ENGLISH
- 27 -
INSTRUCTIONS FOR USE
HYDRAULIC CONNECTION
FLUSHING THE SYSTEM
Fit suitable gate shut-off valves to the heating system piping.
To protect the heat system from corrosive damage,
encrustations or deposits, it is important, before installation of
theappliance,toushthesystem.Thismustbecarriedoutin
accordance with UNI-CTI 8065, using suitable products such
as,forexample,SentinelX300(newsystems),X400andX800
(oldsystems)orFernoxCleanerF3.
Complete instructions are provided with the products but,
for further information, you can contact the manufacturers
SENTINELPERFORMANCESOLUTIONSLTDor
FERNOXCOOKSONELECTRONICSdirect.
Afterushingthesystem,toprotectitagainstcorrosionand
deposits,werecommendusinginhibitorssuchasSentinel
X100orFernoxProtectorF1.
It is important to check the concentration of the inhibitor after
eachsystemmodicationandduringeachmaintenancecheck,
following the manufacturers instructions (suitable tests are
available at retailers).
The safety valve bleed must be connected to a collection funnel
to channel any purging during intervention.
Information:
Failure to ush the heating system or to add an adequate
inhibitor invalidates the warranty of the equipment and of
other accessories such as pumps and valves, for example.
FILLING THE SYSTEM
Filling must be done slowly so as to allow air bubbles to
come out through the appropriate vents, located on the heating
system.
For closed circuit heating systems, the load pressure of the
systeminacoldstateandthepre-inationpressureofthe
expansiontankmustbethesame.
•Inopenvesselheatingsystems,directcontactbetweenthe
circulating liquid and the air is enabled.
During the heating season, the end user must regularly check
thelevelofcirculatingwaterintheexpansiontank.
The recirculation system water content must be constantly
maintained.
Regular monitoring of the water level should be carried out
every 14 days to maintain an almost constant water content.
Ifadditionalwaterisrequireditmustthellingprocess
must be carried out, when the boiler stove is cooled to room
temperature.
These precautions are designed to prevent the onset of thermal
stress in the steel body of the boiler.
•Insystemsequippedwithanexpansiontank,thewater
pressure in the stove boiler - when the system is cold - must not
be lower than 0.3 bar;
•Thewaterusedforllingtheheatingsystemmustbe
decontaminated and contain no air.
Caution!
Do not mix the heating water with anti-freeze or anti-
corrosion agents in the wrong concentrations!
This can damage the seals and cause noises to occur during
operation.
The manufacturer is not liable in the event of damage to
people or property caused by failure to comply with the
above.
Once all the hydraulic connections are in place, proceed to
verication of the pressure seals, by lling the boiler.
This operation must be carried out with caution, adhering to the
following steps:
•opentheairreleasevalvesontheradiators,boiler,andinthe
system;
•graduallyopenthesystemwatertap,makingsurethatany
automatic air vent valves installed in the system are working
properly;
•closetheventvalvesontheradiatorsassoonaswaterleaks
out;
•checkonthebuilt-insystemmanometerthatthepressure
reaches about 1 bar (only applies to closed vessel systems -
check local regulations or standards to ensure that they allow
it); for open vessel systems, water make-up is automatic via
the vessel itself;
•closethesystemwatertapandthenagainreleasetheair
through the air release valves on the radiators;
•checkthetightnessofallconnections;
•afterhavingcarriedouttherstboilerignition,andbrought
the system up to temperature, stop the pump operation and
repeat the air venting operations;
•allowthesystemtocooland,ifnecessary,restorewater
pressure to 1 bar (only applies to closed vessel systems -
check local regulations or standards to ensure that they allow
it); for open vessel systems, water make-up is automatic via
the vessel itself
27

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Edilkamin Kit - R-RW-R2-RW2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info