697430
27
Zoom out
Zoom in
Vorherige Seite
1/48
Nächste Seite
Control unit
27
Uni Condens 8000 F – 6720867056 (2016/10)
Secure all cables with cable clips (supplied with the control unit):
Insert the cable clip together with the cable from above into the
slots in the frame ( fig. 27, page 27).
Slide the cable clip downwards.
Counterhold.
Flip the lever up.
Fig. 27 Securing a cable with a cable clip
Refit the cover hood on the control unit ( fig. 7.2.1, page 26).
Secure the control unit cover hood by tightening the screws
( fig. 25, page 26).
7.2.3 Control unit settings
If a control unit from the CFB 800/CFB 900 series is used, burner
modulation in standard mode is not enabled for 2.5 minutes.
Avoid fast upwards modulation.
Regulator settings
Table 12 Adjustable parameters for CFB 810 and CFB 840
Set boiler temperature controller and maximum boiler temperature
The boiler temperature controller ensures emergency operation with an
adjustable boiler water temperature if the control electronics fail. In
standard control mode, the maximum boiler temperature adopts the
function of the boiler temperature controller. The maximum boiler water
temperature can be selected in the control unit in the "Boiler
parameters" menu, under menu item "Max. shutdown temperature".
Control unit settings
Fig. 28 Control unit settings
[1] High limit safety cut-out
[2] Temperature controller
[3] MEC2
Select temperatures ( tab. 12, page 27) at high limit safety cut-out
[1] in the control unit and at temperature controller [2].
Select the maximum boiler water temperature at the MEC2 [3].
The maximum temperature demand is not a value that is set directly. The
maximum temperature demand is composed of the set temperature and
the rise.
Example DHW demand:
Sum of the set DHW temperature (60 °C) and the parameter "return
temperature increase" (20 °C) in the "DHW" menu:
60 °C + 20 °C = maximum temperature demand 80 °C.
Example heating circuits:
Sum of the set temperature of the heating circuit with mixer with the
highest temperature required (70 °C) and the parameter "return
temperature increase" (5 °C) in the "Heating circuit data" menu:
70 °C + 5 °C = maximum temperature demand 75 °C.
All maximum temperature demands must always be 7 K below the
maximum selected boiler water temperature.
Adjustable
parameter
(max. temperature)
CFB 810 CFB 840
High limit safety cut-
out (STB)
1)
1) Set the high limit safety cut-out and temperature controller as high as possible,
but ensure the settings are at least 5 K apart.
110 °C 110 °C
 at least 5 K
Temperature
controller (TR)
1)
105 °C 90 °C
 at least 6 K at least 18 K
Max. boiler water
temperature
99 °C 84 °C
 at least 7 K
Max. temperature
demand
2)
of heating
circuit
3)
and DHW
4)
2) Both temperature demands must always be at least 7 K under the maximum
boiler temperature.
3) The temperature demand of heating circuits equipped with an actuator is
composed of the set flow temperature and the "return temperature increase"
parameter in the heating circuit data menu.
4) The temperature demand of DHW heating is composed of the set DHW
temperature and parameter "return temperature increase" in the DHW menu.
92 °C 77 °C
6720615883-31.1RS
.
.
.
.
.
0010011563-001
1 2 3
80
27

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Uni Condens 8000 F wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Bosch Uni Condens 8000 F

Bosch Uni Condens 8000 F Bedienungsanleitung - Deutsch - 16 seiten

Bosch Uni Condens 8000 F Bedienungsanleitung - Englisch - 12 seiten

Bosch Uni Condens 8000 F Bedienungsanleitung - Holländisch - 12 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info