Table 1: If the radio link does not operate …...
Test as follows Yes NO
1 Receiver: is the round signal lamp on? Continue at 2 Check mains power supply, renew fuse inside receiver if necessary
2. Receiver: Is a channel (1...8) signal lamp flashing Duplicate address; see 4.7.1 or
Can the audible warning signal be heard?
(possibly only after 1 hour) Transmitter signal still missing; continue at 3 Continue at 5
3. Check active links: see 4.4
If the ‘learned’ channels come on? continue at 4 New learning procedure: see 4.1
4. Transmitter: is the battery OK? Continue at 5 Fit new batteries
5. Transmitter: set to 30 °C
Is the relay energised after 30 seconds (lamp comes on)? Continue at 6 No transmitter signal: continue at 7
6. Transmitter: Set to 5 °C
Is the relay switched off after approx. 30 seconds (lamp off)? Everything OK No transmitter signal: continue at 7
7. Transmitter - receiver - thermal actuator: check wiring,
if necessary Re-learn link with receiver
Can items 5 and 6 now be performed successfully? Everything OK (see 4.2 Radio link range test)
8. Reduce distance between transmitter and receiver If necessary, use the device Receiver may have a fault
to approx. 2 metres. with an additional antenna
Can items 5 and 6 now be performed successfully?
Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7 Room 8
4
3
2
1
Valve
Valve
R1
4
3
2
1
Valve
Valve
R2
4
3
2
1
Valve
Valve
R3
4
3
2
1
Valve
Valve
R4
4
3
2
1
Valve
Valve
R5
4
3
2
1
Valve
Valve
R6
5
4
3
2
1
Valve
R8
Function change over needed if thermal actuator normally open is used - see 4.8
4
3
2
1
Valve
Valve
R7
Fig. 1 Single-room control with simple thermostat; 8 rooms,
each with separate thermostat control
Room 1 Room 2 Room 3 Room 4 Room 5
4
3
2
1
Valve
Valve
R1
4
3
2
1
Valve
Valve
R2
4
3
2
1
Valve
Valve
R3
4
3
2
1
Valve
Valve
R4
4
3
2
1
Valve
Valve
R5
4
3
2
1
Valve
Valve
R6
5
4
3
2
1
Valve
R8
Function change over needed if thermal actuator normally open is used - see 4.8
4
3
2
1
Valve
Valve
R7
Fig. 2 Single-room control; one transmitter supplies signals
on various channels (several valves for 1 room); 5 rooms, each
controlled by a thermostat. Room 1 = 6 valves; room 5 = 3 valves
Room 1 Room 2 Room 3
Room 5
Room 6 Room 7 Room 8
4
3
2
1
Valve
Valve
R1
4
3
2
1
Valve
Valve
R2
4
3
2
1
Valve
Valve
R3
4
3
2
1
Valve
Valve
R4
4
3
2
1
Valve
Valve
R5
4
3
2
1
Valve
Valve
R6
5
4
3
2
1
Valve
R8
Function change over needed if thermal actuator normally open is used - see 4.8
4
3
2
1
Valve
Valve
R7
Room 4
Fig. 3 Single-room control with master/slave system
8 rooms, each controlled by a thermostat. Rooms 1 3 comply with
the internal timer, rooms 4 8 comply with the master timer
program on channel 4.
Room 1 Room 2 Room 3 Room 4 Room 5 Room 6 Room 7
4
3
2
1
Valve
Valve
R1
4
3
2
1
Valve
Valve
R2
4
3
2
1
Valve
Valve
R3
4
3
2
1
Valve
Valve
R4
4
3
2
1
Valve
Valve
R5
4
3
2
1
Valve
Valve
R6
Function change over needed if thermal actuator normally open is used - see 4.8
4
3
2
1
Valve
Valve
R7
5
4
3
R8
Pump
LN
2
1
Fig. 4 Pump logic single-room control for 7 rooms,
channel 8 for pump logic Note: a valve cannot be connected to
channel 8 if the pump logic is used.
5
4
3
2
1
R8
5
4
3
2
1
Pump
NL
Rec. 1 Rec. 2
R8
5
4
3
2
1
R8
5
4
3
2
1
R8
Pump
NL
Rec. 1 Rec. 3
5
4
3
2
1
R8
Rec. 2
Fig. 5 Pump logic with 2 rows of receivers
Fig. 6 Pump logic with 3 rows of receivers
N supplied from external source
Heat / Cool
signal for cooling,
e.g. from heat pump
4
3
2
1
R1
Fig. 7 Heating/cooling changeover
N
Heat / Cool
N
Heat / Cool
N
Heat / Cool
N
Heat / Cool
L
signal from central changeover,
e.g. heat pump
Application diagram with 4 independent receivers
Fig. 8 Heating/cooling changeover
N
HYG
Hygrostat, e.g.
Hyg 6001, SSHyg
L
5
4
3
2
1
R8
Fig. 9 Dew-point identification by hygrostat
Fig. 10 Dew-point identification
by specific dew-point sensor
TAU
Dew-point sensor =
TS 193 683
(max. 4 in parallel)
5
4
3
2
1
R8
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für EBERLE Instat 868-a8U wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von EBERLE Instat 868-a8U

EBERLE Instat 868-a8U Bedienungsanleitung - Deutsch - 4 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info