EN-8
English
11
11 Device Information
1 Type and order code LA 8AS
2Design
2.1 Degree of protection according to EN 60 529 for compact devices
and heating components IP 24
2.2 Installation location Outdoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow/return flow 1°C / °C
1. See operating limits diagram
Up to 58 / above 18
Air °C -25 to +35
3.2 Temperature spread of heating water (flow/return flow) at A7 / W35 8.9 5
3.3 Heat output / COP at A-7 / W35 2kW / ---
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting
capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: 2 °C external air temperature
and 55 °C heating water flow temperature.
5.1 / 2.5 4.9 / 2.4
at A-7 / W45 2kW / --- 4.8 / 2.0
at A2 / W35 2kW / --- 6.6 / 3.1 6.5 / 3.0
at A7 / W35 2kW / --- 8.3 / 3.7 8.2 / 3.6
at A7 / W45 2kW / --- 7.9 / 3.0
at A10 / W35 2kW / --- 8.8 / 3.8 8.7 / 3.7
3.4 Sound power level dB(A) 62
3.5 Sound pressure level at a distance of 10 m (air outlet side) dB(A) 32
3.6 Heating water flow with an internal pressure differential of m³/h / Pa 0.8 / 2700 1.4 / 9000
3.7 Air flow rate m³/h / Pa 2500
3.8 Refrigerant; total filling weight type / kg R404A / 1.9
3.9 Lubricant; total filling weight type / litres Polyolester (POE)/ 1.5
4 Dimensions, connections and weight
4.1 Device dimensions H x W x L cm 128 x 75 x 65
4.2 Device connections to heating system Inch G 1'' external
4.3 Weight of the transportable unit(s) incl. packing kg 166
5 Electrical Connection
5.1 Nominal voltage; fuse protection V / A 400 / 16
5.2 Nominal power consumption 2 A2 W35 kW 2.24 2.28
5.3 Starting current with soft starter A 19.5
5.4 Nominal current A2 W35 / cosA / --- 3.8 / 0.8 3.9 / 0.8
6 Complies with the European safety regulations 3
3. See CE declaration of conformity
7 Additional model features
7.1 Defrosting Automatic
Type of defrosting Reverse cycle
Defrosting tray included Yes (heated)
7.2 Heating water in device protected against icing 4
4. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes
7.3 Performance levels 1
7.4 Controller internal/external External