10 Troubleshooting
Logano plus GB402 – 6 720 804 428 (2012/09)
46
V 4U 521 Excessive sensor
differential at the
boiler sensor
between
temperature
sensors 1 and 2.
Excessive temperature
differential between
temperature sensors
1 and 2 (deviation
> 5 K/2s).
Check that the "Reset" button
illuminates on the SAFe.
Press "Reset" on the SAFe.
Check that the check valve on the
cylinder primary pump is closed.
Close the check valve if it is still
open.
Check whether the flow and
return have been connected
correctly.
If flow and return have been
swapped, connect flow and
return correctly.
Check whether the plug-in
connection on the boiler sensor
and on the SAFe are
contaminated or damaged.
If required, clean or replace the
plug-in connections.
Check the resistances at the
boiler sensor according to table or
visually inspect the plug at the
temperature sensor.
Replace the boiler sensor if the
sensor values deviate from the
stated values, or if the plug is
faulty.
Check the voltage values on the
boiler sensor according to table.
Replace the SAFe if there are
deviations.
V 4U 522 Boiler sensor
short circuit
between
temperature
sensors 1 and 2.
A temperature sensor
fault was detected in
test mode.
Check the sensor lead.
Check the plug-in connection.
Replace in case of damage.
Clean or replace if
contaminated.
Refit plug it is found to be
loose.
Check sensor values according to
table.
Replace the temperature
sensor in case of deviations.
Check the voltage at the
temperature sensor according to
table.
Replace the SAFe in case of
deviations.
V 4Y 523 Boiler
temperature
sensor lead
break.
Temperature too low at
the boiler temperature
sensor (< -5 °C)
Check the sensor lead. Replace in case of damage.
Check the plug-in connection. Clean or replace if
contaminated.
Replace in case of damage.
Refit plug it is found to be
loose.
Check sensor values according to
table.
Replace the temperature
sensor in case of deviations.
Check the voltage at the
temperature sensor according to
table (SAFe documentation).
Replace the SAFe in case of
deviations.
V 4U 524 Boiler sensor
short circuit.
The boiler sensor
detected an
excessively high
temperature
(> 130 °C).
Check the sensor lead. Replace in case of damage.
Check the plug-in connection. Clean or replace if
contaminated.
Replace in case of damage.
Refit plug it is found to be
loose.
Check sensor values according to
table.
Replace the temperature
sensor in case of deviations.
Check the voltage at the
temperature sensor according to
table (SAFe documentation).
Replace the SAFe in case of
deviations.
V 4A 575 Intelligent high
limit safety cut-
out responds.
The boiler flow
temperature has
reached its maximum
permissible level.
Hi limit safety cut-out has
responded.
Check gas train.
(Does the flame extinguish
after a control shutdown?)
B 5L 542 Incomplete
communication
with the SAFe.
The MC10 generates
this fault if not all
required data is
supplied by the SAFe.
Check the cabling between the
SAFe and the MC10.
Replace the SAFe if the
connections are OK.
Type
1)
Display
code
Fault code Cause Description Test procedure/cause Correction
Tab. 22 Fault displays
1) V = locking; B = blocking
46

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Buderus Logano plus GB402 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Buderus Logano plus GB402

Buderus Logano plus GB402 Bedienungsanleitung - Deutsch - 2 seiten

Buderus Logano plus GB402 Bedienungsanleitung - Englisch - 20 seiten

Buderus Logano plus GB402 Installationsanweisung - Holländisch - 60 seiten

Buderus Logano plus GB402 Bedienungsanleitung - Holländisch - 16 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info