1 Important Information
During start-up, observe the respective national safety
regulations and the applicable VDE safety regulations,
particularly VDE 0100, as well as the technical connection
requirements of the utility companies (EVU) and network
operators!
The heat pump controller should only be operated in dry
rooms with temperatures ranging between 0 °C and 35 °C.
Ensure that no condensation forms on the device.
All sensor connecting cables with a conductor cross-section
of 0.75 mm² can be extended to a maximum of 40 m.
Sensor leads should not be installed next to power cables.
To ensure that the frost protection function of the heat pump
works properly, the heat pump controller must remain
connected to the power supply and the flow must be
maintained through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal
resistance of the measuring instrument, a voltage can also
be measured when the contacts are open. However, this will
be much lower than the mains voltage.
Terminals J1 to J11, J20, J21, J23 and the terminal strip X3
of the N1 heating controller are connected to an extra-low
voltage supply. Terminals J1 to J4, J9 to J10 and the
terminal strip X3 of the N17 cooling modul are connected to
an extra-low voltage supply. If, due to a wiring error, the
supply voltage is mistakenly connected to these terminals,
the heat pump controller will be destroyed.
2 Heat Pump Manager: Scope of Supply
The heat pump manager is available in three versions.
Integrated in the heat pump casing
Wall-mounted heat pump manager
for a heat pump heating system
Wall-mounted heat pump manager
for a heat pump system for heating and cooling (Chap. 5 on
p. 8).
The scope of supply of the wall-mounted heat pump manager
includes:
Heat pump manager with casing
3 dowels (6 mm) with screws for wall mounting
External temperature sensor
Operator's manual and operating instructions for users
Installation and start-up instructions for technicians
3 Installation
3.1 Attaching the wall-mounted heat pump manager (heating)
The controller is attached to the wall with the 3 screws and
dowels (6 mm) included in the scope of supply. The following
mounting procedure should be used to avoid soiling or damaging
the controller:
Mount the dowels for the upper fastening eye at operator
level.
Screw the screw into the dowel so that the controller can be
mounted.
Hang the controller on the upper fastening eye.
Mark the position of the side drill-holes.
Remove the controller.
Mount the dowels for the side drill-holes.
Re-hang the controller and tighten the screws.
Fig. 3.1: Dimensions of the wall-mounted heat pump manager (heating)
16

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Dimplex WPM Econ5Plus wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info