Appendix
6 Installation instructions 0020246836_02
Appendix
A Detecting and eliminating faults
Fault Possible cause Remedy
No flow rate at the water
tap
1. The cold-water isolation valve is closed.
2. The main filter is blocked.
3. The pressure reducer is not installed correctly.
1. Check and open the cold-water isolation valve.
2. Close the cold-water isolation valve, and clean
the filter and the pressure reducer.
3. Check whether the pressure reducer has been
installed correctly.
Low flow rate and pres-
sure at a water tap
1. The filter in the cold water pipe is clogged. 1. Close the cold-water isolation valve, and clean
the pressure reducer filter.
Water from the water tap
is cold
1. The cylinder was not started up.
2. The cold-water isolation valve is not fully open.
3. The heat generator is not operating.
4. The thermal cut-out for a system component
has been triggered.
5. The 2-port motorised valve is defective.
6. The immersion heater is defective.
1. Open all of the relevant valves.
2. Check the thermostat or the room thermostat
and, if required, set this.
3. Check the heat generator to see if a fault code
is present.
4. Check and initialise the cylinder.
5. Check the connections for the 2-port motorised
valve.
Domestic hot water
temperature at the water
tap too high
1. The thermostat is set too high.
2. The thermostatic valve is not present or is
defective.
1. Check the target temperature. It must be
between 60 and 65 °C.
2. Install a mixer tap.
3. Check the cabling. Repair the cable.
4. Reduce the temperature of the thermostat to
60 °C.
5. Replace the thermostatic valve.
Irregular domestic hot
water output at the water
tap
1. The expansion vessel is defective.
2. The thermal cut-out for a system component
has been triggered (thermal control).
1. Compare the temperature between the con-
trols. The maximum temperature has priority.
2. If required, adjust the pre-charge pressure.
3. Interrupt the power supply to the product and
the heat generator. Check the thermal cut-outs
for the system components and replace these
in the event of a defect.
B Inspection and maintenance work Overview
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na-
tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of
the intervals listed.
# Maintenance work Interval
1 Check the connections for tightness (visual inspection). Annually
2 Check the temperature and pressure relief valve (by actuating it) Annually
3 Check the pressure in the expansion vessel (annual manometer). Annually
4 Check the tightness of the flange in the cleaning eye (visual inspection) Annually
5 Check the state of wear of the magnesium protection anode Annually
6 Clean the cylinder Annually
7 Check the contacts of the external current anode for corrosion Annually
8

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bulex FES 300 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info