12 Installation
4.2 Mounting the evaporative module
4.2.1 Notes on positioning the evaporative module
The design and dimensioning of the AHU/air duct as well as the location of the evaporative module
inside the duct are determined, recorded and set compulsory when planning the entire system. Prior to
installation, however, make sure the following criteria have been taken into consideration:
The AHU/air duct oor must be designed with a loading capacity capable of supporting the evapora-
tive module’s weight. The weight of the evaporative module can be found on the rating plate.
In the area where the evaporative module is installed the oor of the AHU/air duct must offer a plane
support (lengthwise and crosswise).
The evaporative module must be installed in a waterproof section of the AHU/air duct.
Downstream, directly after the evaporative module a drain pan with provision for running water
to waste must be installed. The drain must be connected via a drain trap to the waste water line of
the building. The drain trap must be sufciently high and must be lled with water prior to commis-
sioning, so that the drain trap is not emptied by the air pressure in the duct. The drain pan and the
drain trap must be accessible for cleaning and disinfection as part of the periodic maintenance of
the system.
For installation and maintenance sufciently large access doors before and after the evaporative
module must be available in the AHU/air duct.
The supply air must be ltered. We recommend to install an air lter with quality standard F7 (EU7)
or better before the evaporative module. If no air lter or an air lter with lower quality is installed an
increased maintenance will result.
An even air ow over the full cross section of the evaporative module must be guaranteed. If
necessary, rectiers or perforated plates must be installed.
The evaporative module must be positioned on upstands (supplied) to allow to install the drain pipe
with a downslope through the side wall of the AHU/air duct.
In case of low ambient temperature the AHU/air duct must be insulated to prevent the moist air from
condensing inside the duct.
If the AHU is equipped with a heater, make sure it is at least 600 mm (24") away from the evapora-
tive module.
If the face velocity exceeds 3.5 m/s (689 fpm), the optional droplet separator cassettes must be
installed.
Appropriate clearance must be available for the hydraulic module (and associated plumbing) when
installing externally.
12

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Condair ME Control wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info