Outdoor Temperature Reset Operation
Outdoor Temperature Reset is available by setting the
Application Mode in the Setup Menu to RSET.
In a heating system, the rate of heat supplied to the building
must equal the rate at which heat is lost. If the two rates are
not equal, the building will either cool off or over heat.
The rate of building heat loss depends mostly on the outdoor
temperature. Outdoor Reset allows a hot water heating
system to increase the water temperature, adding heat to the
building, as the outdoor temperature drops. The rate at which
the water temperature is changed as a function of outdoor
temperature is defined by the characterized heating curve.
Indirect Domestic Hot Water (IDHW) operation is available
during outdoor temperature reset operation.
Central Heat (CH) Call
----------------------------
A CH Call is required in order for the control to provide target
water temperature for the space heating system. Once the
control registers a CH Call, it will display the “Heat” icon
under the Calls in the display. A heat call can be provided
in two ways:
Contact Closure
A dry contact or 24 V (ac) signal is applied across the CH
Call terminals 5 & 6.
Characterized Heating Curve
- -- --- ---- ---- --- ----
A characterized heating curve determines the amount the
target water temperature is raised for every drop in outdoor
air temperature.
The characterized heating curve takes into account the
type of terminal unit that the system is using. Since different
types of heating terminal units transfer heat to a space using
different proportions of radiation, convection & conduction,
the supply water temperature must be controlled differently.
The control uses the terminal unit setting to vary the supply
water temperature to suit the terminal unit being used. This
improves the control of the air temperature in the building.
Boiler Characterized Heating Curve
Terminal
Unit
Boiler
Design
Boiler
Indoor
Outdoor
Design
Decreasing Outdoor Temperatures
Increasing Water Temperatures
Terminal Unit
- ------- -----------------------------
Select the appropriate terminal unit in the Setup Menu. This
will change the shape of the characterized heating curve
to better match the heat transfer properties of that specific
terminal unit.
Hydronic Radiant Floor (HRF1)
A heavy or high mass, hydronic radiant floor system. This type
of a hydronic radiant floor is embedded in either a thick concrete
or gypsum pour. This heating system has a large thermal mass
& is slow acting.
Dual Fuel Boiler Operation
The Heatronic 4000 supports the operation of dual fuel
boilers. Dual fuel boiler functionality is only available with
applicable Bosch / Buderus boiler models. The control allows
for up to two dual fuel boilers with selection capability for
Boiler 1 and Boiler 3.
If a dual fuel boiler is selected for boiler 1, the boiler 1 output
is used to control the gas burner and the boiler 2 output is
used to control the oil burner. Also, the boiler pump and,
if applicable, boiler outlet sensor, are to be connected to
boiler 1.
If a dual fuel boiler is selected for boiler 3, the boiler 3 output
is used to control the gas burner and the boiler 4 output is
used to control the oil burner. Also, the boiler pump and,
if applicable, boiler outlet sensor, are to be connected to
boiler 3.
Fuel Switch
- - - - - - - - - - - - - - -------------------------
A fuel switch is required in order for the control to switch
burner operation from gas to oil.
Once the control registers
a fuel switch, it will display FL SW in the status field. A
fuel switch is provided by a dry contact or 24 V (ac) signal
applied across the fuel switch terminals 9 & 10. The device
that provides a fuel switch is typically a manual switch
located on the boiler which selects what burner (gas or oil)
becomes active.
If the fuel switch is not present, the gas burner is active and
the oil burner is inactive. If the fuel switch is present, the oil
burner is active and the gas burner is inactive.
10

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Heatronic 4000 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Bosch Heatronic 4000

Bosch Heatronic 4000 Bedienungsanleitung - Französisch - 60 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info