18 | Commissioning
MC 4006 720 816 739 (2015/05)
4.5 Cascade settingsmenu
When a cascade module is installed, the menu Service menu > Cascade
settings is displayed on the user interface (not available for all user
interfaces). When this menu is not available in the installed user
interface, the cascade module uses default settings. These settings can
be changed with an appropriate user interface even when the user
interface is only temporarily connected.
4.6 Diagnosismenu
The menus depend on the installed user interface and the installed
system.
Monitored values
If a MC 400 module is installed, the Monitored values > Cascade menu
is displayed.
This menu allows you to call up information on the current status of the
system and the individual devices in the cascade. For example, you can
display the level of the system's flow and return temperature, or the
current appliance output.
If a MC 400 module is installed, the menu Monitored values > System
information > Cascade is displayed.
This menu allows you to call up information on the MC 400 module
(cascade module type, cascade module software version) and the
individual devices in the cascade (such as control device 1 type,
control unit 1 software version).
The information and values that are provided depend on the system that
has been installed. Observe the documents for the heat source, user
interface, additional modules and other system components.
The default settings are shown in bold in the adjustment
ranges.
Menu item Adjustment range Function description
Offset header sensor – 20 ... 0 ... 20 K The flow temperature demanded by the control is changed by this value.
Set temp. cascade max 30 ... 90 °C Maximum flow temperature of the cascade at the low loss header.
Casc. pump overrun time 0 ... 3 ... 15 min The heating pump (secondary side) connected to the cascade module runs for the time set here longer than for the
heat requirement.
Flow temp. peak load 30 ... 50 ... 70 °C In the control strategy "Serial cascade with peak load coverage" (coding card at position 3), the heat source
necessary to cover the peak load is connected when the flow temperature required by the controls exceeds the
value set here.
Outside temp. Peak load – 20 ... 10 ... 20 °C In the control strategy "Serial cascade with peak load coverage" (coding card at position 3), the heat source
necessary to cover the peak load is connected when the outside temperature falls below the value set here.
Start-up delay Next device 0 ... 6 ... 30 min Once a heat source is connected, the controls wait for the time set here until the next device is connected.
Tolerated overtemp. 0 ... 5 ... 10 K To reduce the device cycles, the heat sources are only turned off when the flow temperature exceeds the desired
set temperature by the tolerated overtemperature (positive switching differential).
Tolerated undertemp. 0 ... 5 ... 10 K To reduce the device cycles, the heat sources are only turned on when the flow temperature falls below the desired
set temperature by the tolerated undertemperature (negative switching differential).
Table 6
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch MC 400 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info