TDMA CONTROL 601/701:
16
Published 07/2007
Maximum: 2...50 k W
Boiler Capacity
The maximum boiler capacity for modulated boiler regula-
tion is set here.
0 V : 0...50 k W
Boiler Capacity
The boiler capacity at 0V can be set at this point.
10 V : 2...50 k W
Boiler Capacity
The boiler capacity at 10V can be set at this point.
P - P A R A : 0...50.0
Regulator Parameter
T n : 0...500.0 S e c
Regulator Parameter
The „P“ and „I“ parameters of the 0 to 10 volt output can
be set here.
Example: The thermal capacity of the Firma Giersch Giega
Star „Therme“ Boiler
(1) Boiler capacity max:
30 kW
(2) Boiler capacity min:
10 kW
(3) 0V:
0 kW
(4) 10V:
30 kW
P-Parameter:
10
I-Parameter:
15s
If the boiler target temperature is either exceeded or not
achieved the capacity of the „Therme“ will be decreased or
increased until the target temperature is reached.
ATTENTION:
Modulated boiler operation is only suitable for boilers
which set their operational capacity above 0 – 10V and
are not automonously modulated.
Pump Revolutions
minimum : 100 %
The minimum pump speed is set here. The boiler or ther-
mal store loading pump is controlled so that the target
boiler temperature is achieved. For modulated boiler op-
eration the pump speed of the loading pump is always
100 %.
Minimum running time
Boiler : 0...30 min.
The minimum boiler running time is set here, although the
maximum allowable boiler temperature will still activate
the safety shutdown.
Back up running time
Boiler pump: 0...20 MIN
The extended running time of the boiler pump is set here.
Extended running time
Thermal store pump: 0...20MIN
The extended running time of the thermal store loading
pump is set here.
ADVICE:
It is imperative to follow the operating instructions of
the boiler manufacturer when using the boiler regulat-
ing functions.
Boiler regulating: Input - Function – Output
Input
Function
Boiler temperature sensor
(Art. N
o
. RE 046)
Maximum temperature
Minimum temperature Boiler
pump
Thermal store loading pump
Output: Boiler on/off, Boiler or Thermal store loading pump
2.6.2 Solid Fuel Boiler Pump
Solid Fuel Boiler
Minimum Temperature:30...80°C
When the solid fuel boiler temperature sensor records the
minimum temperature the „solid fuel boiler“ function is ac-
tivated. The solid fuel boiler will run until the minimum
temperature is exceeded by 2K (the 2K hysteresis is set in
the factory).
Solid Fuel Boiler:
Difference: 2...24 K
This function is used to set the temperature difference by
which the solid fuel boiler temperature sensor must be
higher than the „solid fuel boiler thermal store temperature
sensor“ so that the „Solid Fuel Boiler“ function is activated.
The 2K hysteresis is set in the factory.
Boiler OFF when Solid Fuel Boiler ON?
Yes / No
If this function is set to „Yes“, then the boiler (e.g. oil or
gas) will switch off when the thermal store is being loaded
via the solid fuel boiler.
Solid Fuel Boiler Regulating: Input - Function – Output
Input
Function
16

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Consolar Control 601 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info