De Dietrich Gas 310/610 ECO

Fan not operating
- Fan defective
- Fan cable is corroded, resulting in absence of voltage or control signal.

Fan operates continuously or signal
incorrect
- Check the fan cable connectors on both the fan and the automatic burner unit
side.
- Fan electronics defective
- Excessive negative chimney pressure

Max ΔT exceeded
Check;
- Flow
- System as has proper air elimination
- Water pressure in the system

Temperature sensor fault Short circuit of flow temperature sensor

Temperature sensor fault Short circuit of return temperature sensor

Temperature sensor fault Short circuit of flue gas temperature sensor

Temperature sensor fault Flow temperature sensor not connected or defective

Temperature sensor fault Return temperature sensor not connected or defective

Air pressure differential sensor short
circuited
- Check the connecting cable of the air pressure differential sensor
- Air pressure differential sensor is defective or not connected

Air pressure differential sensor open
- Check the air pressure differential sensor connecting cable for short circuiting,
etc.
- Air pressure differential sensor is defective

Temperature sensor fault Flue gas temperature sensor not connected or defective

one or more parameters are out of limits The input of the parameter(s) are incorrect

Hydraulic pressure sensor short circuited
- Check the hydraulic pressure sensor connecting cable for short circuit, etc...
- Hydraulic pressure sensor is defective

Hydraulic pressure sensor open
- Check connecting cable of the hydraulic pressure sensor for short circuit, etc...
- The hydraulic pressure sensor is defective or not connected

Maximum flue gas temperature
exceeded
Check the heat exchanger for fouling on the flue gas side

Air pressure differential sensor not
opening
Check;
- Is the air pressure differential sensor defective
- Has the wiring been short circuited
- Excessive positive chimney pressure

Weak flame ionization signal during
operation (after 4 restarts during 1 heat
demand)
- Flue gas recirculation, check venting & heat exchanger for leaks
- Insufficient air flow due to blockage
- Check the boiler settings

Boiler block temperature too high
Check; The heating pump is operating
- There is sufficient water flow through the boiler
- The water pressure is > 11 psi or 0.8 bar

Gas leak VA1 (optional)
The VPS gas leakage control has detected a leak, Check for external leaks,
otherwise replace gas valve multiblock

Gas leak VA2 (optional)
The VPS gas leakage control has detected a leak, Check for external leaks,
otherwise replace gas valve multiblock

Air pressure differential sensor fault
Air pressure differential sensor fault during pre-purge (after 4 restarts)
Check; Is the air pressure differential sensor defective
- Has the wiring short circuited
- Excessive high positive chimney pressure

Boiler block temperature > flow
temperature + hysteresis
Check; - The heating pump is operating
- There is sufficient water flow through the boiler
- The water pressure is < 11 psi or 0.8 bar

Temperature sensor fault Short circuit of boiler block sensor

Temperature sensor fault Boiler shut-off sensor is not connected or defective

Boiler block temperature too high
Check; - The heating pump is operating
- There is sufficient water flow through the boiler
- The water pressure is < 11 psi or 0.8 bar
other
codes
Control unit has internal fault
Proceed as follows with all non-listed codes
- Press the reset button once
- Check that the wiring is not short circuited
- If the fault persists, contact our service department
Table 23 Failure codes
WARNING!! Do not reset the boiler control until you can identify and have resolved the problem. Unresolved problems
could cause personal injury or damage to the boiler and controls.
61

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für De Dietrich Gas 310 ECO wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info