Placing of the boiler according to the required free space:
basic environment AA5/AB5 according to ČSN 33 2000-1 ed.2:2009
in front of the boiler, a manipulation area of at least 1000mm is required
the minimum distance between the back side of the boiler and the wall is 500 mm
a distance of 800 mm between the wall and the side of the boiler with the fuel container is
needed to enable removal of the worm feeder
at the side of the boiler body, there must be a handling area at least 500 mm so that cleaning of
convective areas of the boiler body is possible
above the boiler, at least 500 mm of free space is required so that cleaning of convective area of
the boiler body is possible
Placing of the boiler with respect to the chimney:
BENEKOV R100 boiler is connected to the chimney with a metal pipe of 250 mm diameter.
Fuel storage:
It is recommended to store the pellets in original packings (PET or “big bags”) in a dry place.
it is forbidden to store the fuel behind the boiler or next to the boiler in a distance shorter than
400mm
the producer recommends to store the fuel at least 1000 mm from the boiler or to store it in a
separate room
Permanent air circulation for burning and ventilation must be provided in the room where the boiler is
installed. Air consumption of BENEKOV R100 boiler at nominal power is approximately 300 m
3
. h
-1
Connection of the pipeline of the heating system or pipeline of the heating element must be carried out
by a certified person.
WARNING: When the boiler is connected to the heating system, the drain tap must be placed as
low and as near to the boiler as possible.
6. Installation - instructions for the contract service company
The heating boiler must be installed only by an authorized service company that has been
certified for assembly of such devices.
6.1. Connectors of electrical wiring
During the installation, it is not necessary to interfere with the electrical wiring of the boiler control unit in
any way. All the inlets for electrical wiring for all electrical parts of the boiler as well as its additional
devices are placed in the connectors which allow easy connection to or disconnection from the
switchboard of the boiler control unit.
Depending on the type and equipment of the boiler, the following connectors may be placed on the boiler
and marked with icons:
- connector of the fuel feeder drive
14

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Benekov R100 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info