INSTALLATION MANUAL
2.12 Does appliance switch off
exactly 22 sec after
servomotor starts running?
2.19 Replacegascontrol
(thermo-electric valve does not
shut down quick enough because
of some permanent magnetism).
2.14 Does main burner go out
after 'some time'? 2.18 Can fire be switched off?
2.20 Perfect!
You have a well functioning
fire
2.16 Is flame picture OK?
2.13 Checkcrosslightingmain
burnerand2ndthermocouple
system.
Measurevoltageof2nd
thermocouple
- Check voltage in mV, 22 sec after
servomotor starts to run, c.q. just
before fire goes out. Glass window
to be mounted!
- Measure between black wire + earth
point on gas control.
- Requirement: voltage >5 mV after
rectification actions.
Voltage0mV
- 2nd couple defective.
- Cross ligting main burner very slow.
Take actions "Cross lighting too
slow" (see below), before taking any
further action!!
Voltage<1,8mV
- Cross ligting main burner too slow.
Take actions "Cross lighting too
slow" (see below), before taking any
further action!
- 2nd couple barred. Check:
- 2nd couple free of vermiculite,
chips or pebbles;
- position of logs or pebbles;
- burner holes under 2nd couple
open.
- 2nd couple defective (cross lighting
OK, but voltage creeps up too slow).
- Flames instable, see 2.15. Rectify,
before any other action is taken!!
- Burner pressure (too high or too
low).
- 2nd couple not positioned correctly
in flame.
Bend into correct position (see fig.
43).
- 2nd thermocouple positioned
correctly (see manual). Bend into
flame (only if cross lighting and
flame picture are OK!! See 2.17).
Voltage>1,8mV
- Receiver defective. Replace.
Crosslightingofmainburnertoo
slow
Measure the time in sec from start
running of servomotor till the flame
reaches the 2nd couple.
Requirement: the flame must be in
position at the 2nd couple <10 sec.
If not, check:
- 2nd couple free from vermiculite,
chips or pebbles;
- position of logs or pebbles;
- burner holes (locally) blocked.
Remove vermiculite dust.
- vermiculite missing or not evenly
distributed across burner(s);
- chips on burner;
- lack of combustion air. See 2.15.
- cross lighting in low setting
(possible when thermostat function
is used).
2.15 Check
Gassupply
- Supply pressure does not drop
away as main burner (or other
appliance) lights, causing pilot
flame to shorten.
- Burner pressure (too high or too
low).
Flamesinstable(suffocating,lack
ofair).
Dancing flames on burner.
Lack of combustion air. Check:
- flue system permissible;
- proper flue terminal used, make
should be 'DRU';
- terminal correctly sited on roof or
wall relative to obstructions;
- integrity of flueing system (no
interruptions, not barred,
cobwebs);
- air inlet guides;
- flue restrictor/damper;
- throttle rings.
See manual for specific
requirements.
PowerVent®
Possibly not enough draught. Check
if pressure difference set too high.
Consult PowerVent® installation
manual.
Pilotburner
- Pilot burner dirty. Weak pilot
flame being drawn away by
flames main burner.
Clean with compressed air.
See 2.04.
2.17 Check
Flames:toolow
- Supply pressure does not drop
away as main burner or other
appliances in the building light,
causing flames to shorten.
- Burner pressure (too low).
- False air: Check soundness glass
window gasket/ soundness of the
connection of the glass panes of
two/three sided appliances (no
slots allowed).
Flames:toohigh
- Line pressure.
- Burner pressure.
Flames:noevendistributionor
outonpartoftheburner(s)
- Position of logs or pebbles.
- Burner holes (locally) blocked.
Remove vermiculite dust.
- Vermiculite not distributed evenly
across burner(s).
- Adjustment of throttle ring(s).
Flames:tooblue/tooyellowor
sooting
- Air inlet guides.
- Flue restrictor/damper.
- Adjustment of throttle ring(s).
Flames:suffocating:lackofair
You see dancing flames on burner,
seeking for air. See 2.15.
Flamepicture'restless'
Indication of too much draught.
Check:
- adjustment of appliance damper
and air inlet guides);
- vertical flue length allowed (<12
m);
- window glass not mounted gas
tight.
PowerVent®?Check:
Possibly too much draught. Check:
- Pressure difference set too high.
- Silicon pressure measurement
hoses leaking.
Consult PowerVent® installation
manual for more info.
no no yes yes
no
yes
yes no
21
21

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für DRU Diablo Next wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von DRU Diablo Next

DRU Diablo Next Installationsanweisung - Deutsch - 36 seiten

DRU Diablo Next Bedienungsanleitung - Deutsch - 20 seiten

DRU Diablo Next Bedienungsanleitung - Englisch - 20 seiten

DRU Diablo Next Installationsanweisung - Holländisch - 36 seiten

DRU Diablo Next Bedienungsanleitung - Holländisch - 20 seiten

DRU Diablo Next Bedienungsanleitung - Holländisch - 16 seiten

DRU Diablo Next Bedienungsanleitung - Französisch - 20 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info