6 720 811 270 (2015/04)AGS10-2, AGS10E-2, AGS20-2, AGS50-2
6.2.6 Determining the frost threshold temperature
To determine the degree of frost protection, we recommend checking
the frost protection of the heat transfer fluid when first putting the
system into operation, by means of a frost protection gauge (a
refractometer). This check should be repeated at regular intervals (at
least every two years).
The commonly used instruments for testing motor vehicle engine
coolants are not suitable for this purpose. A suitable device can be
ordered separately.
For system operation with heat transfer medium LS
If the solar system is operated with heat transfer medium LS, the value
must be converted using Tab. 10.
6.2.7 Correcting frost protection
If the minimum frost protection level is not being maintained, more heat
transfer fluid must be added.
Use Tab. 11 to determine the volume of the system, so that you can
calculate the exact amount to be added (which is equal to the amount
which first needs to be drained out).
Use the formula on the right to determine the amount of concentrate
to be added (V
replace
).
Example of heat transfer medium L:
System volume (V
total
) = 22 l
Frost protection level (reading taken): – 14 °C
Equals concentration of ( Tab. 10, page 15): 29 % (C = 29)
•Result: V
replace
= 4.3 l
Drain the calculated amount to be added (V
replace
) and add
concentrate.
6.3 Setting the flow rate
The flow rate is set when the system is cold (30 - 40 °C).
When the solar pump is speed-controlled, the controller determines
the flow rate based on operating requirements.
If the controller is not equipped with speed control or if speed control
has been deactivated, the flow rate must be set to a fixed flow rate.
If you wish to set the flow rate:
1. Carry out the preparatory work ( Chapter 6.3.1)
2. Check the flow rate ( Chapter 6.3.2)
3. Set the flow rate ( Chapter 6.3.3)
6.3.1 Carrying out the preparatory work
Rotate ball valves [1] to 0° (check valves ready for operation).
Completely open the flow limiter [2].
On the controller, select mode “Manual ON” ( controller instruction
manual).
Fig. 26
[1] Gravity brake ready for operation
[2] Adjusting screw on the flow limiter, depending on the type
[3] Read-off edge for the flow rate, depending on the type
Value recorded for heat transfer
medium L (concentration)
Corresponds to frost protection
with heat transfer medium LS
– 23 °C (39 %) – 28 °C
– 20 °C (36 %) – 25 °C
– 18 °C (34 %) – 23 °C
– 16 °C (31 %) – 21 °C
– 14 °C (29 %) – 19 °C
– 11 °C (24 %) – 16 °C
– 10 °C (23 %) – 15 °C
– 8 °C (19 %) – 13 °C
– 6 °C (15 %) – 11 °C
– 5 °C (13 %) – 10 °C
– 3 °C (8 %) – 8 °C
Table 10
NOTICE: Frost damage
Every two years, check whether the required frost
protection level (to at least –25 °C) is being
maintained.
System part Fill volume
Collector: see collector instructions (technical data)
1 single-line solar pump station 0.20 l
1 twin-line solar pump station 0.50 l
1 coil in the solar cylinder (see technical guide)
1 m Cu pipe Ø 15 mm 0.13 l
1 m Cu pipe Ø 22 mm 0.31 l
1 m Cu pipe Ø 28 mm 0.53 l
1 m Cu pipe Ø 35 mm 0.86 l
1 m Cu pipe Ø 42 mm 1.26 l
1 m stainless steel corrugated pipe DN16 0.26 l
1 m stainless steel corrugated pipe DN20 0.41 l
1 m stainless steel corrugated pipe DN25 0.61 l
Table 11 Volume of the separate system parts
V
replace
= V
total
x
43 - C
concentration
100 - C
concentration
Table 12 Formula for calculating the amount of fluid to be replaced
0,5
7
6
5
4
3
2
1
L/min
7
6
5
4
1
0,5
3
2
6720801165.18-2.ST
1
20
0
40
60
°C
80
100
120
20
0
40
60
°C
80
100
120
S E
3
2
15

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch AGS10-2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info