BENNING PV 1-1
19
the BENNING PV 1-1.
- Switch on the BENNING CC 3 current clamp adapter and select the 40 A range.
- Switch on the BENNING PV 1-1 and press the
Auto
-key
3
until the symbol B for current
clamp measurement is displayed.
- For direct current (DC) measurements, press the null balance key (ZERO) of the
BENNING CC 3 until a current value of approx. 0 A is displayed.
- Enclose the single-wire live conductor by means of the current clamp adapter.
- The measured current will be shown on the display
1
.
See gure 8: AC/ DC current measurement by means of optional current clamp adapter
BENNING CC 3
8.6 Measurement on several identical PV modules/ PV strings
For PV systems with several identical PV strings, the open-circuit voltages and short-circuit cur-
rents must be compared with each other at stable radiation conditions. The values should be
identical and should have a maximum deviation of 5 % (at stable radiation conditions). Moreover,
the measured values have to be compared with the values to be expected.
- At the beginning of the series of measurements, press and hold the -key
8
and the
-key
6
in order to delete the measured value memory.
- Connect the first PV string of the PV generator to the BENNING PV 1-1.
- Press the
Auto
-key
3
to start the automatic measurement of the first PV string.
- Press the -key
8
to store the measured values.
- Connect the next PV string to the BENNING PV 1-1 and press the
Auto
-key
3
to start the
automatic measurement.
- Press the -key
8
to store the measured values.
- Repeat this procedure for all identical PV strings at stable radiation conditions.
- After measurement, the stored measured values can be recalled pressing the -key
6
. As
soon as a measured value deviates by more than 5 % from the average value of all stored
measured values regarding the open-circuit voltage or short-circuit current, the ">5%" sym-
bol O starts flashing.
- To call the average values, press the -key
6
repeatedly until the storage location 0 is
displayed. The average values of the open-circuit voltage and of the short-circuit current are
shown on the display
1
.
See gure 6: Automatic solar panel measurement, ISO measurement via earthing conductor
8.7 Measured value memory
8.7.1 Storing measured values
The BENNING PV 1-1 can store up to 200 display screens. Depending on the measure-
ments carried out, the values for protective conductor resistance, open-circuit voltage, short-
circuit current, insulating resistance with testing voltage and even the measured AC/DC current
( BENNING CC 3) are stored with a date/ time stamp.
- Press the -key
8
to store the displayed measured values to the first free storage location.
Successful storage will be confirmed by the "STORE" symbol L on the LC display
1
.
8.7.2 Calling measured values
- Press the -key
6
to recall the stored measured values with the corresponding storage
location number N. The symbol “RECALL” M is displayed
1
. The storage location number
N is shown on the display
1
.
- Press the -key
6
to go to the previous storage location.
8.7.3 Deleting the measured value memory
- To delete the entire measured value memory, press the
-
key
8
and the -key
6
.
8.7.4 Warning in case of the measured value deviating by 5 %
- In case the displayed measured value memory (open-circuit voltage and short-circuit cur-
rent) deviates by 5 % from the average value of all stored measured values, the "5%" symbol
starts flashing.
8.7.5 Average value of the entire measured value memory regarding the open-circuit voltage
and short-circuit current
- Press the -key
6
repeatedly until the storage location 0 N is shown on the display
1
.
The symbol “RECALL” M is displayed
1
.
- The storage location 0 N calculates the average values for open-circuit voltage and short-
circuit current from all stored measured values.
8.7.6 Reading out the measured value memory via the USB interface
To read out the measured values via the USB interface
7
, you have to install the hardware driver
from the "Treiber-driver" directory on the enclosed CD-ROM and then the download program
from the CD-ROM's "Programm-program" directory on your PC once.
In order to download the data, please proceed as follows:
- Disconnect all safety measuring leads from the BENNING PV 1-1.
- Connect the BENNING PV 1-1 to your PC by means of the USB connecting cable.
- The hardware driver is installed automatically on a free COM port and confirms that the new
hardware can be used.
25

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

benning-pv-1.1

Suche zurücksetzen

  • Was ist der Grund für eine zusätzliche DC Spannungsanzeige bei der Auto Messung, an der Stelle wo sonst R PE angezeigt wird und die für die Auto Messung eigentlich nicht relevant ist? Eingereicht am 14-12-2022 19:53

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Benning PV 1.1 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Benning PV 1.1

Benning PV 1.1 Kurzanleitung - Holländisch, Französisch, Italienisch, Spanisch - 14 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info