The water connection may be made only through an inspected membrane safety valve or membrane safety valve combi-
nation tting (not a piston valve)! A safety valve combination consists of a shut-o, test, non-return, waste and safety valve
with expansion water drain and is installed between the cold water feed line and cold water inlet of the tank in the order
shown:
Tank connection to DIN 1988 and ÖNORM B2531:
Always observe the following:
To ensure proper function of the tting, the latter must be installed only in a frost-protected space. The safety valve runout
must be open and visible and the waste line of the drip catcher (expansion water funnel) must be routed to the waste water
duct so that neither frost nor obstructions caused by dirt and such can cause a problem. Ensure that the drip cup or item to
be drained is free of deposits and soiling.
No shut-o valve or other restriction may be installed between the safety valve and cold water inlet of the water heater.
The safety valve must be set to a response pressure which is less than the rated pressure of the tank.
Before nally connecting the tank, ush the cold water line.
After making the water connection and air-bubble free lling of the tank, check the tting for proper function.
When lifting or turning (venting) the safety valve test button, the water must ow out freely and without backing up through
the expansion water outlet funnel.
The discharge openings of the safety valves (domestic water and heating circuits) must open out into an appropriate drainage
object in order to avoid any damage caused by the escape of operating uid.
To check the return valve, the shut-o valve must be closed and no water may ow out from the opened test valve. The safety
valve must be checked according to DIN 1988 or ÖNORM B2531.
The water heater is operated using the hot water valve on the service water tting. This means the tank is under continuous
line pressure. To protect the internal boiler against overpressure when heating up, the expansion water created is dispersed
through the safety valve every time it is heated. The return valve prevents hot water from owing back into the cold water line
when there is a pressure drop and thus protects the boiler from heating when no water is present.
The shut-o valve can be used to isolate the tank on the water side and thereby eliminate the pressure from the cold water
supply, also allowing use of the waste valve when necessary.
In order to allow for a trouble-free repair, a removal or exchange of the device, it is necessary to establish the connection
of the tank by means of a detachable connection (Dutch). Tank leaks as a result of an improper connection and resulting
damage and consequential damage are excluded from the warranty and product liability.
3. CIRCULATION CONNECTION
Due to signicant energy loss, a circulation connection should be avoided when possible. If a highly branched service water
network requires a circulation line, this must be well insulated and the circulation pump controlled via a timer and ther-
mostat. The switching temperature of the thermostat should be kept low (45°C). The circulation connection piece has an
external thread.
Tank
Safety valve
Waste valve
Non-return valve
Test valve
Pressure reducing valve
Shut-off valve
Service water fixtures
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Austria Email KRU 052 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info