SMOKE ALARMS
& HEAT ALARMS
$ The maximum interconnect wiring length is 250 metres. The maximum num-
ber of alarms interconnected together is 12. BRK smoke alarms should not be con-
nected to any model produced by another manufacturer.
The location of the alarms must comply with the applicable building codes and the
advice in section C: WHERE TO LOCATE below.
#$$
#../20*7-
8:;=:/*,.68=7<270*7-;.:2.;*5*:6;
1. Use either of the methods of in-
stallation shown in Fig1 and 2.
When selecting cable for con-
necting interlinked smoke alarms
the interlink wire should be
treated as live.
The installation method shown in
Fig 1 is suitable for a plaster-
board or similar ceiling where ac-
cess to the void behind it is
available and suitable to mount
the junction box.
2. Connect the brown wire to the
brown (live) in the house wiring
and the blue wire to the blue (neu-
tral). NO CONNECTION SHOULD
BE MADE TO THE MAINS ELEC-
TRICITY SUPPLY EARTH TERMI-
NAL. TERMINATE HOUSE
WIRING EARTH IN SPARE CON-
NECTOR.
3. For multiple alarm installations
use a “three core and earth” style
cable between all the alarms to be interconnected and connect the third core
of that cable to the white wire from the smoke alarm. DO NOT use the earth
wire for the interconnect line. This must be treated as live, i.e. insulated and
sheathed. If the alarm is not going to be interconnected, cap the unused
wires.
4. Remove the baseplate from the back of the alarm by twisting anti-clockwise
as far as it will go. (about 12 mm). Detach the locking pin.
650MBX, 670MBX and 680MBX Detach battery door screw from the base
plate. Open the battery door on the back of the alarm, connect the battery,
close the door and secure with the screw provided before fitting the alarm to
the baseplate. Test the alarm using the test button.
5. Attach the flat side of the mounting plate and tighten screws to fit snugly
against the pattress or junction box and ceiling or wall.
6. Bring the power connector through the centre opening of the plate.
7. Plug the lead into the rear of the alarm.
8. Place the alarm on the baseplate by lining up arrows on the baseplate and the
alarm rim and twist clockwise to fasten.
To secure the alarm to the baseplate, insert the locking pin (removed from the
base in 5 above) into the ‘T’ shaped slot located above the arrow on the rim of
the alarm.
LOCKING PINS / KEYS UST BE FITTED. DO NOT ATTEMPT TO REMOVE THE
ALARM FROM THE BASEPLATE WITHOUT FIRST REMOVING THEM.
8:#.:2.;*5*:6;;=9952.-27<1.*7-;.:2.;?2<1
#-8,4270+*;.
1. Connect the brown (live) in the house wiring to connector Land the house blue
wire (Neutral) to connector N.
NO CONNECTION SHOULD BE MADE TO THE MAINS ELECTRICITY
SUPPLY EARTH TERMINAL. TERMINATE HOUSE WIRING EARTH IN SPARE
CONNECTOR MARKED E. See Fig 2
2. For multiple alarm installations use a “three core and earth” style cable
between all the alarms to be interconnected and connect the third core of that
cable to connector marked I. DO NOT use the earth wire for the interconnect
line. This must be treated as live, i.e. insulated and sheathed.
3. Locate the molded arrow on the side of the base and smoke alarm see fig 3.
Position the smoke alarm just below the base with both arrows in the same
orientation and locate the alarm onto the base by gently applying pressure
until the alarm ‘clicks’ into place.
OWNERS
MANUAL
Sprue Safety Products Ltd.
Unit 6, Carter Court
Davy Way
Waterwells Business Park
Quedgeley
Gloucester
GL2 2DE
United Kingdom
COVERS Simple Fitting Instructions
Location Guide
User Information
Basic Fire Safety Tips
Simple Maintenance Instructions
 "$$ #"
"$$#'"#%
M A I N S P O W E R E D
When installing this alarm for use by others,
please leave this manual or a copy with the
end user.
EARTH
BLACK or GREY (INTERLINK)
BLUE (NEUTRAL)
BROWN (LIVE)
WHITE
BROWN
BLUE
BASEPLATE
INSTALLATION USING JUNCTION BOX
ALARM
JUNCTION BOX
BATTERY
ACCESS
DOOR
Fig 1.
#
OPTICAL SMOKE ALARMS
"(
("
IONISATION SMOKE ALARMS
"(
("
HEAT ALARMS
"(
("
220-240VAC ( )
MAINS POWERED ALARMS
CLASS II APPARATUS
2502-B0018 RevA
#"%#
((*7-(
• Check battery has been fitted correctly.
• Check alarm is not beeping.
• Test alarm before switching on the electricity supply.
All Alarms:
• Check the green light is on (behind the front grill).
• Check the red light flashes every 45 seconds or so.
• When testing linked alarms check that they all interconnect within 10 second
%#$$
'" Wiring should be installed by a qualified electrician in accordance with
BS7671. Permanent connection to the fixed wiring of the building should be made in
a suitable junction box. This alarm must not be exposed to dripping or splashing.
Connect the alarm as late as possible in an installation, particularly in new build, to
avoid contamination. Remove the dust cover before applying power.
$ For detailed guidance on the siting of this alarm refer to section C of this
handbook.
 "$$ The circuit used to power the alarm must be a 24 hour voltage circuit
that cannot be turned off by a switch. BS5839 Part 6 states that: -
For mains powered alarms, each with an integral standby supply (Grade D), the mains
electricity supply should take the form of either:
a) an independent circuit at the dwelling’s main circuit board, in which case no other
electrical equipment should be connected to this circuit (other than a dedicated
monitoring device installed to indicate failure of the mains electricity supply to the
alarms); or
b) a separately electrically protected, regularly used local lighting circuit.
For mains powered alarms, with no standby supply (Grade E), the mains electricity
supply may only take the form of an independent circuit as per a) above. If it is neces-
sary to use an RCD for protection, it should operate independently of any RCD pro-
tection for circuits supplying sockets or portable equipment.
All interconnected alarms should be installed on a single final circuit.
4. Switch on the mains electricity
supply.
5. Check that the green light is
on and that the red light is
flashing every
45 seconds or so. The lights
are located behind the grille
on the front of the
alarm.
6. Press and hold the test button
until the alarm sounds. NOTE:
On the 670 and
650 series, pressing this but-
ton places the alarm in pause mode.
#)#$#"$
"
Test each alarm in the system
checking that all other alarms in
the system are triggered within
10 seconds.
'"
Do not attempt to test the alarm
with flame heat or smoke, the re-
sults may be misleading and may
damage the alarm.
The dust cover must be removed
as late as possible before com-
missioning. This will reduce the chances of the alarm being contaminated by building
dust etc.
Remove the alarm from the system before testing the wiring with high voltage insula-
tion testing equipment otherwise this will damage the alarm and will invalidate the war-
ranty.
'"$$
1. As a minimum smoke alarms should be located between sleeping areas and poten-
tial sources of fire such as living rooms and kitchens. In single storey homes with
one sleeping area a smoke alarm should be installed in the hallway as close as pos-
sible to the living accommodation. To ensure audibility in the bedrooms it may be
necessary to install more than one smoke alarm, particularly if the hallway is more
than 15m long. In single storey homes with two separate sleeping areas, a minimum
of two smoke alarms is required, one outside each sleeping area. In multilevel or
split level homes as a minimum a smoke alarm should be installed on the ground
floor between the staircase and any rooms in which a fire might start and on each
storey in circulation areas which form part of the escape route (normally hallways
and landings).
$ Heat alarms should not be used in escape routes instead of smoke alarms.
They should only be used in the applications listed below in addition to smoke
alarms and should always be interconnected to smoke alarms.
2. Additional alarms should be installed in bedrooms in anticipation of fires originating
there, caused by faulty wiring, lights, appliances, smokers or other hazards.
3. For best protection, smoke alarms should be installed in every room in your home,
apart from those listed in the ‘LOCATIONS TO AVOID’ section. Heat alarms should
be used in kitchens, boiler rooms, laundry rooms, garages and such like where
smoke alarms would be unsuitable. All alarms must be interconnected.
4. Install smoke alarms in circulation areas at a distance no greater than 7.5m from the
farthest wall, no greater than 7.5m from a door to any room in which a fire might
start and no greater than 7.5m from the next smoke alarm.
5. When heat alarms are installed in a room, they should be at a distance no greater
than 5.3m from the farthest wall no greater that 5.3m from a door to any room in
which a fire might start and no greater than 5.3m from the next heat or smoke alarm.
6. As it is impossible to predict the source of a fire the best location for an alarm is the
centre of the room or hallway. If it is necessary to locate the smoke alarm on a wall
always locate the detection element of the alarm 150mm to 300mm (6 to 12 inches)
below the ceiling and the bottom of the alarm above the level of doors and other
openings.
$.*<*5*:6;;18=5-78<+.?*5568=7<.-.
7. In rooms with simple sloped, peaked or gabled ceilings install smoke alarms 900mm
(3 feet) from the highest point of the ceiling. ‘Dead air’ at the peak of the ceiling may
prevent smoke from reaching the alarm in time to provide an early warning.
8. Closed doors and other obstructions will interfere with the path of smoke and heat
Fig 2.
Fig 3.
Live = Brown
Neutral = Blue
Interconnect =
Grey or Black
1

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für BRK 780MRL wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info