4.0 Installation instructions cont.
4.11 Connection to a combustion air supply and exhaust system C63x not tested in conjunction with
gas boiler.
The straight air/exhaust system for connection to a combustion air supply and exhaust system must not be
longer than 2m. A maximum number of three 90° angles are permitted for the installation. If combustion air is
supplied from the shaft, it must be kept free from any dirt.
4.12 Multiple assignment of exhaust systems (not part of the delivery program)
For modular flue systems, the calculation, layout and proof of functionality by the chimney manufacturer must
be taken into consideration.
Temperature (°C)
Volume flow (m³/h)
Mass flow (g/s)
Conveyance pressure (Pa)
Ultramax PB
Max./Min.
Max./Min.
Max./Min.
Max./Min.
65
70 / 55
113 / 16
31 / 4
230 / 10
85
70 / 55
149 / 30
41 / 8
230 / 15
100
70 / 55
168 / 34
46 / 9
230 / 15
120
70 / 55
209 / 42
58 / 12
230 / 15
Flue System
The Ultramax PB Boilers have been tested using 110/150 Concentric Flue and as a result of the
examination, the appliances may be used with up to 15m of Concentric Flue Pipe plus 4 x 93 degree bends
plus a Concentric Terminal.
If planning to install a non room sealed flue; the following data will be of assistance:
Boiler Model
PB 65
PB 85
PB 100
PB120
Max Resistance of Flue
Pa
230
230
230
230
1m Length 110mm Ø PP Flue
Gas Tube
Pa
1.25
2.25
3.0
4.0
110mm Ø 93º PP Bend
Pa
1.25
2.25
3.0
4.0
110mm Ø 45º PP Bend
Pa
1.0
1.8
2.4
3.2
110mm Ø Open Termination with
Bird Mesh Guard
Pa
1.25
2.25
3.0
4.0
4.13 Ventilation / exhaust system
Applicable local regulations must be complied with when installing the exhaust system. The Ultramax PB
heating boiler must be operated with an approved exhaust system only. Customer supplied exhaust systems
must be resistant to moisture, corrosion and condensate, and must comply with all static and operational
requirements. The chimney design should be such that resistance to flow and therefore static pressure within
the system is minimised. The termination should be open with a mesh only.
The connection between flue and Ultramax PB must be sloped (3%) so that the accumulating condensate
may flow back from the exhaust pipe. This connection should have as few bends as possible. The exhaust
vent shall have inspection openings to current Standards and Codes of Practice.
4.14 Exhaust Pipes
Horizontal pipe layout must be avoided in order to avoid any puddling of condensate. You must ensure that
the various components are connected and sealed tightly. Any assembly shall use 45° bends. Vertical parts
shall be fastened with straps.
4.15 Placement and Distances
Minimum distances must be maintained in order to enable free access for operation and maintenance.
20

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Elco Ultramax PB 65 - 120 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info