INSTALLATION INSTRUCTIONS &
MANUAL FOR MAINTENANCE
HORIZON BELL
LARGE TUNNEL 3
CF/LF
Gas • res with closed combustion system
Bell• res wishes you many cosy evenings with your new Bell• res gas • re
This document is an essential part of your gas • re.
Read it carefully before installation and maintenance of the
gas • re and keep it in a safe place!
Serial number:
Production date:
3
Bell res English
Installation instructions
BELLFIRES GAS FIRE WITH CLOSED COMBUSTION SYSTEM:
Horizon Bell Large Tunnel 3 CF (Centre Fire) (HBLT3 CF)
Horizon Bell Large Tunnel 3 LF (Line Fire) (HBLT3 LF)
4
Bell res English
Installation instructions
7
Bell res English
Installation instructions
1 INSTALLATION INSTRUCTIONS
1.1 GENERAL
The gas fi re must be positioned and connected as a “room sealed system” (balance
ue) appliance by a “Gas Safe Register” registered gas installation engineer in
accordance with the following installation instructions, nationally and locally applicable
regulations (see “Technical Details/ Regulations” at the rear of this manual). If you have
any queries regarding the installation, please consult your local gas company.
Important: Before beginning the installation, check that the details on the
rating plate correspond to the gas type and pressure to which
the appliance will be connected.
The appliance is supplied with a “Centre Fire” or “Line Fire” double burner, as ordered.
These burners each have their own specifi c fl ame image which is defi ned by the
perforation pattern in the burner cover. See Chapter 5 and the Instructions for use.
The appliance is factory set to the correct nominal heat input. The pilot light is set to the
correct level of consumption.
Depending on the requested version, the appliance will be delivered from the factory
with a Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm concentric connection for
extracting the fl ue gases and supply of combustion air.
It is possible to install the gas fi re with either a wall or roof outlet.
The roof connection must be carried out using the concentric fl ue system Ø100 mm -
Ø150 mm. The fumes are exhausted naturally to the outside environment through the
inner Ø100 mm pipe whereas the combustion air supply passes between the Ø100 mm
and Ø150 mm pipes.
The wall connection must be carried out using the concentric fl ue system Ø130 mm -
Ø200 mm. The fl ue gases are evacuated outside by means of natural draft through the
internal pipe of Ø130 mm, whereas the combustion air is supplied between the pipes of
Ø130 mm and Ø200 mm. The wall outlet itself is, depending on the concentric fl ue gas
system confi guration, Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm. (In some cases,
with a wall connection, a complete concentric fl ue system Ø100 mm - Ø150 mm is also
possible (see Chapter 1.6.1).)
The gas fi re can be installed in a completely sealed or mechanically ventilated house
without extra ventilation and/or fume extraction.
The gas fi re is installed as a built-in appliance in a fi replace.
In order to prevent the fi replace heating up excessively, it must be properly
ventilated by installing vents at the top and bottom of the fi replace.
9
Bell res English
Installation instructions
Part no Option
Convection package Horizon Bell Large Tunnel 3
331585 1x Top plate Convection
312829 1x Convection set General
330361 Set of high adjustable feet (4 pieces)
311973 Mantle iron L = 1800 mm
1.4 OPTIONS AND ACCESSORIES
The following options and accessories can be supplied by your dealer:
Part no Accessorie
312829 Convection set General: (for convection air extraction)
302188 1x Flexible aluminium pipe Ø125 mm, L= 3 m (max.)
310178 2x Fitting box 135 x 135 mm
309872 2x Convection exit grid, white, 145 x 145 mm
309730 2x Collar adaptor Ø125 mm
304040 4x Hose clamp Ø125 mm
329874 Set carrying brackets (2 pieces)
3........ Bellfi res (M&G) concentric fl ue system
See component summary
3........ Poujoulat (PGI) concentric fl ue system
See component summary
3........ Ontop (Metaloterm US) concentric fl ue system
See component summary
10
Bell res English
Installation instructions
1.5 PREPARATION FOR INSTALLATION
The following preparation must be carried out before the gas fi re can be installed.
1.5.1 Instructions for positioning the outlet
1.5.1.1 Positioning the outlet for correct operation:
Roof-mounted outlet:
Figure 1: Roof-mounted outlet
This must be positioned at least 0.5 m from the roof edge;
the apex of the roof can be disregarded.
Wall-mounted outlet:
Figure 2: Wall-mounted outlet
This must be positioned at least 0.5 m from:
the corner of the building.
the roof overhang, the rain gutter.
balconies etc., unless the exhaust construction
extends to at least the face of the protruding section.
>0.5 m
>0.5 m
11
Bell res English
Installation instructions
1.5.1.2. Positioning the outlet to avoid affecting the surrounding area
All listed “distances” in this section are no more than
guidelines.
For the exact minimum “distances”, please consult your
national and local directives.
“Distance” = minimum distance required for positioning of the outlet to avoid
adverse effects with respect to:
A. A ventilation opening serving an occupied room, a toilet or a bathroom.
B. A heating air supply, when the supply fl ows through an occupied room.
C. A window that can be opened and that is near an occupied room, a toilet
or a bathroom.
Roof-mounted outlet:
To avoid adverse effects Distance: outlet - A, B or C
At the same roof level. >3 m (*)
At a different roof level. >1 m (*)
At a lower positioned wall. >1 m
At a higher sloping surface. >3 m (**)
(*) If the required distance cannot be achieved, the outlet position rules take
precedence.
(**) If the required distance cannot be achieved, the position of the outlet must
be at least 1 m above the highest facade/roof.
12
Bell res English
Installation instructions
Wall-mounted outlet:
To avoid adverse effects Distance: outlet - A, B or C
At walls in buildings with staggered Not permitted if A, B, or C are located
heights. above the outlet.
On a wall - general. (*) Above the outlet: >2 m
Below the outlet: >0.75 m
Left and right of the outlet: >0.75 m
At <1 m from the roof overhang. >2 m
Beneath balconies, walkways etc. >2 m from the underside of the
protruding balcony or walkway.
Beneath balconies, walkways >2 m
etc. where the outlet extends to
the front.
To the garden or on the terrace. >2 m to the outside space. (**)
With respect to a facing wall. >2 m (if the distance from the facing
wall is less, the criteria detailed for
“On a wall - general” apply).
Enquire at your local gas company for the regulations relating to outlets
positioned opposite each other and outlet(s) in facade(s) that form an angle.
(*) These minimum distances do not apply if there is an obstruction
between the outlet and A, B and C that protrudes at least 0.5 m from
the wall and has a length exceeding the distance.
(**) This distance is not required if the outlet is situated at least 1 m
higher than the intended area of the outside space.
If the outlet has a clearance of less than 0.5 m from the hard surface of a public area at
a height of less than 2 m, it must be fi tted with an effective protector. The mesh size of
the guard must not affect the correct operation of the appliance.
14
Bell res English
Installation instructions
Figure 4: Vertical roof-mounted outlet without bend
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
18
10, 11, 12, 13
1
4
Y
28
16
17
16
24
23
24
23
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric
(min.-max.) connection connection
on appliance is on appliance is
Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m Width: Width:
B = 30 mm B = 65 mm
Horizon Bell Large Tunnel 3
4.0 - 12.0 m Width: Width:
B = 40 mm B = 80 mm
RIGID CONCENTRIC FLUE Ø100 mm - Ø150 mm SYSTEM CONNECTION
POSSIBILITIES
Appliance: Concentric fl ue connection Ø100-Ø150 mm or Ø130-Ø200 mm
15
Bell res English
Installation instructions
Figure 5: Vertical roof-mounted outlet with bend
(*) : (Y1 + Y2) : X > 2 : 1
(Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
16
23
Y2
X
10, 11, 12, 13
14, 15
Y1
4
1
28
23
23
17
24
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*) Distance Y1 + Y2 (*) Concentric Concentric
(min.-max.) (min.-max.) (min.-max.) connection connection
on appliance is on appliance is
Ø100-Ø150 mm Ø130-Ø200 mm
Horizon Bell 1.0 - 11.0 m 0 - 3.0 m 1.0 - 11.0 m - Width:
Large Tunnel 3 B = 40 mm
17
Bell res English
Installation instructions
Figure 7: Vertical chimney outlet using a lined chimney with a bend > 45°
(Flexible Ø100 mm and/or rigid Ø100 mm / Ø150 mm)
(*) : (Y1 + Y2+ Y3) : X > 2 : 1
(Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y2
Y1
10, 11, 12, 13
> 45°
X
Y3
32
18
30
29
5
7
29
26
25
23 28
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*)
Distance Y1 + Y2 + Y3 (*) Concentric Concentric
(min.-max.) (min.-max.) (min.-max.) connection connection
on appliance is on appliance is
Ø100-Ø150 mm Ø130-Ø200 mm
Horizon Bell 1.0 - 11.0 m 0 - 3.0 m 1.0 - 11.0 m - Width:
Large Tunnel 3 B = 40 mm
18
Bell res English
Installation instructions
Figure 8: Vertical chimney outlet using an existing unsound lined
chimney or when no chimney liners are present
(Flexible Ø100 mm / Ø150 mm)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y
7
6
8
1832
31
29
30
29
26
29
27
28
29
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric
(min.-max.) connection connection
on appliance is on appliance is
Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m Width: Width:
B = 30 mm B = 65 mm
Horizon Bell Large Tunnel 3
4.0 - 12.0 m Width: Width:
B = 40 mm B = 80 mm
19
Bell res English
Installation instructions
Figure 9: Vertical chimney outlet using an existing unsound lined
chimney or when the chimney is unlined; with a bend >45o
(Flexible Ø100 mm / Ø150 mm)
(*) : (Y1 + Y2+ Y3) : X > 2 : 1
(Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y3
Y2
Y1
X
> 45°
6
8
7
31
29
32
18
30
29
26
29
27
28
29
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*)
Distance Y1 + Y2 + Y3 (*) Concentric Concentric
(min.-max.) (min.-max.) (min.-max.) connection connection
on appliance is on appliance is
Ø100-Ø150 mm Ø130-Ø200 mm
Horizon Bell 1.0 - 11.0 m 0 - 3.0 m 1.0 - 11.0 m - Width:
Large Tunnel 3 B = 40 mm
17

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bellfires HORIZON BELL LARGE TUNNEL 3 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Bellfires HORIZON BELL LARGE TUNNEL 3

Bellfires HORIZON BELL LARGE TUNNEL 3 Installationsanweisung - Deutsch - 108 seiten

Bellfires HORIZON BELL LARGE TUNNEL 3 Bedienungsanleitung - Deutsch - 32 seiten

Bellfires HORIZON BELL LARGE TUNNEL 3 Bedienungsanleitung - Englisch - 36 seiten

Bellfires HORIZON BELL LARGE TUNNEL 3 Installationsanweisung - Holländisch - 96 seiten

Bellfires HORIZON BELL LARGE TUNNEL 3 Bedienungsanleitung - Holländisch - 28 seiten

Bellfires HORIZON BELL LARGE TUNNEL 3 Installationsanweisung - Französisch - 96 seiten

Bellfires HORIZON BELL LARGE TUNNEL 3 Bedienungsanleitung - Französisch - 32 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info