4 Electrical installation work for the heat pump
4.1 Electrical installation work
1) The up to 5-core electricity supply cable for the power
element of the heat pump is fed from the electricity meter of
the heat pump via the utility blocking contactor (if required)
in to the heat pump (see heat pump manual for the supply
voltage).
The power supply for the heat pump must contain an all-pole
shut-off with a contact opening distance of at least 3 mm
(e.g. utility blocking contactor, power contactor), as well as
an all-pole circuit breaker with shared triggering of all outer
conductors (release current and characteristics in
accordance with device information).
2) The three-core electricity supply cable for the heat pump
manager (heating controller N1) is fed into the heat pump
(devices with integrated controller) or to the future mounting
location of the heat pump manager (WPM).
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking
contactor or be connected to the household current, as
important protection functions may otherwise be lost during
a utility block.
3) The utility blocking contactor (K22) with 3 main contacts (1/
3/5 // 2/4/6) and an auxiliary contact (NO contact 13/14)
should be dimensioned according to the heat pump output
and must be supplied by the customer. The NO contact of
the utility blocking contactor (13/14) is looped from terminal
strip X3/G to connector terminal N1-J5/ID3. CAUTION! Low
voltage!
4) The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via
terminals X1/N and N1-J13-NO4.
5) The contactor (K21) for the flange heater (E9) in the
domestic hot water cylinder should be dimensioned
according to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X1/N and N1/J13-NO5.
6) The contactors mentioned in points 3, 4 and 5 are installed
in the electrical distribution system. The mains cables for the
heating elements should be dimensioned and protected
according to DIN VDE 0100.
7) The heat circulating pump (M13) is connected to terminals
X1/N and N1/J13-NO5.
8) The domestic hot water circulating pump (M18) is connected
to the terminals X1/N and N1/J13-NO6.
9) The return sensor is integrated into air-to-water heat pumps
for outdoor installation, and is connected to the heat pump
manager via the control cable. The return sensor must be
installed in the immersion sleeve in the manifold only when
a dual differential pressureless manifold is used. The single-
core wires are then connected to terminals X3/GND and X3/
R2.1. The link cable A-R2, which is positioned between X3/
U2 and X3/1 in delivery state, must then be switched to
terminals X3/1 and X3/2.
The demand sensor R2.2 is connected to the terminals X3/
GND and n1/J2-U2.
10) The external sensor (R1) is connected to terminals X3/GND
(ground) and N1/J2-U1.
11) The domestic hot water sensor (R3) is installed in the
domestic hot water cylinder and is connected to terminals
X3/GND (Ground) and N1/J2-U3.
When using three-phase current pumps, a power contactor can be
activated with the 230 V output signal of the heat pump manager.
Sensor cables can be extended to up to 50 m in accordance with the
dimensioning parameters.
Further information on the wiring of the heat pump manager is available
in the electrical documentation.
The communication cable is necessary for the function of air-to-water
heat pumps in outdoor installation. It must be shielded and laid
separately from the mains cables. It is connected to n1-J25. For further
information, see electrical documentation
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex WPM Econ5 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info