743662
62
Zoom out
Zoom in
Vorherige Seite
1/63
Nächste Seite
TDMA CONTROL 601/701:
62
Published 07/2007
7 Problems and Solutions
Problem:
Cause:
Remedy:
Indicator
.. flashing and sensor fault indi-
cated.
Sensor is interrupted or short circuited.
Check sensor fitting and replace sensor if
necessary.
Regulator is not set correctly.
Check whether a function is activated even
though there is no sensor connected. Deac-
tivate the function.
Solar pump
. ... doesn’t run.
The regulator doesn’t switch the solar
pump on, even though there is sufficient
solar energy to store.
This may not be a fault! The regulator has
paused the solar pump operation as pro-
grammed. See the Technical Documentati-
on under „Solar Pump Operation“.
The solar pump is defective or is incor-
rectly installed.
Test the connection and replace the pump
if necessary.
... switches off because the tempera-
ture in the collector is too high, al-
though the upper thermal store tem-
perature has not reached 90 °C.
The flow volume has been incorrectly
set resulting in too high a difference
between the collector inflow and out-
flow temperatures.
Check the flow volume reading on the Ta-
cosetter or CONTROL601/ 701 (only if
using flow volume measuring to measure
yield). The flow volume must be set at 25
litres per hour and square meter.
Incorrect collector sensor securing. The
absorber temperature is incorrectly
measured.
The sensor should be fitted to the furthest
possible absorber plate, close to the ab-
sorber pipework, so that it receives the
same insolation levels. See also the instal-
lation instructions.
No hotwater
The regulator is incorrectly set.
Check the hot water temperature and time
programme and reset as necesssary.
Temperature sensor or thermal store
loading pump is defective.
Replace sensor or pump.
Heating system:
... Room temperature is too high
when the external temperature is
low or to low when the external
temperature is high.
Heating graph gradient or curvature is
incorrectly set.
Check the regulator settings and reset as
necessary.
...Rooms are cold even though the
boiler is running.
Heating pump is not functioning.
Check the connection and replace the
pump if necessary.
Regulator is incorrectly set.
See the Technical Documentation under
„Operating the Heating and Boiler“ Func-
tions.
If hot water demand has been priori-
tized, the thermal store is loaded as the
priority function and the heating circuit
mixer is switched off.
Deactivate the priority setting if not re-
quired.
Individual menu points or function
options do not show in the display.
The relevant function has not been cho-
sen.
If necessary, activate the function in the
System Variations menu.
62

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Consolar Control 601 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info