www.glendimplex.de 452237.66.54a · FD 0110 EN-3
SI 35TUR English
2 Intended use of the heat
pump
2.1 Area of application
The brine-to-water heat pump is to be used exclusively for the
heating and cooling of heating water. It can be used in new or
existing heating systems. A mixture of water and frost protec-
tion (brine) is used as a heat transfer medium in the heat source
system. Borehole heat exchangers, ground heat collectors or
similar systems can be used as the heat source system.
2.2 Operating principle
Heating
The heat generated by the sun, wind and rain is stored in the
ground. This ground heatis collected at a low temperature by
the brine in the ground heat collector, borehole heat exchanger
or similar.
A circulating pump then conveys the "heated" brine to the
evaporator of the heat pump. There the heat is given off to the
refrigerant in the refrigeration circuit. This cools the brine so
that it can once again absorb thermal energy in the brine circuit.
The refrigerant is drawn in by the electrically driven compres-
sor, compressed and "pumped" to a higher temperature level.
The electrical power needed to run the compressor is not lost in
this process. Most of it is absorbed by the refrigerant in the
form of thermal energy.
Subsequently, the refrigerant is passed through the liquefier,
where it transfers its heat energy to the heating water. Depend-
ing on the set operating point, the heating water is thus heated
up to max. 62 °C.
Cooling
The functions of the evaporator and the liquefier are reversed in
the "Cooling" operating mode.
The heating water transfers its heat to the refrigerant via the liq-
uefier, which is now functioning as an evaporator. The refriger-
ant is brought to a higher temperature level using the compres-
sor. Heat passes into the brine via the liquefier (evaporator in
heating operation) and consequently into the ground.
2.3 Functional description for
integrated thermal energy
metering
The compressor manufacturer’s performance specifications for
different pressure levels are stored in the heat pump software.
Two additional pressure sensors for determining the current
pressure level are installed in the refrigerating circuit, one be-
fore and one after the compressor. The current heat output can
be calculated from the compressor data stored in the software
and the current pressure level. The integral for the heat output
over the runtime gives the quantity of thermal energy supplied
by the heat pump, which is displayed separately for heating,
domestic hot water preparation and swimming pool water
preparation on the manager display.
3Basic device
The basic device consists of a heat pump for indoor installation
wired ready for use with metal casing, switch box and inte-
grated heat pump manager. The refrigeration circuit is "hermet-
ically sealed" and contains the fluorinated refrigerant R410A in-
corporated in the Kyoto protocol. Information on the GWP
value and CO2 equivalent of the refrigerant is available in the
chapter Device information. The refrigerant is CFC-free, non-
ozone depleting and non-combustible.
All components required for the operation of the heat pump are
located in the switch box. An outside temperature sensor in-
cluding fixing accessories and a dirt trap are supplied with the
heat pump. The supply for the load current and the control volt-
age must be installed on-site.
Both the heat source system and the brine circuit manifold
must be provided on-site.
1) Switch box
2) Evaporator
3) Liquefier
4) Compressor 1
5) Compressor 2
6) Expansion valve
7) Filter dryer
8) Four-way reversing valve
1
45
6
2
7
38
19

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex SI 35TUR wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info