ERROR MANAGEMENT
6 720 806 630 (2013/02) 13
Remove the locking ring which retains the filter inside the valve. Use
the pliers provided.
Remove the filter from the valve and flush the filter with water.
Reinstall the filter, circlip and plug.
Open the valve and start the heat pump via the ON/OFF switch.
13 ERROR MANAGEMENT
The control panel has an advanced monitoring system that gives alarms
if anything unforeseen happens. The user can rectify most of these
alarms themselves. There is never a risk of affecting something when an
alarm is reset once or twice. Contact the installer engineer in the event
of repeated alarms.
In the menu Alarm there is:
Alarm log
Info log
Fig. 28
The customer level = 0 gives access to alarm information in the Alarm
log.
Installer/Service level = 1 gives access to:
Delete alarm log
Information regarding the Alarm history.
Information regarding the Info log.
Delete info log
13.1 ALARM LOG AND INFO LOG
In the Alarm log and the Info log, all alarms and warnings that have
occurred are stored in chronological order.
Delete the Alarm log and the Info log after commissioning is
complete.
13.2 EXAMPLE OF AN ALARM:
When an alarm is triggered, an alarm window is displayed and a warning
signal sounds. The alarm window displays the alarm causes and the time
and date that the alarm occurred.
Fig. 29
If you press the rotary selector, Acknowledge is marked, the alarm
symbol disappears and the warning signal is suppressed. The heat pump
restarts if heat demand exists.
The alarm symbol continues to be displayed if a fault is not remedied.
The ON and fault indicators change from flashing red to constant red
indications. Every alarm is stored in the alarm log. Active alarms are
indicated by the alarm symbol.
The alarm symbol appears for both alarms in the heat pump and for
alarms in the Hydrolight/Hydrocomfort unit, if alarms have occurred in
both the units, two alarm symbols will appear.
13.3 BLANK MENU DISPLAY
13.3.1 POSSIBLE CAUSE 1: FAULTY FUSE IN THE DOMESTIC
POWER SUPPLY.
Check whether all domestic fuses are OK.
If required, change/reset fuse/MCB. See installation manual for
details on fuse type.
After the fault has been remedied, the heat pump automatically restarts.
13.3.2 POSSIBLE CAUSE 2: THE MINIATURE CIRCUIT BREAKER IN
THE HYDROLIGHT/HYDROCOMFORT UNIT HAS TRIPPED.
Contact the installer.
13.4 ALL ALARMS, WARNINGS AND INFORMATION
WINDOWS
An alarm can occur temporarily due to various reasons. However, there
is never a risk involved in resetting an alarm. All the alarms that can
appear in the menu display are described in this section. The
descriptions give an idea about the nature of the alarm and what can be
done to rectify it.
The alarm log shows alarms and warnings that have occurred.
13.5 ALARM WINDOW
13.5.1 FAILURE / SHORT CIRCUIT ON SENSOR
Fig. 30
All sensors connected to the heating installation can give an alarm in the
event of a fault. In the example, it is sensor T3, hot water, which has
given an alarm. All sensors give alarms in the same way.
Possible cause 1: occasional fault.
Confirm alarm and continue monitoring.
Possible cause 2: fault at temperature sensor or incorrect
connection.
Contact the installer in the event of repeated alarms.
13.5.2 MAX FLOW TEMPERATURE, HEATING SYSTEM OR MAX
FLOW TEMPERATURE, MIXED HEATING SYSTEM
The flow temperature has reached the max. allowable temperature.
▶Select Acknowledge.
Contact the installer in the event of repeated alarms.
13.5.3 T8 HIGH FLOW TEMPERATURE OR T71 HIGH FLOW
TEMPERATURE
Fig. 31
Ensure that the heating circuit is free from air at all times,
i.e radiators or underfloor cicuits.
6 720 648 135-07.1I
6 720 617 422-23.1I
6 720 617 422-23.1I
6 720 641 467-24.1I
13

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Greensource Hydrolight - Hydrocomfort wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info