Neglecting to clean the circuit board
and other electronic components in a
dusty environment can lead to a risk of
overheating and ignition.
6 - MAINTENANCE AND
TROUBLESHOOTING
In order to maintain eciency and improve durability
it is advised that an annual maintenance check be
carried out by a qualied professional.
• Any work on the heat pump must be
carried out by a qualied professional.
• Observe all health and safety rules !
• Any work on the refrigerant circuit must be
carried out by a qualied professional with a
Category 1 certicate of aptitude.
• It is strictly prohibited to release refrigerant gas
into the atmosphere.
The refrigerant must be collected before any
work is carried out on the circuit.
• Switch o the heat pump water heater before
opening it.
Wait for the fan to come to a complete stop
before starting work on the appliance.
•Do not get water on any of the electrical parts.
The pressure limiting device must be operated
regularly to eliminate limescale and to check
for blockages.
• Check the condition of the corrosion-proof
anode at minimum once per year.
6.1 - Water circuit / Condensate
draining
To check that the condensates are draining correctly:
- Remove the upper cover (see §«Electrical connections»
procedure).
- Check for blockages in the drainage outlet.
- Clean the condensate recovery trough, where deposits
from the air intake may have gathered.
- Clean the exible drainage hose.
The pressure limiting device must be switched on regularly to
eliminate limescale and to check for blockages.
Check that all hydraulic connections on the heat pump water
heater are watertight.
When draining the tank, ensure that there is a large enough air
inlet at the top to avoid any depression in the tank. The following
materials and products should be avoided:
- Brushes with steel bristles or pads
- Scouring powder
- Any bleach-based product or chlorinated derivative
In case of maintenance or if taking the heat pump water
heater out of service, please respect the environmental
protection regulations regarding recovery, recycling and disposal
of consumables and components.
The only maintenance work needed on the air intake circuit is to
clean the evaporator (at least once per year and dependent on
the quality of air intake).
If using air lters check if they are clean regularly. Clean and
replace if necessary.
The fan blades are sharp-edged and may cause injury; take care
not to damage or deform them.
6.2 - Air intake circuit
It is mandatory to periodically inspect for the cleanliness and the
absence of dust deposits on the electronic circuit board and the
electrical terminals:
• of the compressor;
• of the electrical resistance ;
• of the dierent condensers.
Verify the correct tightness of all lugs. Adapt the frequency
of inspection to the air quality. In a dusty environment more
frequent maintenance and inspection is necessary, at minimum 1
time per year.
6.3 - Electrical maintenance
.../...
The refrigerant circuit containing
ammable refrigerant complies with national
gas regulations.
In case of operating on the refrigerant circuit:
1) Secure the area you will be working in
2) Inform people of the potential danger
involved in the work
3) Check that the risk of inammation is
minimised
4) Avoid working in a conned space; the area
must be suciently ventilated
5) Check the area with an appropriate leak
detector before and during the work
6) Place a CO2 dry powder extinguisher near
the work area
The R290 refrigerant in the heat pump
circuit poses no risk to the environment,
but it is ammable.
The R290 refrigerant is odourless.
Do not damage the pipes in the refrigerant
circuit.
Do not handle a flame or any other flammable
source on the inside of the appliance.
If the refrigerant is leaking, unplug the
appliance, air out the room, and contact
customer service.
Do not use any mechanical means to speed
up the defrosting process.
Do not pierce or burn the appliance: in case
of intervention on the refrigerant circuit, the
refrigerant must be recovered. .../...
- INSTALLER HEAT PUMP WATER HEATER 200 -270L AIR D/2 - MANUAL-
16
16

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex Edel 270 AIR D-2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Dimplex Edel 270 AIR D-2

Dimplex Edel 270 AIR D-2 Bedienungsanleitung - Holländisch - 48 seiten

Dimplex Edel 270 AIR D-2 Installationsanweisung - Holländisch - 48 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info