587696
8
Zoom out
Zoom in
Vorherige Seite
1/45
Nächste Seite
4
m
m
The hexagon wrench
is required.
Packed valve handling precautions
Open the valve stem all the way out, but do not try to open it beyond
the stopper.
Securely tighten the valve stem cap with torque in the following table:
Wiring Connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminals as identified with their
respective matched numbers on the terminal block of indoor and
outdoor unit.
3. When connecting the connecting cable to the outdoor unit terminals,
make a loop as shown in the installation diagram of indoor and
outdoor unit to prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the
outdoor unit. Proceed them so that they do not touch any electrical or
metal parts.
Stripping length of the connecting cable
CAUTION
Wrong wiring connection may cause some electrical parts burn out.
Be sure to comply with local cords on running the wire from indoor
unit to outdoor unit (size of wire and wiring method, etc.).
Every wire must be connected firmly.
This installation fuse (25A) must be used for the power supply line
of this air conditioner.
If incorrect or incomplete wiring is carried out, it will cause an
ignition or smoke.
Prepare the power supply for exclusive use with the air conditioner.
This product can be connected to the mains.
Connection to fixed wiring: A switch which disconnects all poles
and has a contact separation of at least 3 mm must be
incorporated in the fixed wiring.
NOTE : Connecting cable
Wire type : More than H07RN-F or 245 IEC66
Gas side 30 to 42 N·m
(9.52 mm) (3.0 to 4.2 kgf·m)
Liquid side 16 to 18 N·m
(6.35 mm) (1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Gas Leak Test
Check places for
the outdoor unit.
Electric parts cover
Valve cover
Check the flare nut connections for the gas leak with a gas leak
detector or soap water.
OTHERS
Model 38VYX025-R 38VYX035-R
Power source 50/60 Hz, 220 – 240 V Single phase
Maximum running current 8A 11A
Plug socket & fuse rating 25A
Power cord H07RN-F or 245 IEC66 (1.5 mm
2
or more)
Check places for
the indoor unit.
When two indoor units are installed in the separated rooms, it
is not necessary to change the selector switches.
Remote control selector switch
When two indoor units are installed in the same room or
adjacent two rooms, if operating a unit, two units may receive
the remote control signal simultaneously and operate. In this
case, the operation can be preserved by setting either one
indoor unit or remote control to B setting. (Both are set to A
setting in factory shipment.)
The remote control signal is not received when the settings of
indoor unit and remote control are different.
There is no relation between A setting/B setting and A room/B
room when connecting the piping and cables.
Setting of Remote Control
Selector Switch
10
L3N
30
10
40
Connecting cable
Earth line
GB - 4
1
2
3
LN
Connecting cable
Earth lin
e
Terminal block
8

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Carrier 38VYX025-R wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info