13
„TARIFF 2“ (NT/LT)
If the tariff is offering a time-controlled switching between HT and LT, please set the 2nd tariff here (see „TARIFF1“).
„T2 ON / T2 OFF“ („TARIFF 3“)
Appears only when „TARIFF 2“ is set.
Please enter the times for switching here.
Example:
T2 ON = 22:00
T2 OFF = 06:00
„TARIFF 3“ does not apply in Germany.
„DISP ON / OFF“
Time to switch the display backlight on and off.
„C-FACTOR“
Please modify this value only assisted by a specialist after measurements!
With this factor, the static measurement errors against the utility meter can be equalized.
After a longer measurement period (e.g 1 month) the consumption value of the utility meter and the measured
consumption of ENSEMBLE must be compared. If, for example, the ENSEMBLE records 2% less, the measurement
can be corrected with C_FACTOR = 1.02 for the future.
This factor is multiplied with the transmitter value.
„SET PULSE“ (for transmitter with LED sensor only)
With this setting, the value of a electronic meter’s flashing pulse (pulse rate) is defined. Usual values are, for example,
1,000 to 10,000 pulses per kWh. This information is usually printed on the electronic electricity meter.