as for the
D15P and D20P boilers and is sold separately under a different code. The recommended additional
ash pans with the volume of 28 and 67 l are the same.
Operation Manual - GB
GB
www.atmos.cz
GB - 11
5. Fuel
The prescribed fuel are high-quality pellets of Ø 6 - 8 mm and the length of 10 - 25 mm and
the calorific value of 16 - 19 MJ/kg
-1
. Such pellets are considered as high-quality pellets that do not
disintegrate into sawdust and are made of soft wood without bark and other pollutants (white pellets).
We also recommend you to burn pellets without biological additives that reduce burning-down of the
fuel and increase ash production.
6. Boiler foundations
Boiler type (mm) A B
D14P, D21P
700 700
D25P
700 800
High-quality wooden pellets - white without
black dots (bark)
Poor-quality wooden pellets - dark
with bark (with black dots)
We recommend you to make concrete (metal-
lic) foundations for the boiler.
GB
www.atmos.cz
12 - GB
Operation Manual - GB
7. Type of environment and location of the boiler with the
burner in the boiler room
Boilers with a pellet burner may be used in the AA5/AB5 basic environment in accordance with
the ČSN3320001 standard. Boilers must be installed in a boiler room with guaranteed sufficient sup-
ply of combustion air. It is unacceptable to locate boilers on residential premises (incl. corridors). The
cross-section of the opening
for supply of combustion air
to the boiler room must be at
least 350 cm
2
for boilers with
an output of 15 - 45 kW.
1. Chimney
2. Flue gas duct
3. Boiler
4. A25 burner
5. External conveyor
6. Bin (500 l)
8. Chimney
A boiler with a burner must always be connected to the chimney vent with consent of the
responsible chimney maintenance company. The chimney vent must always produce sufficient
draught and exhaust flue gas to the free atmosphere in virtually all operation conditions. For proper
function of boiler the separate chimney vent must be properly dimensioned as the combustion, out-
put and service life of the boiler depends on its draught. The draught of a boiler directly depends
on its cross-section, height and roughness of the inner wall. No other device may be connected to the
chimney to which a boiler is connected. The diameter of the chimney must not be smaller than the
outlet on the boiler (min. 150 mm). The chimney draught must achieve prescribed values (see the
technical specifications in the boiler manual). However, the boiler must not be excessively high so as
not to reduce the efficiency of the boiler and not to disturb its combustion (tear the flame). In case of
too strong draught install a throttling flap or draught reducer in the flue gas duct between the boiler
and the chimney.
Guideline values of dimensions of the chimney cross-section:
20 x 20 cm height 7 m
Ø 20 cm height 8 m
15x15cm height 11 m
Ø 16 cm height 12 m
The exact determination of chimney dimensions is defined by the ČSN 73 4201 standard.
The prescribed chimney draught is specified in the “Technical data” chapter of the manual of the
particular boiler.
Operation Manual - GB
GB
www.atmos.cz
GB - 13
9. Flue gas duct of the boiler
The flue gas duct from the boiler must lead to the chimney vent. If the boiler cannot be connected
directly to the chimney vent, the corresponding flue gas duct adapter must be as short as possible with
regard to the particular conditions, but not longer than 1 m, without additional heating surface and it
must rise towards the chimney. Flue gas ducts must be mechanically strong and leak-proof for flue
gas and cleanable inside. Flue gas ducts must not lead throu-
gh other owners‘ residential or commercial units. The inner
cross-section of the flue gas duct must not be larger than the
inner cross-section of the smoke uptake and must not get
narrower towards the chimney. The use of smoke elbows is
not suitable. Designs of passages of flue gas ducts through
structures of flammable materials are defined in Annexes 2
and 3 of ČSN 061008 and are mainly suitable for mobile
units, wooden huts, etc.
1 - Flue gas thermometer
2 - Cleaning opening
3 - Throttling flap (draught reducer)
INFO -
In case of too strong draught of the chimney install a throttling flap /3/ or a draught
reducer in the flue gas duct, see the ATMOS price list.
10. Fire protection within the installation and use of heat appliances
Extract from ČSN 061008 - Fire safety of local appliances and sources of heat
Safe distances
On installation of an appliance the safe distance from building materials must be maintained, at least
200 mm. This distance is valid for boilers and flue gas ducts located near flammable materials of the
B, C1 and C2 flammability class (the flammability class is specified in tab. no. 1). The safety distance
(200 mm) must be doubled if boilers and flue gas ducts are located near flammable materials of the
C3 class (see tab. no.1). The safety distance must be doubled if the flammability class of flammable
material is not evidenced. The safety distance may be reduced to a half (100 mm) if you use a non-
-flammable heat insulating panel (asbestos panel) with the thickness of at least 5 mm, located 25 mm
from the protected flammable material (flammable insulation). A shielding panel or protective screen
(on the protected object) must exceed the outline of the boilers (incl. flue gas ducts) at each side by
at least 150 mm and the top surface of the boiler by at least 300 mm. A shielding panel or protective
screen must also be used to protect fixtures of flammable materials if the safe distance cannot be
maintained (e.g. in mobile units, huts, etc. - more details in ČSN 061008). The safety distance must
also be maintained in case of installation of fixtures near boilers.
If boilers are located on a floor of flammable materials, they must be installed on a non-flam-
mable, heat-insulating pad, exceeding the ground plan at the side of the feeding and ashpan opening
GB
www.atmos.cz
14 - GB
Operation Manual - GB
by at least 300 mm before the opening - at the other sides by at least 100 mm. As non-flammable, heat
insulation pads you can use all materials of the A flammability class.
Tab. 1
Flammability classes of build-
ing materials and products
A - no flammability
granite, sandstone, concrete, brick, ceramic tiles, mortar, fire-resist-
ant plastering, etc.
B - difficult flammability
Akumin, Izomin, cemented fibreboard, Lignos, panels of basalt felt,
fibreglass panels, Novodur
C1- poor flammability
hardwood (oak, beech), hardboard panels, plywood, Sirkolit, Wer-
zalit, hardened paper (Formica, Ecrona)
C2- medium flammability
softwood (pine, larch, spruce), chipboard and cork panels, rubber
flooring (Industrial, Super)
C3- high flammability
Fibreboard panels (Hobra, Sololak, Sololit), cellulose materials,
polyurethane, polystyrene, polyethylene, lightened PVC
WARNING - In circumstances leading to the danger of transient ingress of flammable gases
or vapours and during work that might result in a temporary risk of a fire or explosion (e.g.
gluing of linoleum, PVC, etc.) the boilers must be put out of operation in time before the
occurrence of the danger. No objects of flammable substances may be put on the burner
and boiler in a smaller distance than the safe distance from them (more - see ČSN EN
13501-1).
11. Connection of boilers to the electric mains
The boilers are connected to 230 V, 50 Hz mains with a mains cable without a plug. The mains
supply cable is of the M type and in case of repair it must be replaced with the same type by the ser-
vicing organization. Boilers must be connected to the mains by a qualified person in accordance with
valid regulations of the particular country.
CAUTION - The mains cable must not be equipped with a plug (designed to be connected
to a socket). It must be connected in a fixed way to a switchboard or junction box to avoid
confusion of the conductors.
Operation Manual - GB
GB
www.atmos.cz
GB - 15
12. Electric wiring diagram of the electro-mechanical control for
the D14P, D21P and D25P boilers without an exhaust valve
with a 5-pin connector
1 2 3 4 5 6 7 8 9 10 11 12

M
M

M

R


vyp2-1
vyp2-4
vyp2-2
vyp2-5
1 2 4 5






poj-Cpoj-1
FUSE 6,3 A
SICHERUNG 6,3 A
POJISTKA 6,3 A



L2
L1
N

R(L3)



L
N
HLvyp
SNvyp
HNvyp
SLvyp
1 24 5









 


t
PE
T-C
T-2
T-1



t
PE
PT-1
PT-C



L
N
230V/50Hz






A
























a+
b-




B










C
D



F
E
G
G







A



B
C
D
E
F





















L
N
t
BT100-L2
BT100-L1



BT100-N1
BT100-N2




GB
www.atmos.cz
16 - GB
Operation Manual - GB
13. Obligatory ČSN EN standards for the design and installa-
tion of boilers
ČSN EN 303-5 - Central heating boilers using solid fuel
ČSN 06 0310 - Central heating, design and installation
ČSN 06 0830 - Safety devices for central heating and hot water preparation
ČSN EN 73 4201 - Designing of chimneys and flues
ČSN EN 1443 - Chimney structures - General requirements
ČSN 06 1008 - Fire safety of local appliances and sources of heat
ČSN EN 13501-1 - Fire classification of construction products and building structures - part 1
ČSN EN 1264-1 - Floor heating - Systems and components - Definitions and marking
ČSN EN 1264-2 - Floor heating - Systems and components - Heat output calculation
ČSN EN 1264-3 - Floor heating - Systems and components - Design
ČSN EN 442-2 - Heating elements - Tests and their evaluation
Standards for evaluation of conformity and other technical standards:
ČSN EN ISO 12100-1:2004/A1:2009, ČSN EN ISO 12100-2:2004/A1:2009, ČSN EN 953+A1:2009,
EN ISO 11202: 2009, EN ISO 3746:2009, ČSN ISO 1819:1993, ČSN EN 60335-1 ed.2:2003
CAUTION - The installation of the boiler must always be carried out in accordance with a
prepared design. The boiler may only be installed by persons trained by the manufacturer.
14. Selection and method of connection of control and heating-
system elements
The boilers are delivered to the user with the basic control of the boiler output, which complies with
the requirements for the heating comfort and safety. The control ensures the required output tempe-
rature of the boiler water (80-90°C). The boilers are equipped with a built-in thermostat controlling
the pump in the boiler circuit. The connection of these elements is indicated in the electric wiring dia-
gram. Each pump in the system must be controlled with a separate thermostat to avoid cooling of the
boiler at the return line below 65°C. If the boiler is installed without a storage or equalizing tank, the
pump in the circuit of the heated building must be controlled by a separate thermostat or electronic con-
trol unit to only run when the pump in the boiler circuit is running. If you use two thermostats, either for
the control of one pump, set the thermostat that controls the pump in the circuit of the heated building
to the value of 80°C and the thermostat that controls the pump in the boiler circuit to the value of 75°C.
You can also control both the pumps with one thermostat at the same time. If there is very good spon-
taneous (gravity) circulation of water between the boiler and the system, which extends the time neces-
sary for the boiler to reach the required temperature, you can reduce the setting of the thermostat of the
boiler circuit pump to a lower temperature. The required water temperature for the building is always
set with the use of a three-way mixing valve. The mixing valve may be controlled manually or with an
electronic control unit, which will contribute to more comfortable and more economical operation of
the heating system. The way of connection of all the elements is always determined by the designer
in accordance with the specific conditions of the heating system. The electric installation related to
the sufficient equipment of the boilers with the above mentioned elements must be implemented by a
qualified person in accordance with valid ČSN EN standard. If you install the ACD01 electronic control
unit, follow the instructions in the operation manual of this unit. Connect this control unit in the boiler
in accordance with the electric wiring diagram in this manual. Never switch off the ACD01 electronic
control unit outside the heating season (with the main switch on the boiler)!
Operation Manual - GB
GB
www.atmos.cz
GB - 17
For the installation of the boiler we recommend you to use an open expansion vessel;
however, it may also be closed if permitted by the legislation of the particular country.
You must install the boiler in such a way to avoid its overheating and consequent dam-
age even in case of a power supply failure.
During the installation support the back part of the boiler to raise it by 10 mm to fa-
cilitate its rinsing and bleeding.
For the control of the heating system we recommend the following controllers:
a) ATMOS ACD 01 - equithermal control set for solid fuel boilers
b) KOMEXTHERM, Prague phone: +420 235 313 284
c) KTR, Uherský Brod phone: +420 572 633 985
d) Landis & Staefa phone: +420 261 342 382
15. Protection of the boiler from corrosion
The prescribed solution consists in the installation of the boiler with Laddomat 21, or a thermo-
-regulation valve, which allows you to create a separated boiler and heating (primary and secondary)
circuit to ensure the minimum temperature of return water to the boiler of 65°C. The higher the
return water temperature is, the lower you will keep condensation of tar and acids that are harmful for
the boiler body. The output water temperature of the boiler must be permanently in the range
of 80 - 90°C. The flue gas temperature must not drop below 110°C during normal operation. A low
flue gas temperature causes condensation of tar and acids even though the output water temperature
(80 - 90°C) and the return water temperature (65°C) is maintained. These situations may occur e.g.
in case of a wrong setting of the pellet burner (low output). For the outputs of 4 - 100 kW you can
also use a three-way mixing valve with a servo drive and electronic control to maintain the minimum
temperature of return water to the boiler (65 - 75°C).
CAUTION - We recommend you to always use the D14P, D21P and D25P boilers in
combination with an equalizing tank with the volume of 500 to 1000 l.
16. Basic connection diagram of the boiler with an equalizing
tank and burner control by the TS and TV sensor
GB
www.atmos.cz
18 - GB
Operation Manual - GB
17. Diagram of prescribed connection of the boiler with an
equalizing tank and the ACD01 control unit
18. Connection diagram of the boiler with Laddomat 21
Operation Manual - GB
GB
www.atmos.cz
GB - 19
19. Laddomat 21
With its construction, Laddomat 21 replaces the tra-
ditional connection composed of individual parts.
It is composed of a cast-iron body, thermoregula-
tory valve, pump, non-return ap valve, ball valves
and thermometers. When the water temperature
reaches 78 °C, the thermoregulatory valve opens
the water supply from the storage tank. The con-
nection with Laddomat 21 is considerably easier
and therefore, we recommend it. A spare thermo-
cartridge of 72 ° C is supplied with the Laddomat
21 device. It is used for boilers over 32 kW.
OPERATION DATA
Max. operating pressure
0,25 MPa
Design pressure
0,25 MPa
Test over pressure
0,33 MPa
Hoghest operating temperature
100°C
WARNING - Laddomat 21 is designed only for boilers with output up to 75 kW (inclu-
sive). We recommend using it only with boilers with output up to 50 kW (inclusive).
20. Thermoregulatory valve
Thermoregulatory valve type ESBE, TV 60 °C is used with
solid fuel boilers. When the boiler water temperature reaches
+ 60 °C , the thermoregulatory valve opens and fluid from
the building heating circuit (2) enters the boiler circuit ( 3
1). Inlets 1 and 3 always remain open. This ensures that the
minimum temperature of the water returning to the boiler
is maintained. If need be, a thermoregulatory valve set to a
higher temperature (E.g. 7C) may be used.
Recommended sizes of the thermoregulatory valve TV 60°C.
For boilers: D14P, D21P, D25P .......................................................DN25, DN32









GB
www.atmos.cz
20 - GB
Operation Manual - GB
21. Operation instructions
Preparation of boilers for the operation
Before putting the boiler in operation you must make sure that the system is filled with water and
bled. You must always operate the boiler in accordance with the instructions contained in this manual to
achieve high quality and safety of the functionality of the boiler. The boiler may only be operated by
adult persons. The commissioning of the boiler must be done in accordance with this manual and the
operation manuals attached to the pellets burner by a qualified person.
Before igniting pellets perform several operations. Check all the lids and doors for proper clo-
sing. Check whether the burner is properly tightened to the boiler over the gasket and that the end
switch stop is in its place. Also, check the hose between the burner and the conveyor for proper tensio-
ning and such inclination that allows free falling of pellets to the burner. They must not accumulate in
the hose. The angle of the worm conveyor should be at least 45°; otherwise the boiler may not achieve
the nominal output.
If everything is OK, draw pellets to the conveyor. In the case of the ATMOS A25 burner plug the
power supply cord of the conveyor to a standard 230V/50Hz socket. When pellets start to fall out of the
conveyor, plug the power supply cord of the conveyor back to the socket for normal operation. Turn on
the main switch (green), the switch of the pellet burner and the switch of the automatic deashing system
(if installed).
Adjust combustion of the burner with the use of a flue gas analyzer in the measurement place
(opening) in the flue between the boiler and the chimney. Always adjust the burner in a stabilized
condition, approx. 20 - 30 minutes after fuel ignition. If there is no flue gas analyzer available for the
boiler adjustment at the moment, you can adjust the pellet burner „roughly by guesswork“. Set the
quantity of fuel and combustion air in such a way to stop the flame just before the opposite wall (the
flame should not touch the wall). However, the flames must not turn at the opposite wall. In such a way
add combustion air (open the fan flap) or reduce the fuel supply.
CAUTION - This adjustment does not replace adjustment made with the use of a flue gas ana-
lyzer by a qualified person. Changes of settings of the boiler and burner may only be performed
by a person that is qualified in accordance with all the valid regulations and ČSN EN standards.
Fan of the burner with an air flap.
By opening the air flap you will reduce the
length of the flame.
Burner flame ending 1 - 3 cm before the op-
posite wall.
Operation Manual - GB
GB
www.atmos.cz
GB - 21
22. Burner connection for the D14P, D21P and D25P boilers
1. ATMOS 25 pellet burner 3. 2 x M8 screw
2. Sealing cord, 18 x 32 mm, small 4. 2x M8 decorative nut
23. Boiler system with an external storage container and conveyor
1. ATMOS D14P, D21P, D25P boiler 4. Pellet container (250, 500 and 1000 l)
2. ATMOS 25 pellet burner 5. Conveyor leg
3. ATMOS DA1500 conveyor - 1.5 m 6. Cleaning door
RECOMMENDATION - We recommend you to select the container size of 500 l to 1000
l, which will be sufficient for 3 to 14 days, depending on the consumed power. The larger
the volume of the container, the better. The length of the conveyor may be 1.5 m, 2.5 m or
2.5 m. As the pellet storage you can also use a clearly delimited part of the room complying
with fire regulations from which pellets may be drawn to an intermediate storage container
at the boiler, or directly to the boiler.
GB
www.atmos.cz
22 - GB
Operation Manual - GB
24. Boiler room with a large built-in pellet storage
A boiler plant with a built-in pel-
let storage with the volume of
e.g. 5 m
3
in which you can store
3250 kg of pellets. For this purpose
a 2 m (2.5 m) conveyor is used. For
easy access to the storage a segmen-
ted opening is produced that can
be adapted to the pellet level in the
storage and enables cleaning of the
storage from dust and dirt once a
year. In the top part of the storage
there are two openings for replenis-
hment of pellets from a cistern that
have different sizes with regard to
pellet suppliers.
For optimum collapsing of the pel-
let heap the optimum angle of the
inner walls in the storage must be
at least 45°. All the walls are incli-
ned to the lowest point of the stora-
ge from which the worm conveyor
draws pellets.
CAUTION - If pellets are drawn to the storage in the boiler plant directly from the cistern,
several principles must be observed that prevent their crushing during pneumatic transport.
First of all you must make sure that they do not hit the hard wall of the storage, but a screen
that is suspended in the centre of the storage from the ceiling. is way you will ensure even
filling of the storage and prevent crushing into small pellets and dust. Ask the pellet suppliers
about further possibilities and conditions of pellet drawing.
Operation Manual - GB
GB
www.atmos.cz
GB - 23
25. Cleaning of the boilers and ash removal
The burner and the boiler must be cleaned regularly and thoroughly once every 1 to 30 days de-
pending on the quality of pellets and the output setting. Fly-ash and dirt accumulated in the combustion
chamber of the burner and boiler considerably reduce the service life and output. Do the regular clean-
ing of the boiler in such a way that you rst let the burner burn out (turn off the burner switch /20/).
Open the cleaning door, remove the front stainless-steel screen and clean the combustion chamber of
the burner, incl. the air openings in the chamber with the provided poker. If the combustion chamber of
the burner is heavily soiled, remove it for cleaning. Further, remove the decelerators from the tube plates
located in the top part of the combustion chamber and clean them with the provided brush. During this
cleaning return the front stainless-steel screen back to the boiler, but the other way round to make it
prevent large quantities of dust from falling out of the boiler during the cleaning. Also, do not forget
to clean the back smoke channel and scrape the walls of the combustion chamber of the boiler with the
provided poker or brush. Finally, remove the ash pan and dispose of the ash while observing all the fire
measures. The interval of the cleaning and ash removal depends on the fuel quality, heating intensity,
chimney draught and other circumstances. Put everything in the original condition after the cleaning.
At least once a year remove the burner and clean it completely. See the manual of the burner.
Removable combustion chamber of the bur-
ner with air supply openings - must be clea-
ned regularly
Sample cleaning of the tube plate with the
front screen arranged the other way round
Sample cleaning of the smoke channel. It is
performed after cleaning of the tube plate in
the combustion chamber of the boiler
Large ash pan partly drawn out
GB
www.atmos.cz
24 - GB
Operation Manual - GB
26. Maintenance of the heating system, including boilers
At least once every 2 weeks check or replenish water in the heating system. If the boilers are out
of operation in winter, there is a danger of water freezing in the system and therefore you had better
drain water from the system or fill it with an antifreeze mixture. Otherwise, only drain water in ine-
vitable cases and for the shortest possible time. After the end of the heating season thoroughly clean
the boiler and replace the damaged parts. Do not wait with the replacement of parts until the last
moment; prepare the boiler for the heating system in spring already.
27. Operation and supervision
Boiler operators must always follow the operation and maintenance instructions. Interventions
into boilers that could endanger the health of the operators or other persons in the vicinity are prohibi-
ted. Boilers may only be operated by a person that is more than 18 years old, that has been acquainted
with the instructions and operation of the equipment and that complies with the requirements of § 14
of the Directive no. 24/1984 Coll. You must never leave unattended children near boilers that are in
operation. During the operation of solid fuel boilers it is prohibited to use any flammable liquids for
lighting the fire and it is also prohibited to increase the nominal output of the boiler during operation
(overheating). You must not put flammable objects on the boiler and near the fuel feeding and
ash pan openings and ash must be stored in non-flammable containers with a lid. Boilers in
operation must be under occasional supervision of the operator. The user may only carry out repair
consisting in simple replacement of a spare part (e.g. a sealing cord, etc.). During the operation check
the doors and cleaning openings for tightness and always tighten them properly. The user must not al-
ter the structure and electric installation of boilers. The boiler must always be cleaned properly and in
time so that free passage of all the ways can be guaranteed. Cleaning doors must always be properly
closed.
28. Možné závady a způsob jejich odstranění
Problem Cause Remedy
The “mains” indicator does
not light up
- no mains voltage
- incorrectly inserted plug in
the mains socket
- faulty main switch
- defective cord
- check
- check
- replace
- replace
The boiler does not achieve
the set output and the set wa-
ter temperature
- little water in the heating system
- high output of the pump
- the output of the boiler is not
sufficiently sized for the par-
ticular hot-water system
- poor-quality fuel
- low chimney draught
- high chimney draught
- insufficiently cleaned boiler
- replenish
- adjust the flow and pump
control
- design issue
- burn high-quality pellets
- new chimney, unsuitable con-
nection
- install a throttling flap in the
flue or a pressure reducer
- clean
Operation Manual - GB
GB
www.atmos.cz
GB - 25
Leaky doors
- faulty glass cord
- low chimney draught
- replace
- adjust the door hinges
- faulty in the chimney
Defects and shortcomings of
the burner, conveyor and the
deashing system
- no more fuel
- the fuel is cindered and blocks
the chamber on the burner
- the hose between the conveyor
and the burner gets clogged
- the burner does not provide
the required output
- the worm conveyor does not
run (stops)
- other defects of the burner
- the deashing system does not
work after turning the switch
off and on
- replace and before the new
star draw pellets to the con-
veyor
- clean the combustion chamber
and hose replace pellets or
clean the combustion chamber
of the burner once a day until
you burn all the poor-quality
pellets
- low calorific value of the pel-
lets, change the setting
- replace the gearbox of the
conveyor - defect
- check the quality of pellets,
high resistance (diameter,
length)
- follow the operation instruc-
tions of the burner
- check - replace the module
under the boiler hood or the
defective gearbox
29. Spare parts
Thermometer /15/ (code: S0041) 1
Main switch /16/ (code: S0091) 1
Control thermostat /17/ (code: S0021) 1
Pump thermostat /18/ (code: S0023) 1
Safety thermostat /19/ (code: S0068) 1
Fuse T6,3A/1500-typ H /20/ (code: S0200) 1
Door sealing cord, 18 x 18 /7/ (code: S0240) 1
Ash pan /3/ D14P, D21P (code: P0097), D25P (code: P0080) 1
Sealing cord between the burner and boiler, 18 x 32 mm (code: S0165) 1
Double switch of the automatic deashing system and pellet burner /20/ (code: S0098) 1
Sibral gasket under the smoke channel lid (with an opening) (code: S0120) 1
Klingerite gasket under the smoke channel lid (without openings) (code: S0124) 1
Sibral insulation of the burner opening lid /10/ (code: S0275) 1
Tube plate decelerator /12/ D14P, D21P (code: P0098), D25P (code: P0210) 3
Replacing the door sealing cord
Procedure: Use a screwdriver to remove the old cord and clean the groove where it was seated.
Use a hammer to slightly shape the cord from the square cross-section to the trapezoidal cross-secti-
on. Grip the cord and impress it along the perimeter of the door (with the narrower base to the groove)
Operation Manual - GB
GB
www.atmos.cz
GB - 27
GUARANTEE CONDITIONS
Hot-water boiler
1. If adhered to the product’s use, operation and maintenance as described in the instruction manual,
we guarantee that the product will maintain the characteristics as stipulated by the correspond-
ing technical standards and terms for the duration of a guarantee period of 24 months after the
product’s acquisition by the user, a maximum of 32 months after the manufacturer sells it to the
sales representative. If the boiler is installed with a TV 60°C thermoregulatory valve or with a
Laddomat 21 in combination with the accumulation storage tanks (see attached schematics), the
guarantee period for the boiler drum is extended from 24 to 36 months. The guarantee period for
other parts remains unaffected.
2. If a defect not caused by the user, appears on the product during the guarantee period, the defect
will be repaired free of charge.
3. The guarantee period is extended by the period of time for which has the product been under re-
pair.
4. A claim to provide a guarantee period repair shall be made by the customer at the service com-
pany.
5. The guarantee claim is justified only in cases where the boiler installation was carried out by a
person trained by the manufacturer and in compliance with valid standards and the instruction
manual. A necessary condition for justifying a guarantee claim is possession of a legible and com-
plete record identifying the company who installed the boiler. If the installation was not carried
out in a professional manner, the subsequent costs are borne by the company that carried out the
installation.
6. The purchaser was familiarised with the use and operation of the product – in a provable way.
7. A claim to provide an after-guarantee period repair shall be made by the customer at the service
company, too. In this case, the customer bears the repair costs.
8. The user is obliged to adhere to instructions from the operation and maintenance manual. If the
operation and maintenance manual is not adhered to, in cases of negligent or unprofessional han-
dling, or burning prohibited substances, the guarantee expires and the repair costs are borne by
the customer.
9. Boiler installation and operation must be in compliance with the instruction manual where the
outgoing water temperature is in the 80 - 90° range and the temperature of water returning to
boiler at least 65°C in all its operation modes.
10. There is an obligation to have the boiler inspection carried out including its controls settings,
structural elements and extraction system by an expert company at least once a year – confirmed
in a warranty card
For boilers designated for the Czech Republic, Poland, Russia, Romania, Lithuania, Latvia and
Hungary no guarantee conditions or insurance policies from outside these countries apply.
Guarantee and post-guarantee period repairs are carried out by:
- installation company that carried out the installation
- Jaroslav Cankař a syn ATMOS, Velenského 487, 294 21 Bělá pod Bezdězem,
Czech Republic, Telephone. +420 326 701 404
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Atmos D14P wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info