583651
18
Zoom out
Zoom in
Vorherige Seite
1/188
Nächste Seite
18
Cooling Operation
The 48/50PG and 48/50PM units cooling operation consists of:
demand, mode determination, staging request to satisfy the
demand, and handling a request with the units resources. These
resources can include compressors, an economizer, and a reheat
coil. This section covers mechanical cooling. For economizer and
reheat cooling, refer to the Economizer and Humidimizer
sections, respectively. The unit enters a cooling mode based on a
demand, decides how to satisfy the demand, executes its plan, and
then leaves the cooling mode.
Cooling Mode Control
The cooling HVAC mode (Run StatusMODEHVAC=3) has
six different expandable texts: Cooling, Free Cooling, Unoccupied
Free Cooling, Reheat1, Reheat2, or Reheat1/Reheat2. These are all
part of a general cooling mode and resemble the specific type of
cooling that is being performed at any given time. All types of
cooling are still performed under the general cooling function, and
the expanded text is for user reference only. The control will
display if it is ok to select the cooling mode (Operating Modes
COOLOK.CL= Yes).
Thermostat Control
For the unit to enter cooling mode, three things must be true: the
indoor fan must be ok to use, the mode changeover time guard
must be expired, and there must be a cooling demand (Y1, Y2, or
reheat demand). The unit will remain in cooling until the cooling
demand is dropped or if any of the above conditions turn false. If
only a reheat demand exists and a heat demand (W1, W2) occurs,
the unit will end cooling. The cooling mode can not officially end
until all compressors are off.
Space Sensor Control
For the unit to enter cooling mode, four things must be true: the
indoor fan must be ok to use, the mode changeover time guard
must be expired, the unit must have a valid space temperature, and
there must be a cooling or reheat demand. The unit will remain in
cooling for at least one minute and until the cooling demand drops
below 0.5F or if any of the above conditions turn false. If only a
reheat demand exists and the heat demand becomes greater than the
Reheat Heat Setpoint Deadband (SetpointsRH.HB), the unit will
end cooling. The cooling mode can not officially end until all
compressors are off.
Staging Control
Once the unit is in a cooling mode, it must decide what the demand
is and how to satisfy it. If an economizer is installed and can be
used for cooling (Operating ModesCOOLOK.EC= Yes), the
unit will use it first (see economizer section for its operation). If
the economizer can not be used or additional cooling is needed, a
mechanical cooling check is performed. OK to use Compressors?
(Operating ModesCOOLOK.MC), will be set to yes when
compressors are enabled and not locked out. Based on the unit
control configuration, requested cooling stages (Run Status
COOLREQ.C) will be determined then passed to compressor
control to actually add the cooling stages.
Thermostat Control
There are two ways of requesting stages when thermostat control is
enabled, Traditional Thermostat control or Adaptive control.
Traditional Thermostat control is used if the Thermostat Control
Type (T.CTL) is set to 1, 2, or 3 and the economizer is not
available for free cooling. If Thermostat Control (T.CTL) is set to
0 or any time the economizer is available for free cooling, the unit
will use Adaptive control for staging.
T.CTL = 0 (Adaptive Control)
Stage timers, Supply air trend, and supply air temperature limits
apply when determining the request for stages. The first request
(REQ.C=1) comes immediately when the Y1 input is active. The
Cool Stage Increase Time (ConfigurationCOOLC.INC) or
the Cool Stage Decrease Time (ConfigurationCOOLC.DEC)
has to expire before another stage can be added or a stage can be
subtracted. The SupplyAir Trend (Operating
ModesCOOLSA.TR) decides if the next stage can be
requested or should be subtracted based on the Y2 input status.
For 48/50PG16 units, the supply air trend will allow up to 2
requested stages for just the Y1 input and allow up to 3 requested
stages for an Y1 and Y2 input. If the Y1 and Y2 inputs are
dropped, the supply air trend is not considered because cooling is
no longer needed. If at any time the SupplyAir Temperature
(SAT) falls below the Minimum Supply Air Temperature Upper
Level (ConfigurationCOOLSATSAT.U), the requested
stages will not be allowed to increase. If at any time the SAT falls
below the Minimum Supply Air Temperature Lower Level
(ConfigurationCOOLSATSAT.L), the requested stages will
be reduced by one without honoring C.DEC. If SAT.L and SAT.U
are configured so that they are close together, the last stage of
compressor might cycle rapidly, slowed only by its minimum on
and offtime requirements.
T.CTL = 1 (1 Stage Y1)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request one
stage. Y2 will request all stages.
T.CTL = 2 (2 Stage Y1)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request two
stages on 48/50PG16 units and one stage for all other units. Y2
will request all stages.
T.CTL = 3 (Digital)
Stage timers, Supply air trend, and supply air temperature limits do
not apply when determining the request for stages. Request staging
will follow the thermostat inputs directly. Y1 will request one
stage. Y2 will request two stages. Y1 and Y2 will request three
stages on 48/50PG16 units and two stages for all other nits.
48/50PG and PM
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Carrier 48 50PG C03-14 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info