C850 532015 Rev. A
LOOP 1
LOOP 2
mm
mm
Loop
Perimeter
Nr. of
Windings
less than
3 m
6
from 3 to
4 m
5
from 4 to
6 m
4
from 6 to
12 m
3
more than
12 m
2
ENGLISH
11.5.5 SETTING THE INTEGRATED LOOP DETECTOR
The E850 features an integrated metal mass detector for the
induction detection of vehicles.
Specifications:
Galvanic separation between the detector electronics and
the loop electronics
automatic system alignment immediately following activation
continuous resetting of the frequency drifts
sensitivity independent of loop inductivity
loop work frequency adjustment
occupied loop message with LED visualisation
loop status addressable on OUT 4
Connection:
Connect the detection loops as shown in figure 28:
- Terminals 1 - 2 for LOOP 1 = loop with gate opening function;
- Terminals 3 - 4 for LOOP 2 = loop with closing and/or safety
function.
To enable operation of the connected loops, enter basic
programming level mode and set the parameters
L1 and L2
on
Y, consistent with the connected loops. If only one loop
is installed, enable only the corresponding parameter.
The loop detector operating status is shown using the display
decimal points when the automated system status is visualised
(parameter
St ).
CALIBRATION
Each time the E850 board is powered, the display shows the
automated system status and the integrated loop detector
performs the auto-calibration of the connected loops. Therefore,
perform an auto-calibration of the E850 for at least 5 seconds.
Calibration is signalled by the two flashing decimal points, as
shown in figure 43.
If one or both magnetic loops are
not installed, the loop detector remains in constant
calibration mode without causing problems to board
operation. Therefore, during visualisation of the
automated system status, one or both decimal points
will flash constantly.
Once calibration is completed, the decimal points represent the
loop statuses:
Decimal point ON = Loop ENGAGED
Decimal point OFF = Loop CLEAR
Decimal point FLASHING = Loop NOT CONNECTED or
CALIBRATING
Fig. 43
ADJUSTING THE SENSITIVITY
By adjusting the sensitivity you determine the variation of
inductivity, for each channel, which a vehicle must cause in order
to activate the corresponding detector output.
Sensitivity is adjusted separately for each channel with the use
of the parameters
S1 and S2 at basic programming level. See
section 11.5.1.
ADJUSTING THE HOLDING TIME
The holding time count starts when the loop is engaged.
When the time has elapsed, if the loop is still occupied, a new
automatic calibration is performed, in which the presence of the
metal mass on the loop no longer determines its engagement.
At the end of the new calibration the loop is considered “clear”.
The holding time can be adjusted using the parameters
h1 and
h2 in advanced programming mode.
See section 11.5.4.
ADJUSTING THE FREQUENCY and NEW BALANCING
The work frequency of each detector channel can be adjusted on
two levels using dip-switches DS1 (see fig.27).
DIP 1 ON = Loop 1 frequency LOW
OFF= Loop 1 frequency HIGH
DIP 2 ON = Loop 2 frequency LOW
OFF= Loop 2 frequency HIGH
When one of the dip-switches is changed, we recommend
performing a new calibration. If two loops are installed, select
different frequencies for each loop.
NOTES FOR MAKING THE LOOPS
The loop must be made at least 15 cm from fixed metal objects,
at least 50 cm from moving metal objects and no more than 5
cm from the surface of the final paving.
Use a standard unipolar cable measuring 1.5 mm² in diameter (if
the cable is laid below ground level directly, it must have double
insulation). Make a preferably square or rectangular loop, by
preparing a cable runner in PVC or by tracing the paving as
shown in figure 44 (corners must be cut at a 45° angle to avoid
cable breaks). Lay the cable using the number of windings shown
in the table. The two ends of the cable must be twisted together
(at least 20 times per metre) from the loop to the detector. Avoid
splicing a cable (if necessary, weld the conductors and seal the
splice using a heat-shrinking sheath) and keep it separate from
the mains power lines.
Fig. 44
25

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für FAAC C850 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info