6 720 646 804
Installation instructions
11
Fig. 6
A 27” minimum vertical clearance is required to remove
the filter for cleaning and to replace the anode rod. The
hot and cold water plumbing and electrical connections
must not interfere with the removal of the filter.
Fig. 7
Condensation drain
The unit has a condensate drain, therefore a drain must
be available in close proximity to the unit. The drain must
be no higher than 36” above the floor (laundry drain is
acceptable).
If no drain is available, then a common condensate
pump with a capacity no less than 1 gallon/day must be
purchased from a local builder and supply store and
installed.
3.3 Venting (specifications and vent
runs)
Venting the outlet air of the water heater to another
room may be an option for specific applications. See
Section 3.6.
Duct diameter: 8”
Maximum outlet duct length: 16.5 feet
Maximum Air flow: 219 CFM
Maximum no. of elbows: 1.
The vent collar accessory (see Fig. 2) must be installed
in order to accommodate the required 8" diameter vent
pipe. Line up tabs on vent collar with slots in vent
opening. Rotate to lock into place.
If terminating venting to the outdoors, pitch horizontal
pipe downward towards termination 1/4" per foot to
avoid damage from rain.
3.4 Water piping
3.4.1 Inlet - Outlet connections
Refer to the illustration below for suggested typical
installation. The installation of unions or flexible copper
connectors is recommended on the hot and cold water
connections so that the water heater may be easily dis-
connected for servicing if necessary. The HOT and
COLD water connections are clearly marked and are
¾”NPT on all models.
IMPORTANT: Do not apply heat to the HOT or COLD
water connections. If sweat connections are used,
sweat tubing to adapter before fitting the adapter to the
water connections on heater. Any heat applied to the
hot or cold water connection will permanently damage
the dip tube.
Fig. 8 Typical installation
3.4.2 Dielectric union (recommended acces-
sory)
Different metals between plumbing and tank materials
and additionally the effect of hot water can cause
corrosion of one of the metals (generally the one in the
tank is the metal attacked)
The Dielectric union will avoid any physical contact
between the two metals, acting as an effective insulator
and preventing this attack. How quick this corrosion
progresses, if at all, depends on the content of your
water, its pH, the dissolved minerals and the metals
involved.
27”
6720646804-05.1V
i
Install a shut-off valve in the cold water line
near the water heater. This will enable eas-
ier service or maintenance of the unit later.
6720646804-09.1V
6” air gap
Relief discharge
line to suitable
open drain
6’ drain hose
Thermal expansion
tank (if required)
To cold water
supply
Hot water outlet
to fixtures
Union
Union
Temperature and
pressure relief valve
(shown in different
location for clarity)
Drain valve
Jacket
access panel
Jacket
access panel
Auxiliary catch
pan 2” maximum
Electrical junction box
(use only copper
conductors)
To electrical
distribution panel
11

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Compress 3000 - HP 200-1 E AI-F wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info