5.4.8 CONNECTION TO THE ACCUMULATION TANKS
System of the connection is based on warming the accumulation tanks, where is the accumulated
warmth from accumulation tanks gradually drained according to the requirements of heated space. Dur-
ing the bioler operation at full output are accumulation tanks warmed at 80–90 °C. Heating with accu-
mulation tanks in connection with ATTACK SLX boiler brings several advantages. Main advantages are
higher efficiency, lower fuel consumption, prolonged lifetime of the boiler, more frequent operation,
minimal creation of acids and condensates, higher comfort, lower risk of boiler overheating and fuel sav-
ing.
Recommended volume of the accumulation tank for ATTACK SLX 25 boiler is 2000 l (for other outputs
see technical parameters). Boiler is able to produce 180 kWh of energy at one loading of the hard wood
to the feeding chamber (it is ca. 7 hours of operation at full 25 kW output). It correspond to charge of
2 000 l accumulation tank from 20 °C to 90 °C if there is no energy offtake (that is why is necessary to
keep in mind by choosing the size of accumulation tank, that boiler must be operated according to the
size of accumulation tank. It means that, if you have 2000 l tank, load the wood chamber fully. If you
have 1000 l tank, load the chamber halfway – if there is no energy offtake from the accumulation tank). If
the accumulation tank is charged (bottom temperature of the accumulation tank achieves 70 °C) and
boiler achieved set boiler temperature, do not load the wood to the boiler. If you would load the wood to
the boiler in this state, wood would not be combusted (boiler has already achieved set temperature and
fan has turned off). It would get dry and condensates would create in the feeding chamber, what lowers
boiler lifetime. It is necessary to fill the wood at the time when the accumulation tank is almost dis-
charged.
Example 1:
Outside temperature of the environment is −5 °C and heat loss of the object is 10 kW by this tempera-
ture. Boiler has 25 kW at the full output operation. Accumulation tank with volume 2000 l is discharged
(its upper and bottom temperature is 20 °C). The heating system (to cover heat loss) drains 10 kW output
from accumulation tank and boiler has 25 kW output, accumulation tank will be heated by the output of
15 kW – difference between them. 15 kW output makes energy of 105 kWh by full loading of the cham-
ber with hard wood and time of the operation ca. 7 hours. Energy of 105 kWh warms accumulation tank
from 20 °C to 65 °C. It means, that this is the safe economic operation without putting the boiler out of
operation or draining excessive warmth to the waste (boiler was cooled by the aftercooling circuit). Boil-
er is able to cover the heat loss for up to 15 hours at one wood loading.
Example 2:
Outside temperature of the environment is +3 °C and heat loss of the object is 5 kW by this temperature.
Boiler has 25 kW at the full output operation. Accumulation tank with volume 2000 l is discharged (its
upper and bottom temperature is 20 °C). The heating system (to cover heat loss) drains 5 kW output from
accumulation tank and boiler has 25 kW output, accumulation tank will be heated by the output of 20
kW – difference between them. 20 kW output makes energy of 140 kWh by full loading of the chamber
with hard wood and time of the operation ca. 7 hours. Energy of 140 kWh warms accumulation tank from
20 °C to 80 °C. It means, that this is the safe economic operation without putting the boiler out of opera-
tion or draining excessive warmth to the waste. If the heat loss of the object would be constant all the
time – 5 kW, charged accumulation tank would be able to cover heat loss for about 28 h, what is togeth-
er with operation time up to 35 hours without need of wood loading.
That is why it is necessary to keep in mind, that boiler should be loaded only with amount of wood
necessary for charging the accumulation tank, because pointless overheating might lead to putting the
boiler out of the operation or removing excessive warmth to the waste. This is uneconomical and re-
quires activation of the safety element – aftercooling loop.
19

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für ATTACK SLX wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von ATTACK SLX

ATTACK SLX Bedienungsanleitung - Deutsch - 112 seiten

ATTACK SLX Zusatzinformation - Deutsch - 21 seiten

ATTACK SLX Zusatzinformation - Englisch - 21 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info