Troubleshooting
Condens 7000 WP – 6721841195 (2022/01)
40
229 B Flame failed during burner operation 1. Open the main shut-off valve.
2. Open the device shut-off valve.
3. Shut down the device and check the gas line.
4. Signal evaluation on printed circuit board defective.
5. Replace flame sense electrode.
6. Establish protective conductor connection (PE) in the control device.
7. Replace ignition cable.
8. Replace the connecting lead to the flame sense electrode.
9. Replace air/gas ratio control valve.
10.Set the burner correctly or replace the burner nozzles.
11.Set the burner at minimum rated load.
12.Convert the flue system.
13.The interconnected combustion air supply is too low or the ventilation opening is too
small.
14. Clean the heating block on the flue gas side.
15.Replace control device/burner control unit.
232 BBoiler locked by external switching contact 1. Connect the plug for the external switching contact.
2. Install jumper/check condensate pump according to manufacturer's specifications.
3. Adapt switching point of the external temperature switch to the system.
4. Replace connecting lead to the external temperature switch.
5. Replace external temperature switch.
233 V Boiler identification module or device
electronics faulty
1. Install boiler identification module/coding plug.
2. Connect plug to boiler identification module/coding plug.
3. Replace boiler identification module/coding plug (Bosch contact customer service).
234 VGas valve electrical fault 1. Replace connecting lead and reset once replacement is complete.
2. Replace air/gas ratio control valve and reset once replacement is complete.
235 V Conflicting versions of boiler electr. and
boiler identification
1. Check boiler identification module/coding plug.
2. Install valid combination of control device/burner control unit.
237 VSystem fault 1. Replace boiler identification module/coding plug.
2. Replace control device/burner control unit.
238 V Boiler electronics faulty Replace control device.
242 -
263
VSystem fault boiler electronics / basic
controller
1. Remedy contact problem.
2. If necessary, replace control device or boiler identification module/coding plug (Bosch
contact customer service).
265 O Heat demand lower than energy supplied
268 OComponent test activated
269 V Flame monitoring Replace control device/burner control unit.
273 BOperation interrupted following 24 hours of
continuous operation
The fan and burner start automatically after the safety check.
281 B Pump stuck or running in air 1. Check whether the pump is blocked, unblock or replace if necessary.
2. Ensure that the heating water can circulate correctly.
3. Vent the pump.
306 VFlame signal after closing the fuel supply 1. Replace the air/gas ratio control valve.
2. Replace the ionisation cable.
3. Replace the control device/burner control unit.
316 V Flue gas temp. too high during sensor test 1. Replace flue gas temperature sensor.
2. Replace the connecting lead to the flue gas temperature sensor.
3. Replace the control device/burner control unit.
317 VShort-circuit at flue gas temp. sensor 1. Replace flue gas temperature sensor.
2. Replace the connecting lead to the flue gas temperature sensor.
3. Replace the control device/burner control unit.
318 V Flue gas temperature sensor interrupted 1. Connect the plug to the flue gas temperature sensor.
2. Check the connecting lead to the flue gas temperature sensor.
3. Replace flue gas temperature sensor.
4. Replace the control device/burner control unit.
Fault
code
Fault
category
Fault text on the display, description Remedy
40

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Condens GC7000WP wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Bosch Condens GC7000WP

Bosch Condens GC7000WP Installationsanweisung - Deutsch - 60 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Deutsch - 12 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Englisch - 12 seiten

Bosch Condens GC7000WP Installationsanweisung - Holländisch - 56 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Holländisch - 12 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info