English LAK 3IMR - LAK 14ITR
12 Device information
1 Type and order code LAK 3IMR LAK 6IMR LAK 9IMR LAK 14IMR LAK 14ITR
2 Design
Heat source Air Air Air Air Air
2.1 Model Split reversible Split reversible Split reversible Split reversible Split reversible
2.2 Controller WPM WPM Econ WPM Econ WPM Econ WPM Econ
2.3 Thermal energy metering no no no no no
2.4 Installation location Indoors / out-
doors
Indoors / out-
doors
Indoors / out-
doors
Indoors / out-
doors
Indoors / out-
doors
2.5 Performance level Variable Variable Variable Variable Variable
3 Operating limits
3.1 Heating water flow / return °C up to 55 / from
20
up to 55 / from
20
up to 55 / from
20
up to 55 / from
20
up to 55 / from
20
3.2 Cooling water flow °C 7 to 25 7 to 25 7 to 25 7 to 25 7 to 25
3.3 Air (heating) °C -20 to +30 -20 to +30 -20 to +30 -20 to +30 -20 to +30
3.4 Air (cooling) °C +10 to +43 +10 to +43 +10 to +43 +10 to +43 +10 to +43
4Flow / sound
4.1 Heating water flow / internal pressure differential
in accordance with EN 14511 m³/h / Pa 0.530 / 3700 1.6 / 20000 1.6 / 20000 2.4 / 30400 2.4 / 30400
free compression Pa 66900 38800 38800 29600 29600
Minimum heating water flow m³/h / Pa 0.3 / 1200 0.75 / 8500 0.75 / 8500 0.9 / 10000 0.9 / 10000
free compression Pa 72800 68500 68500 77300 77300
4.2 Noise-power level in accordance with
EN 12102 outdoors1dB(A) 60 63 63 68 67
4.3 Sound pressure level in 10 m distance, outdoors2 1dB(A) 30 35 35 40 39
4.4 Sound power level for outdoor lowered operation 1dB(A) 51 61 61 65 64
4.5 Sound pressure level at 10 m distance
for outdoor lowered operation 1 2dB(A) 21 33 33 37 36
4.6 Noise-power level in accordance with
EN 12102 indoors dB(A) 42 42 42 42 42
4.7 Sound pressure level at a distance of 1 m indoors dB(A) 35 35 35 35 35
4.8 Air flow m³/h 3000 3600 3600 7200 7200
5 Dimensions, weight and filling quantities
5.1 Device dimensions 3indoors H x W
x D mm 694x450x240
870x655x320
694x450x240
834x950x330
694x450x240
834x950x330
694x450x240
1380x950x330
694x450x240
1380x950x330
5.2 Weight of the transport unit(s)
incl. packaging indoors / outdoors kg 21 / 51 23 / 69 23 / 69 25 / 94 25 / 116
5.3 Device connections for heating
inches G 1A G 1A G 1A G 1A G 1A
5.4 Refrigerant; total filling weight type/
kg R410A / 1.0 R410A / 1.9 R410A / 1.9 R410A / 2.38 R410A / 2.98
5.5 GWP value / CO2 equivalent --- / t 2088 / 2 2088 / 4 2088 / 4 2088 / 5 2088 / 6
5.6 Lubricant; total filling quantity type/
litres
Polyvinyl ether
(PVE) / 0.57
Polyvinyl ether
(PVE) / 0.9
Polyvinyl ether
(PVE) / 0.9
Polyvinyl ether
(PVE) / 1.3
Polyvinyl ether
(PVE) / 1.3
5.7 Volume of heating water in the outdoor component Litres 00000
5.8 Electrical pipe heater kW 2 2.4 or 64 2.4 or 642.4 or 642.4 or 64
5.9 Start-to-leak pressure, safety valve bar 2.5 2.5 2.5 2.5 2.5
6 Electrical connection
6.1 Supply voltage / fuse protection Compressor 1~/N/PE 230 V
(50 Hz) / C16 A
1~/N/PE 230 V
(50 Hz) / C25 A
1~/N/PE 230 V
(50 Hz) / C25 A
1~/N/PE 230 V
(50 Hz) / C40 A
3~/N/PE 400 V
(50Hz) / C16A
Electrical pipe heater 1~/N/PE 230 V
(50 Hz) / C10 A
1~/N/PE 230 V
(50 Hz) / C32 A
1~/N/PE 230 V
(50 Hz) / C32 A
1~/N/PE 230 V
(50 Hz) / C32 A
3~/N/PE 400 V
(50Hz) / C10A
Compressor + electrical pipe heater 3~/N/PE 230 V
(50 Hz) / C25 A
3~/N/PE 400 V
(50 Hz) / C25 A
3~/N/PE 400 V
(50 Hz) / C25 A
3~/N/PE 400 V
(50Hz) / C25A
RCD type BBBBB
6.2 Control voltage / fuse protection 1~/N/PE 230 V
(50 Hz) / C13 A
1~/N/PE 230 V
(50 Hz) / C13 A
1~/N/PE 230 V
(50 Hz) / C13 A
1~/N/PE 230 V
(50 Hz) / C13 A
1~/N/PE 230 V
(50Hz) / C13A
6.3 Degree of protection according to EN 60 529 indoors/outdoors IP 20 / IP X4 IP 20 / IP X4 IP 20 / IP X4 IP 20 / IP X4 IP 20 / IP X4
6.4 Starting current limiter Inverter Inverter Inverter Inverter Inverter
6.5 Rotary field monitoring Yes Yes Yes Yes Yes
44

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex LAK 14ITR wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info