11
ENGLISH
FLUE SYSTEM
FLUE SYSTEM
(fumes duct, flue and chimney pot)
(fumes duct, flue and chimney pot)
This chapter has been drawn up pursuant to European
regulations EN 13384, EN 1443, EN 1856 and EN
1457. The installer must observe both these and any
other local regulations. This manual does not in any
way substitute such regulations.
The product must be connected to a flue system which
ensures that the fumes produced by combustion are
expelled in complete safety.
Before positioning the appliance, the installer must
check that the flue is suitable.
FUMES DUCT, FLUE
FUMES DUCT, FLUE
The fumes duct (which connects the combustion
chamber smoke outlet with the flue) and the flue itself
must, among other regulatory requirements:
receive the fumes from a single product (the outlets
of multiple appliances may not be conveyed into
a single flue)
be routed vertically for the most part
have no downwards sloping sections
preferably have a circular internal cross section, or
with a ratio of the sides of less than 1.5
terminate at roof level with a proper chimney pot:
the flue may not discharge directly on the wall
or into an enclosed space, even if the space in
question is open to the sky
be made of material with rated fire reaction class
A1 as per UNI EN 13501 or analogous national
regulations
be certified, with a chimney plate if metal
be of uniform cross section or vary in cross section
only immediately after the outlet, not at some
midpoint of its length.
THE FUMES DUCT
THE FUMES DUCT
Further to the general prescriptions for the fumes
duct and flue, the fumes duct:
may not be made of flexible metal material
must be insulated, if routed through unheated
areas or outdoors
must not be routed through rooms where the
installation of combustion heat generators is
prohibited or there is risk of fire, or that cannot be
inspected
must enable the recovery of soot and be open for
inspection
must have a maximum of 3 bends with a maximum
angle of 90°
if there is a horizontal section, it can have a
maximum length of no more than 3 metres,
depending on the draw. Note, in any case, that
long sections encourage the accumulation of dirt
and are harder to keep clean.
THE FLUE:
THE FLUE:
Further to the general prescriptions for the smoke duct
and flue, the flue:
must only be used for discharging fumes
must be correctly sized to satisfy the requirements
for fume discharging (EN 13384-1)
should preferably be insulated, in steel with a
circular internal section. If rectangular, the corners
must have a radius of not less than 20 mm, with
aratio of the internal dimensions of <1.5
must normally be at least 1.5 metres in vertical
length
must have a constant cross section
must be waterproof and thermally insulated to
ensure a good draw
preferably provide a collection chamber for
unburnt residues and condensates
if pre-existing, must be clean, to prevent fire
hazards
in general, we recommend fitting a tube inside the
existing masonry chimney if its diameter is greater
than 150 mm.
INSTALLATION
INSTRUCTIONS FOR THE SMOKE
INSTRUCTIONS FOR THE SMOKE
DISCHARGE WITH OR WITHOUT
DISCHARGE WITH OR WITHOUT
CONCENTRIC PIPE
CONCENTRIC PIPE
INSTALLER
11

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Edilkamin Dania Air Tight wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Edilkamin Dania Air Tight

Edilkamin Dania Air Tight Bedienungsanleitung und Installationsanweisung - Deutsch - 56 seiten

Edilkamin Dania Air Tight Bedienungsanleitung und Installationsanweisung - Holländisch - 56 seiten

Edilkamin Dania Air Tight Bedienungsanleitung und Installationsanweisung - Französisch - 56 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info