636469
28
Zoom out
Zoom in
Vorherige Seite
1/68
Nächste Seite
6720818454 (2016/02) US SSB
28 | Installation
Wall Terminal Material Supplier Part Number
3" (80 mm) parallel stainless steel Flex-L 46546901
3” (125 mm)
4” (100mm)
Concentric kits
PVC or CPVC IPEX IIa
196006 (PVC), 197009 (CPVC)
196021 (PVC), 197021 (CPVC)
3” (125mm)
Wall termination kit
PVC IPEX IIa 081219
3” (125 mm)
4” (100mm)
Low prole termination kit
PVC IPEX IIa
196985
196986
3” (80 mm)
twin pipe termination
PVC/parallel stainless steel ANSI/ASTM D1785 or Field Controls 46600203
4” (100 mm)
twin pipe termination
PVC/parallel stainless steel ANSI/ASTM D1785 or Field Controls 46600204
3” (80 mm) twin pipe termination PP
M&G Duravent PolyPro or
Centrotherm InnoFlue
3PPS-HTP (M&G Duravent) or
ISLPT0303 (Centrotherm)
4” (100 mm) twin pipe termination PP M&G Duravent PolyPro 4PPS-HTP (M&G Duravent)
3” (80 mm) single pipe termination PP M&G Duravent PolyPro 3PPS-HST (M&G Duravent)
3” / 5” (80/125 mm) concentric
termination
PP
M&G Duravent PolyPro or
Centrotherm InnoFlue
3PPS-HKL (M&G Duravent) or
ICWS3539 (Centrotherm)
4” / 6” (100/150 mm)
concentric termination
PP
M&G Duravent PolyPro or
Centrotherm InnoFlue
4PPS-HK (M&G Duravent) or
ICWS4639 (Centrotherm)
Tab. 6 Wall terminals
4.7.4 Vent and combustion air pipe length [For single boiler
installations]
The maximum length for vent and combustion air pipes can be found in
the following table. Please note the length is for each vent / combustion
air pipe and not combined.
SSB255 SSB399 SSB512
3” (80 mm) 100 ft (30 m) 20 ft (6 m) 20 ft (6 m)
4” (110 mm) 165 ft (50 m) 100 ft (30 m) 100 ft (30 m)
5” (130 mm) 165 ft (50 m) 165 ft (50 m) 165 ft (50 m)
Tab. 7 Equivalent length for PVC and CPVC pipes
In the following tables are listed the equivalent length for PVC/CPVC
pipes and PP pipes:
3” (80 mm) 4” (100mm)
1 ft vent pipe 1 ft 1 ft
45° elbows 2.5 ft 4 ft
90° elbows 5 ft 7 ft
Tab. 8 Equivalent length for PVC and CPVC pipes
3”
(80 mm)
4”
(110 mm)
5”
(130 mm)
6”
(150 mm)
8”
(200 mm)
1 ft vent pipe 1 ft 1 ft 1 ft 1 ft 1 ft
1 ft ex pipe 2 ft 2 ft 2 ft N/A N/A
45° elbows 3 ft 5 ft 6 ft 6 ft 13 ft
90° elbows 7 ft 12 ft 14 ft 14 ft 19 ft
Tee 12 ft 19 ft 21ft 22 ft 29 ft
Tab. 9 Equivalent length for PP pipes
For the equivalent vent length of Stainless Steel AL29-4C venting
material and the roof and wall terminals please refer to the installation
manual of the vent system supplier.
To calculate the allowed length of a vent and combustion air system
follow this example:
When using a SSB255 with 3” (80 mm) PP system with 3 x 45° -elbows
and a 90° -elbow as termination, the total venting equivalent length for
each pipe [vent or combustion air] may not exceed 100 ft. ( 30 m).
3 × 45°-elbow = 3 x 3 ft. (0.91 m) = 9 ft. (2.7 m)
1 × 90°-elbow terminal = 7 ft. (2.1 m).
Total friction loss equivalent =16 ft. (4.8m)
Total venting length for this example is:
SSB255 = 100 ft. (30 m) - 16 ft. (4.8m) = 84 ft. (25.60 m) each for the
intake and exhaust piping.
When the total ue system equivalent length is veried it is necessary to
set the par N° 99 “Flue length range” according to the total length of the
installed ue system as dened in the following table:
Value
for par
99
System with Max.
eq. length of
20+20 ft
System with Max.
eq. length of
100+100 ft
System with Max.
eq. length of
165+165 ft
1 From 0 to 10 ft From 0 to 50 ft From 0 to 82 ft
2 From 11 to 20 ft From 51 to 100 ft From 83 to 165 ft
3 From 21 to 30 ft From 101 to 150 ft From 166 to 248 ft
4 From 31 to 40 ft From 151 to 200 ft From 249 to 330 ft
Tab. 10 Value for the par N° 99 depending on the sum of equivalent
length of vent and combustion air pipe
Dening the correct value to assign to par N° 99 follow this
example:
When using a SSB399 with 4” (110 mm) PP venting material the
maximum equivalent length is 100 feet for both vent and combustion
air piping. Consider the equivalent length of vent pipe is 56 ft. and the
combustion air pipe is 42 ft. First step is to verify that both the vent and
combustion air pipe is less than 100 ft:
56<100 : veried
42< 100 : veried
The sum of equivalent length of vent and combustion air pipe is:
56+42=98 ft. See Tab. 10 for dening parameter 99.
Row 2 - System with Max eq. length of 100 ft + 100 ft. The example
provided a total equivalent length of 98 ft. which falls in between 51 - 100
ft found on row 2. So par N° 99 = 2.
28

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Buderus SSB512 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Buderus SSB512

Buderus SSB512 Installationsanweisung - Französisch - 68 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info