636469
24
Zoom out
Zoom in
Vorherige Seite
1/68
Nächste Seite
6720818454 (2016/02) US SSB
24 | Installation
Remodeling areas;
Garages with workshops.
4.7.1 General venting and combustion air piping system
The SSB boilers require an approved vent system-designed for positive
pressure.
Vent connectors serving appliances vented by natural draft shall not be
connected to any portion of mechanical draft systems operating under
positive pressure.
Ensure that the ue pipes and seals are not damaged.
Use only primer and glue compounds approved for use with the vent
material used.
Never install a barometric or a thermally controlled vent damper with this boiler.
Do not route the ue system piping through or inside another duct that is
used for exhausting air or other ue gases.
The condensate trap must be primed at all times. Failure to do so may
allow combustion gases to escape into boiler room.
The unit is to be used for either direct vent installation or for installation
using room air for combustion. When room air is used, it is necessary to
provide an adequate opening for the fresh air intake.
You must use any of the vent/air piping methods shown in this manual.
Be sure to locate the unit such that the vent and combustion air piping
can be routed through the building and properly terminated.
The boiler / vent installation must be in accordance with Venting
of Appliances, of the latest edition of the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or section, Venting Systems and Air Supply
for Appliances, of the CAN/CSA B149.1, Natural Gas and Propane
Installation code or applicable provisions of the local, state and federal
building codes.
All vent pipes must be installed according to the vent manufacturer’s
instructions.
The exhaust vent and the combustion air inlet lines must be supported to
prevent sagging per the vent manufacturer’s instructions.
Do not mix components from different systems. The vent system could
fail, causing leakage of ue products into the living space. Use only
approved materials.
Use of cellular core PVC and CPVC for venting system is not allowed.
WARNING: Improper venting due to failure to comply with
the warnings above can result in excessive levels of carbon
monoxide!
The exhaust pipe must be pitched a minimum of a 1/4 inch per foot back
to the boiler (to allow drainage of condensate).
The vent system shall be installed so as to prevent the accumulation of
condensate.
Consult local and state codes pertaining to special building code and re
department requirements. Adhere to national code requirements.
Observe the listed maximum lengths of vent system, which are boiler
model dependent
To avoid moisture and frost build-up and to maintain clearances to openings
on adjacent structures, 45 ° and 90 ° elbows or tees may be attached to
the end of the vent termination pipe to direct exhaust plumes away from
the adjacent structure. The total allowable vent length, maximum number of
elbows and distance to air intake restrictions must be adhered to.
Due to the high efciency of the unit it may discharge what looks like
white smoke especially when the outside air temperature is cold. This
is due to the presence of water vapor, normally present in the exhaust
gases.
The following gure shows the acceptable piping installation for venting
and combustion air.
Fig. 25
Two pipes side wall
(Direct venting)
Two pipes vertical
(Direct venting)
Air intake side wall,
vent vertical
(Direct venting)
Air intake vertical,
vent side wall
(Direct venting)
Concentring
vertical pipe
(Direct venting)
Concentring side
wall pipe
(Direct venting)
One pipe venting
side wall (or vertical)
(Not direct venting)
24

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Buderus SSB512 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Buderus SSB512

Buderus SSB512 Installationsanweisung - Französisch - 68 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info