De Dietrich Gas 310/610 ECO
Gas 610 Temperature based 68 194
o
F [20-90
o
C] set the value of the boiler control operation
parameter to . To set the ratio between voltage and the desired flow temperature (see par. 13.2.5
and fig. 21)
0 to 0.9 Volt = boiler off
1 Volt = Flow temperature set point 50
o
F [10
o
C]
8 Volts = Flow temperature set point 176
o
F [80
o
C]
Output basedfixed parameters (20 to 100%), set the value of the boiler control setting parameter
to (see fig. 22)
8.6.6 2-Stage control (2 X no volt switched relays)
The heat output on each boiler module stages between the minimum and the maximum value based on
the set flow temperature, terminal connections X29-9 and X29-10. Set the value of each boiler control
operation parameter to (on/off).
8.6.7 4-Stage High/low control (4 x no volt switched relays)
The heat output is controlled between part load (50%, adjustable) and full load by means of a 4-stage
controller, terminal connection X29-9 and X29-10 low fire; X29-7 and X29-8 high fire.
Set the
value of each boiler control operation parameter to . The output percentage on which the
boiler runs on low fire can be adjusted with parameter (low fire start point as percentage) in the setting
mode. The ‘high fire’ percentage is dependent of the maximum adjusted output, see setting mode,
parameter
(maximum output). During this ‘high’ state modulation on adjusted flow temperature is
released.
8.7 Other inputs
8.7.1 Shut down input
As standard each boiler module is supplied with a shut down interlock carrying a 24 Volt AC boiler control
circuit. This input does not require manual re-set.
Any external devices required to stop the boiler (e.g. limit switches of throttling valves, minimum gas
pressure switches) should be wired in series and connected to terminals X29-5 and X29-6, breaking the
circuit will activate the safety interlock and put the boiler into a shut-off condition with code . If
this input is being used, the wire bridge must first be removed.
8.7.2 Lock-out input
As standard each boiler module is supplied with a lock out interlock carrying a 24 Volt AC boiler control
circuit. This input requires manual re-set if activated.
Any external devices required to stop the boiler (e.g. maximum gas pressure switch) must be volt free and
should be wired in series and connected to terminals X29-1 and X29-2. Breaking the circuit will activate
the safety interlock and put the boiler into a lock out condition, failure code  requiring manual
intervention to re-set it. If this input is being used, the wire bridge must first be removed.
8.7.3 External interlock
As standard each boiler module is supplied with an external interlock carrying a 24 Volt AC boiler control
circuit.
Any external devices required to prevent the boiler from operating (e.g. boiler room ventilation air flow
switch, or butterfly valve end switch) must be volt free and should be wired in series and connected to
terminals X29-3 and X29-4, breaking the circuit will prevent the boiler from starting. Boiler does not go to
lock-out. If this interlock is being used, the wire bridge must first be removed.
38

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für De Dietrich Gas 310 ECO wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info