www.glendimplex.de 452235.66.22a · FD 0106 EN-11
SI 6TU - SI 18TU English
1 Type and order code SI 14TU SI 18TU
2 Design
2.1 Model Universal Universal
2.2 controller Intern Intern
2.3 Thermal energy metering Integreated Integreated
2.4 Installation location / degree of protection according to EN 60 529 Indoors / IP 21 Indoors / IP 21
2.5 Performance levels 11
3 Operating limits
3.1 Heating water flow 1°C
1. If necessary, the operating range can be extended to a brine inlet temperature of -10 °C. In this case, the minimum brine concentration must be adjusted to 30%. (Freezing
temperature -17 C°). At brine inlet temperatures of -10 °C to -5 °C, flow temperature rising from 55 °C to 62 °C.
20 to 62 ±2 20 bis 62 ±2
3.2 Brine (heat source) °C
Antifreeze
Minimum brine concentration (-13 °C freezing temperature)1
-51 to +252
Monoethyleneglycol
25 %1
2. Operation is possible at brine inlet temperatures of up to + 35 °C. At brine inlet temperatures of +25 °C to +35 °C, flow temperature falling from 62 °C to 55 °C.
-51 to +252
Monoethylenglykol
25 %1
4 Performance data / flow rate 3
3. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and
controller should be taken into consideration. The specified values have the following meaning, e.g. B0/W35: Heat source temperature 0 °C and heating water flow temperature
55 °C. These specifications can only be achieved with clean heat exchangers. Information on maintenance, start-up and operation can be found in the respective sections of
the installation and operating instructions.
4.1 Heating water flow rate at internal pressure differential
max. (EN14511) m³/h / Pa
minimal m³/h / Pa
2.4 / 10700
1.2 / 2700
3.0 / 18000
1.5 / 4500
4.2 Heat output / COP EN 14511 EN 14511
at B-5 / W45 kW / --- 11.5 / 3.3 14.9 / 3.2
at B0 / W55 kW / --- 12.8 / 3.0 16.5 / 2.9
at B0 / W45 kW / --- 13.3 / 3.8 17.0 / 3.6
at B0 / W35 kW / --- 13.9 / 5.0 17.5 / 4.7
4.3 Sound power level to EN 12102 4dB(A) 47 50
4.4 Sound pressure level at a distance of 1 m 4 5dB(A)
4. The specified sound levels apply if the supporting feet (available as an option) are not used. If the supporting feet are used, the level can increase by up to 3db (A).
5. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35°C. The specified sound pressure
level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
35 38
4.5 Brine flow with internal pressure differential heat source m³/h / Pa 3.4 / 14000 4.3 / 21500
5 Dimensions, connections and weight
5.1 Device dimensions without connections6H x W x L cm
6. Note that additional space is required for pipe connections, operation and maintenance.
840 x 650 x 555 840 x 650 x 655
5.2 Device connections for heating system Inches G 1 1/4“ AG7
7. Flat-sealing
G 1 1/4“ AG7
5.3 Device connections for heat source Inches G 1 1/4“ AG7G 1 1/2“ AG7
5.4 Weight of the transportable unit(s) incl. packaging kg 140 163
5.5 Refrigerant; total filling weight type / kg R410A / 4.4 R410A / 5.2
5.6 GWP value / CO2 equivalent --- / t 2088 / 9 2088 / 11
5.7 Refrigeration circuit hermetically sealed yes yes
5.8 Lubricant; total filling quantity type / litres Polyolester
(POE) / 1.2 Polyolester (POE)/ 1.9
6 Electrical connection
6.1 Supply voltage; fuse protection V / A 3~ / PE 400V (50Hz) / C13A 3~ / PE 400V (50Hz) / C16A
6.2 Control voltage; fuse protection V / A 1~ / N / PE 230V (50Hz) / C13A 1~ / N / PE 230V (50Hz) / C13A
6.3 Nominal power consumption
B0 / W35 / max. power consumption 3kW 2.78 / 5.4 3.72 / 7.2
6.4 Starting current with soft starter A 23 28
6.5 Nominal current B0 / W35 / cos A / --- 5.02 / 0.8 6.71 / 0.8
7 Complies with the European safety regulations 8
8. See CE declaration of conformity
8
8 Additional model features
8.1 Heating water in device protected against freezing9
9. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes ja
8.2 Max. operating overpressure (heat source/heat sink) bar 3.0 3.0
31

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex SI 14TU wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Dimplex SI 14TU

Dimplex SI 14TU Bedienungsanleitung und Installationsanweisung - Holländisch - 36 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info