Connecting a traffic light
With the DC 3 Standard it is possible to switch a RED traffic light directly.
1
2
3
PE
Ampel
Rot
N
L1
. . . . . . . . . .
. . . . . . . . . .
Using a DC 3 Standard without Comfort module the
RED traffic light may be connected by an additional limit
switch via (N.C.), using the terminals 54/55.
In this case the jumpers on the processor board have to
be set.
Processor board
RED traffic
light
Jumper for RED traffic light without Comfort Modul
To improve the lifetime of the traffic light bulb it is possible
to connect a resistor 39/ 2 watts in series with the bulb of
the traffic light. This resistor fits to a bulb power of 25 watts
(recommended maximum for all geba traffic lights).
If a Comfort module is connected the RED traffic light is
controlled directly.
S
t
a
n
d
a
r
d
Position of jumpers on the main board for safety edge
1. not connected: opto-electronic safety edge
connected: resistor 8,2 k
2. not connected: dead man UP - direction
connected: impuls UP - direction
3. not connected: dead man DOWN - direction
connected: impuls DOWN - direction
If the Comfort module is connected the jumpers 2 and 3
must be removed.
!
1
23
UK
AUF
AB
F
D
Version France
Only if the Comfort module is connected. The dotted lined bridges have to be
connected - door movement with pre-warning.
Before the door moves a pre-warning
- 3 seconds flashing of red traffic light - is given.
UP
DOWN
Connection safety edge (optional, only if Comfort module is connected!)
The controlling of the safety edge is managed by the Comfort module and therefore there
is no need for an additional safety edge controler device. According to the EU regulations it
is necessary to test the pneumatic safety edge on EVERY door cycle.
For this purpose the DC 3 has an intelligent testing device which recognises when the door
has finished the closing cycle.
(resp. switches from STOP with reverse to STOP - electr. safety edge).
In order to test the complete circuit of the pneumatic safety edge, it is necessary to connect
(on the inside of the pressure switch enclosure) a resistor (3,3 to 8,2 k) in series with the
normally closed contact of the pressure switch.
Connection of pressure switch (pneum. safety edge)
48
49
P
3,3 bis 8,2 k
Connecting a pneumatic safty edge (optional, only if Comfort module is connected!)
!
Check settings of Jumper on
mainboard (see page 20)
and DIP-Switches
on Comfort module !
(see backpage)
3,3 to 8,2 k
Connection of bridge on terminals 46 & 47 pre-limit switch.
46
47
Connecting the pre-limit switch
The pre-limit switch has to be mounted at the door guides, so that the closing door reaches the
pre-limit switch (e.g. extra pre-limit switch PS-ECO about 5 cm above the ground. After the pre-
limit switch has reacted the unit controlls the exact reaction of the safety edge as well as the
opening of the limit switch in DOWN direction. The pre-limit switch can also be activated by an
additional N.C. contact, the contact opens about. 5 cm above the ground.
17

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

geba-tronic-dc-3-eco---standard---de-luxe

Suche zurücksetzen

  • störungsanzeige 4 mal blinken der roten led- sicherheitsleiste betätigt Eingereicht am 8-7-2019 07:09

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Geba Tronic DC 3 ECO - Standard - de Luxe wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Geba Tronic DC 3 ECO - Standard - de Luxe

Geba Tronic DC 3 ECO - Standard - de Luxe Bedienungsanleitung - Deutsch - 18 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info