577353
25
Zoom out
Zoom in
Vorherige Seite
1/142
Nächste Seite
02/ 2011
BENNING IT 101
19
During insulation measurements dangerous high voltages
might occur on the test probe tips of the BENNING IT 101. Bear
in mind that these dangerous voltages can also appear on bare
metal parts of the appliance which is being tested. Do not touch
the test tips when the rotary switch J is set to 50 V, 100 V,
250 V, 500 V or 1000 V.
- Make sure that the circuit or test object is free of voltage.
- Select the desired function (MΩ) with the rotary switch J.
- The black safety measuring lead has to be connected to the COM jack M
on the BENNING IT 101.
- The black red measuring lead has to be connected to the jack for V,
Insulation L on the BENNING IT 101.
- The safety measuring lead has to be connected to the measuring point.
- With a voltage of more than 30 V AC/ DC, a flashing warning symbol R
additionally gives a warning of an external voltage being applied and the
insulating resistance measurement is stopped. Switch the switching circuit
off and repeat the measurement.
- Press the TEST key
8
to start the measurement.
- Press the blue key
3
to display the insulating resistance or the leakage
current.
- In order to measure the insulating resistance continuously, first press the
LOCK key
6
and then the TEST key
8
. The value is measured continu-
ously until the TEST key
8
or LOCK key
6
is pressed again.
Before removing the measuring leads, release the TEST key
8
and wait until the voltage applied has dropped to 0 V. Please
bear in mind that internal energy storages of the test sample
thus are discharged via the measuring instrument.
- Resistance values higher than the measuring range are shown on the
display
2
with ">“ P.
See figure 5: Insulating resistance measurement (symbolic)
8.4.1 COMPARE function (comparative function)
- The BENNING IT 101 insulating resistance measuring instrument is pro-
vided with 12 stored limiting values:
100 kΩ, 200 kΩ, 500 kΩ, 1 MΩ, 2 MΩ, 5 MΩ, 10 MΩ, 20 MΩ, 50 MΩ,
100 MΩ, 200 MΩ and 500 MΩ.
- Before measurement, press the COMP key
4
to select the limiting value. In
comparative mode, the "COMPARE" symbol J is shown and the selected
limiting value is indicated at the bottom right of the display
2
. The com-
parative function allows a direct check of whether the values fall below the
limiting values.
- The green LED of the PASS indicator
7
lights, if the measured value
exceeds the comparative value (resistance value).
- Press the COMP key
4
to select and activate the limiting value.
- Press the COMP key
4
for more than 2 seconds to deactivate the com-
parative function.
8.5 Polarization index (PI) and dielectric absorption rate (DAR)
- Make sure that the circuit or test object is free of voltage.
- Select the desired function (MΩ) with the rotary switch J.
- To determine the polarization index (PI), press the LOCK key
6
(PI/DAR)
for more than 2 seconds. The "PI" symbol L is shown on the display
2
.
By pressing the key again, it is possible to choose between measuring the
dielectric absorption rate (DAR) and measuring the polarization index (PI).
The selected (PI L or DAR K) measurement is shown on the display
2
.
- The black safety measuring lead has to be connected to the COM jack M
on the BENNING IT 101.
- The black red measuring lead has to be connected to the jack for V,
Insulation L on the BENNING IT 101.
- The safety measuring lead has to be connected to the measuring point.
- With a voltage of more than 30 V AC/ DC, a flashing warning symbol R
additionally gives a warning of an external voltage being applied and the
measurement is stopped. Switch the switching circuit off and repeat the
measurement.
- The measurement can be started and interrupted by means of the TEST
key
8
.
- The remaining time required for determining the value can be determined
by means of the blue key
3
.
- If the measured value exceeds the measuring range, the error message
"Err" is shown on the display.
25

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Benning IT 101 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info