www.glendimplex.de 452235.66.22a · FD 0106 EN-7
SI 6TU - SI 18TU English
7.4.4 Hydraulic distribution system
The compact manifold and the dual differential pressureless
manifold function as an interface between the heat pump, the
heating distribution system, the buffer tank and, in some cases,
even the hot water cylinder. A compact system is used to sim-
plify the installation process, so that a lot of different compo-
nents do not have to be installed individually. Further informa-
tion can be found in the relevant installation instructions.
Compact manifold
The return sensor can remain in the heat pump, or should be in-
stalled in the immersion sleeve. The remaining empty space be-
tween the sensor and the immersion sleeve must be filled com-
pletely with heat transfer compound.
dual differential pressureless manifold
In order for the heating circuit pumps of the generator and con-
sumer circuits to supply the flow to the return sensor, this must
be installed in the immersion sleeve of the dual differential
pressureless manifold.
7.5 Electrical connection
7.5.1 General
All electrical connection work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J19; N1-J20; N1-J23 to N1-J26 and terminal strip
X3; X5.1. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be
destroyed
7.5.2 Electrical installation
1) The supply electric cable for the output section of the heat
pump (up to 4-core) is fed from the electricity meter of the
heat pump via the utility blocking contactor (if required)
into the heat pump Connection of the mains cable to the
control panel of the heat pump via terminal X1: L1/L2/L3/
PE.
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping
for all external conductors must be installed in the power
supply for the heat pump (tripping current and characteris-
tic in compliance with the device information).
CAUTION!
!
!
Ensure that there is a clockwise rotating field: With incorrect
wiring the starting of the heat pump is prevented. A
corresponding warning is indicated on the display of the heat
pump manager (adjust wiring).
2) The three-core electric supply cable for the heat pump
manager (heating controller N1) is fed into the heat pump .
Connection of the control line to the control panel of the
heat pump via terminal X2: L/N/PE.
Details on the power consumption of the heat pump are
listed on both the product information sheet and the type
plate.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking con-
tactor or be connected to the household current, as impor-
tant protection functions could otherwise be lost during a
utility block.
3) The utility blocking contactor (K22) with 3 main contacts
(1/3/5 // 2/4/6) and an auxiliary contact (NO contact 13/
14) should be dimensioned according to the heat pump
output and must be supplied by the customer.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to connector terminal X3/
A1. CAUTION! Extra-low voltage!
4) The contactor (K20) for the immersion heater (E10) of
mono energy systems (HG2) should be dimensioned ac-
cording to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K20.
5) The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the ra-
diator output and must be supplied by the customer. It is
controlled (230 V AC) by the heat pump manager via termi-
nals X2/N and X2/K21.
6) The contactors mentioned above in points 3, 4 and 5 are
installed in the electrical distribution system. The mains
cable for the installed pipe heater must be laid and secured
in accordance with the valid standards and regulations.
7) All installed electric cables must have permanent wiring.
8) The heat circulating pump (M13) is connected to terminals
X2/N and X2/M13.
9) The DHW loading pump (M18) is connected to terminals
X2/N and X2/M18.
10) The brine or well pump (M11) is connected to terminalsX2/
N and X2/M11 and PE.
11) The return flow sensor is integrated into the heat pumps
and is connected to the heat pump manager via the control
line. The return flow sensor must be installed in the immer-
sion sleeve in the manifold only when a dual differential
pressureless manifold is used. The single-core wires are
then connected to terminals X3/GND and X3/ R2.1. Bridge
A-R2 (situated between X3/B2 and X3/1 when delivered)
must then be moved to terminals X3/1 and X3/2.
12) The external sensor (R1) is connected to terminals X3/GND
and X3/R1.
13) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/GND and X3/R3.
27

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

dimplex-si-18-tu

Suche zurücksetzen

  • Ik vind de gebruiksaanwijzing niet om de pomp in te stekken: warm water, nachttarief, temperatuur … Eingereicht am 22-1-2022 13:36

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex SI 18 TU wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Dimplex SI 18 TU

Dimplex SI 18 TU Bedienungsanleitung und Installationsanweisung - Holländisch - 36 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info